2CTB803873R5200 ABB OVR T2 4L 40-275 P TS QS Type 2 Surge Protective Device

2CTB803873R5200 ABB OVR T2 4L 40-275 P TS QS Type 2 Surge Protective Device

ABB OVR T2 4L 40-275 P TS QS 2CTB803873R5200 is a four-pole pluggable Type 2 surge protective device for 230/400 V AC TN-S networks with a 40 kA maximum discharge current, 20 kA nominal discharge current, 275 V maximum continuous operating voltage and NO + NC auxiliary signalling contacts.

SKU: 2CTB803873R5200MPN: 2CTB803873R5200
Price
List Price £413.63 ex VAT
Your Price (ex VAT) Save 25%
£310.22 25% OFF
You save £103.41 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £310.22
Trade pricing is personalised to your account

Manufacturer Lead Time

£310.22

Why Choose the ABB OVR T2 4L 40-275 P TS QS Surge Protective Device?

The ABB OVR T2 4L 40-275 P TS QS, order code 2CTB803873R5200, is a four-pole, pluggable Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning effects and switching events. Part of the ABB OVR range and ABB's Surge Protection Devices product group, it is designed for 230/400 V AC TN-S networks.

The OVR T2 4L 40-275 P TS QS protects four lines and provides a maximum discharge current (Imax) of 40 kA together with a nominal discharge current (In) of 20 kA using an 8/20 µs surge current waveform. Its 1.25 kV voltage protection level (Up) helps limit transient voltage reaching downstream equipment, while the 275 V AC maximum continuous operating voltage (Uc) suits standard three-phase 230/400 V AC installations.

Featuring replaceable pluggable protection modules, integrated thermal disconnection, mechanical end-of-life indication and NO + NC auxiliary contacts, this SPD supports straightforward servicing and remote status monitoring. Its compact four-module DIN-rail design makes it particularly suitable for commercial and industrial distribution boards requiring dependable Type 2 surge protection with convenient maintenance and signalling.

Key Advantages

  • Dedicated four-pole Type 2 surge protection for three-phase TN-S electrical installations.
  • 40 kA maximum discharge current (Imax) with an 8/20 µs waveform.
  • 20 kA nominal discharge current (In) for robust transient surge protection.
  • 1.25 kV voltage protection level (Up) helps reduce transient voltage stress on downstream equipment.
  • Designed for 230/400 V AC TN-S networks.
  • 275 V AC maximum continuous operating voltage (Uc).
  • Pluggable protection modules support straightforward inspection and replacement.
  • NO + NC auxiliary contacts enable remote SPD status monitoring.
  • Integrated thermal disconnection and end-of-life indication support safe, efficient maintenance.

Key Features

  • ABB OVR Type 2 surge protection range.
  • Four-pole Type 2 / Class II SPD.
  • Four protected lines.
  • 230/400 V AC rated system voltage.
  • 275 V AC maximum continuous operating voltage.
  • 40 kA Imax maximum discharge current.
  • 20 kA In nominal discharge current.
  • 1.25 kV Up voltage protection level.
  • Replaceable pluggable protection modules.
  • Integrated thermal disconnector.
  • Mechanical end-of-life status indication.
  • Integrated NO + NC auxiliary contacts for remote indication.
  • Backup protection capability up to 125 A.
  • DIN-rail mounting in a compact four-module format.

Four-Line Type 2 Surge Protection with Remote Signalling

Type 2 surge protective devices are used in low-voltage distribution systems to discharge surge currents generated by indirect lightning strikes and to limit induced or conducted transient overvoltages. Their characteristic 8/20 µs waveform makes them suitable for installation in main and sub-distribution boards where coordinated surge protection is required for sensitive downstream electrical and electronic equipment.

The OVR T2 4L 40-275 P TS QS combines four-line protection with a substantial 40 kA maximum discharge capability, replaceable protection modules and integrated remote signalling contacts. This combination makes it particularly suitable for three-phase TN-S installations where compact surge protection, straightforward maintenance and remote condition monitoring are required.

Typical Applications

  • 230/400 V AC three-phase TN-S electrical networks.
  • Main and sub-distribution boards.
  • Industrial electrical distribution systems.
  • Commercial building electrical installations.
  • Industrial control and automation panels.
  • Manufacturing and production facilities.
  • Systems requiring remote SPD status monitoring.
  • Protection of sensitive electrical and electronic equipment against transient overvoltages.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal Yes
Device Type Surge protection device
SPD Type Type 2
Poles 4-pole
Earthing System TN-S
Series OVR
Order code 2CTB803873R5200
Product group Surge Protection Devices
Product type Type 2 surge protective device
Test class Class II
Number of poles 4
Number of protected lines 4
Network type TN-S
Rated voltage 230/400 V AC
Maximum continuous operating voltage (Uc) 275 V AC
Maximum discharge current (Imax) 40 kA
Nominal discharge current (In) 20 kA
Discharge current waveform 8/20 µs
Voltage protection level (Up) 1.25 kV
Integrated thermal disconnector Yes
End-of-life indicator Yes
Auxiliary contacts NO + NC
Construction Pluggable
Maximum backup protection 125 A fuse or MCB
Rated short-circuit capability 100 kA
Protection rating IP20
Operating temperature -40 to +80 °C
Mounting DIN rail
Standards IEC 61643-11 / EN 61643-11
Dimensions (H × W × D) 95 × 71.2 × 58 mm
Net weight approx. 0.48 kg
EAN 3660308520555

Frequently Asked Questions

What is the ABB OVR T2 4L 40-275 P TS QS used for?

The ABB OVR T2 4L 40-275 P TS QS is a four-pole Type 2 surge protective device designed to protect 230/400 V AC TN-S electrical installations and connected equipment against transient overvoltages caused by indirect lightning effects and other surge events.

What is the maximum discharge current of the ABB OVR T2 4L 40-275 P TS QS?

The device has a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA, based on an 8/20 µs surge current waveform.

What voltage is the ABB 2CTB803873R5200 designed for?

The OVR T2 4L 40-275 P TS QS is designed for 230/400 V AC systems and has a maximum continuous operating voltage (Uc) of 275 V AC.

Does the ABB OVR T2 4L 40-275 P TS QS provide remote signalling?

Yes. The device includes integrated NO + NC auxiliary contacts for remote status indication, allowing the condition of the surge protective device to be monitored from another location or incorporated into a control or monitoring system.

Does the ABB OVR T2 4L 40-275 P TS QS have replaceable protection modules?

Yes. The OVR T2 4L 40-275 P TS QS uses pluggable protection modules, allowing the protection elements to be replaced while retaining the installed SPD base and associated wiring.