2CTB803873R3500 ABB OVR T2-T3 3L 20-275 P TS QS Surge Protective Device

2CTB803873R3500 ABB OVR T2-T3 3L 20-275 P TS QS Surge Protective Device

ABB 2CTB803873R3500 OVR T2-T3 3L 20-275 P TS QS is a three-line pluggable QuickSafe Type 2 and Type 3 surge protective device with 275 V AC maximum continuous operating voltage, 20 kA maximum discharge current, 5 kA nominal discharge current, 0.85 kV voltage protection level and remote signalling.

SKU: 2CTB803873R3500MPN: 2CTB803873R3500
Price
List Price £279.29 ex VAT
Your Price (ex VAT) Save 25%
£209.47 25% OFF
You save £69.82 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £209.47
Trade pricing is personalised to your account

Manufacturer Lead Time

£209.47

Why Choose the ABB OVR T2-T3 3L 20-275 P TS QS Surge Protective Device?

The ABB OVR T2-T3 3L 20-275 P TS QS 2CTB803873R3500 is a three-line combined Type 2 and Type 3 surge protective device (SPD) designed for low-voltage three-phase electrical installations. Part of ABB's OVR QuickSafe range, it provides coordinated protection against transient overvoltages caused by indirect lightning effects and switching events.

The OVR T2-T3 3L 20-275 P TS QS has a maximum continuous operating voltage Uc of 275 V AC, a maximum discharge current Imax of 20 kA and a nominal discharge current In of 5 kA. Its voltage protection level Up is 0.85 kV, providing low residual voltage for enhanced protection of sensitive downstream equipment.

ABB's QuickSafe (QS) design uses replaceable pluggable protection cartridges for straightforward maintenance, while the TS configuration adds an auxiliary contact for remote status signalling. With three protected lines and a compact 53.4 mm DIN-rail width, the 2CTB803873R3500 provides a practical combination of surge protection, serviceability and remote condition monitoring.

Key Advantages

  • Combined Type 2 + Type 3 surge protection for distribution systems and sensitive downstream equipment.
  • Three protected lines for three-phase low-voltage applications.
  • 20 kA maximum discharge current (Imax) for transient surge-current handling.
  • Low 0.85 kV voltage protection level Up helps reduce transient voltage reaching connected equipment.
  • TS auxiliary contact enables remote monitoring of surge protector status.
  • QuickSafe pluggable construction allows individual protection cartridges to be replaced efficiently.

Key Features

  • ABB OVR T2-T3 QuickSafe surge protection range.
  • Combined Type 2 + Type 3 surge protective device.
  • Three protected lines.
  • 275 V AC maximum continuous operating voltage Uc.
  • 20 kA maximum discharge current Imax using an 8/20 µs waveform.
  • 5 kA nominal discharge current In using an 8/20 µs waveform.
  • 0.85 kV voltage protection level Up.
  • QuickSafe (QS) pluggable technology.
  • Replaceable phase cartridges for simplified servicing.
  • TS remote signalling contact for external SPD condition monitoring.

Combined Type 2 and Type 3 Protection with Remote Signalling

Combined Type 2 and Type 3 SPDs are designed to provide distribution-level surge-current handling together with enhanced voltage limitation close to sensitive electrical and electronic equipment. Type 2 performance safely discharges surge current characterised by an 8/20 µs waveform, while Type 3 protection provides additional protection against transient overvoltages with a low residual voltage.

The ABB OVR T2-T3 3L 20-275 P TS QS combines 20 kA Imax, 5 kA In and 0.85 kV Up across three protected lines. QuickSafe pluggable cartridges simplify servicing, while the TS auxiliary contact allows the SPD's condition to be integrated into compatible building-management, alarm or maintenance-monitoring systems.

Typical Applications

  • Three-phase low-voltage electrical distribution systems.
  • Main and intermediate electrical distribution boards.
  • Commercial building electrical installations.
  • Industrial control and distribution panels.
  • Protection of automation and sensitive electronic equipment.
  • Installations requiring combined Type 2 and Type 3 surge protection.
  • Electrical systems requiring remote SPD condition monitoring.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal Yes
Device Type Surge protection device
SPD Type Type 2+3
Poles 3-pole
Earthing System TN-C
Series OVR T2-T3 QuickSafe
Order code 2CTB803873R3500
EAN / GTIN 3660308520661
Product group Surge Protection Devices
Product type Combined Type 2 + Type 3 surge protective device
Protected lines 3
Maximum continuous operating voltage Uc 275 V AC
Maximum discharge current Imax (8/20 µs) 20 kA
Nominal discharge current In (8/20 µs) 5 kA
Voltage protection level Up 0.85 kV
Construction Pluggable
Technology QuickSafe (QS)
Remote signalling Yes
Auxiliary contact TS remote signalling contact
Replacement phase cartridge OVR T2-T3 20-275 C QS
Replacement phase cartridge order code 2CTB803876R1200
Mounting DIN rail
Dimensions (H × W × D) 95.8 × 53.4 × 65.3 mm
Product weight 0.36 kg

Frequently Asked Questions

What is the ABB OVR T2-T3 3L 20-275 P TS QS?

The ABB 2CTB803873R3500 is a three-line combined Type 2 and Type 3 surge protective device featuring QuickSafe pluggable construction and an auxiliary contact for remote status signalling.

What are the discharge current ratings of the OVR T2-T3 3L 20-275 P TS QS?

The device has a maximum discharge current Imax of 20 kA and a nominal discharge current In of 5 kA, based on an 8/20 µs surge-current waveform.

What is the voltage protection level of 2CTB803873R3500?

The ABB 2CTB803873R3500 has a voltage protection level Up of 0.85 kV, helping limit transient voltage reaching sensitive downstream equipment.

Can the cartridges in the ABB OVR T2-T3 3L 20-275 P TS QS be replaced?

Yes. Its QuickSafe pluggable construction allows the protection cartridges to be replaced. The specified phase replacement cartridge is the ABB OVR T2-T3 20-275 C QS, order code 2CTB803876R1200.

Does the ABB OVR T2-T3 3L 20-275 P TS QS provide remote signalling?

Yes. The TS configuration includes an auxiliary contact for remote status signalling, allowing the condition of the surge protective device to be monitored by compatible external equipment.

Trusted QuickSafe Surge Protection from ABB

ABB OVR QuickSafe surge protective devices provide electrical designers, installers and maintenance professionals with coordinated transient-overvoltage protection, combining replaceable pluggable cartridges, compact DIN-rail construction and remote status signalling for practical three-phase electrical installations.