Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 2CTB803873R3400 OVR T2-T3 3L 20-275 P QS is a three-pole pluggable QuickSafe Type 2 and Type 3 surge protective device for 230/400 V AC TN-C networks with 20 kA maximum discharge current, 5 kA nominal discharge current and 0.85 kV voltage protection level.
£161.14
The ABB OVR T2-T3 3L 20-275 P QS 2CTB803873R3400 is a three-pole combined Type 2 and Type 3 surge protective device (SPD) designed for low-voltage three-phase electrical installations. Part of ABB's OVR QuickSafe range, it is intended for TN-C 230/400 V AC networks, helping protect distribution systems and sensitive downstream equipment against transient overvoltages.
The OVR T2-T3 3L 20-275 P QS has a maximum continuous operating voltage Uc of 275 V AC. It provides a maximum discharge current Imax of 20 kA and a nominal discharge current In of 5 kA using an 8/20 µs waveform, together with a low voltage protection level Up of 0.85 kV.
ABB's QuickSafe (QS) design combines pluggable construction with replaceable protection cartridges for straightforward maintenance. Mechanical indicators provide local operating-status information for each arrester, while the compact three-module design occupies just 53.4 mm of DIN-rail width, making it suitable for commercial, industrial and building distribution boards where space-efficient coordinated surge protection is required.
Combined Type 2 and Type 3 SPDs provide surge-current handling at distribution level together with a low residual voltage suitable for protecting sensitive downstream equipment. Type 2 performance is characterised by safe discharge of surge current using an 8/20 µs waveform, while Type 3 protection is intended to provide enhanced voltage limitation close to sensitive equipment.
The ABB OVR T2-T3 3L 20-275 P QS combines 20 kA Imax, 5 kA In and a low 0.85 kV Up across three protected lines. QuickSafe pluggable construction and mechanical status indication support efficient inspection and cartridge replacement throughout the surge protective device's service life.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| SPD Type | Type 2+3 | |
| Poles | 3-pole | |
| Earthing System | TN-C | |
| Device Type | Surge protection device | |
| Series | OVR T2-T3 QuickSafe | |
| Order code | 2CTB803873R3400 | |
| EAN / GTIN | 3660308519818 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 2 + Type 3 surge protective device | |
| SPD classification | Type 2 + Type 3 / Class II + III | |
| Network configuration | TN-C | |
| Protected lines | 3 | |
| Nominal system voltage | 230/400 V AC | |
| Maximum continuous operating voltage Uc | 275 V AC | |
| Maximum discharge current Imax (8/20 µs) | 20 kA | |
| Nominal discharge current In (8/20 µs) | 5 kA | |
| Voltage protection level Up | 0.85 kV | |
| Construction | Pluggable | |
| Technology | QuickSafe (QS) | |
| Status indication | Mechanical indicator for each arrester | |
| Replacement cartridge | OVR T2-T3 20-275 C QS, 2CTB803876R1200 | |
| Degree of protection | IP20 | |
| Operating temperature | −40 to +80 °C | |
| Mounting | DIN rail | |
| Width | 53.4 mm | |
| Height | 95.8 mm | |
| Depth | 65.3 mm | |
| Product weight | 0.36 kg | |
| Standards | IEC 61643-11 / EN 61643-11 |
The ABB 2CTB803873R3400 is a three-pole combined Type 2 and Type 3 surge protective device with QuickSafe pluggable construction, designed for compatible 230/400 V AC TN-C three-phase networks.
The device has a maximum discharge current Imax of 20 kA and a nominal discharge current In of 5 kA, based on an 8/20 µs surge-current waveform.
The ABB 2CTB803873R3400 has a voltage protection level Up of 0.85 kV, providing low residual voltage for enhanced protection of downstream equipment.
Yes. The QuickSafe design is pluggable and uses the ABB OVR T2-T3 20-275 C QS replacement cartridge, order code 2CTB803876R1200.
The device is designed for compatible 230/400 V AC three-phase TN-C networks and provides surge protection across three lines.
ABB OVR QuickSafe surge protective devices provide electrical designers, installers and maintenance professionals with coordinated transient-overvoltage protection, combining compact DIN-rail construction, replaceable cartridges and clear mechanical status indication for efficient three-phase electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.