Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2 3L 40-275 P TS QS 2CTB803873R2500 is a three-pole pluggable Type 2 surge protective device for 230/400 V AC TN-C networks with a 40 kA maximum discharge current, 20 kA nominal discharge current, 275 V maximum continuous operating voltage and auxiliary signalling contact.
£246.50
The ABB OVR T2 3L 40-275 P TS QS, order code 2CTB803873R2500, is a three-pole, pluggable Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning effects and switching events. Part of the ABB OVR range and ABB's Surge Protection Devices product group, it is designed for three-phase 230/400 V AC TN-C networks.
The OVR T2 3L 40-275 P TS QS provides a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA using an 8/20 µs surge current waveform. Its 1.25 kV voltage protection level (Up) helps limit transient voltage reaching downstream equipment, while the 275 V AC maximum continuous operating voltage (Uc) is suited to 230/400 V AC three-phase systems.
Featuring replaceable pluggable protection modules, ABB QuickSafe technology, mechanical status indication and an auxiliary signalling contact, this SPD combines robust surge protection with convenient local and remote monitoring. Its three-module DIN-rail format makes it well suited to industrial and commercial distribution boards where dependable three-phase surge protection and efficient maintenance are required.
Type 2 surge protective devices are installed in low-voltage distribution systems to limit transient overvoltages generated by indirect lightning effects and electrical switching operations. The ABB OVR T2 range safely discharges surge currents with an 8/20 µs waveform, helping reduce the voltage stress applied to sensitive electrical and electronic equipment.
The OVR T2 3L 40-275 P TS QS combines three-line protection with a substantial 40 kA maximum discharge capability, QuickSafe technology, replaceable protection modules and an auxiliary signalling contact. This combination makes it particularly suitable for three-phase TN-C distribution systems where compact surge protection, straightforward maintenance and remote condition monitoring are required.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| SPD Type | Type 2 | |
| Poles | 3-pole | |
| Earthing System | TN-C | |
| Device Type | Surge protection device | |
| Series | OVR | |
| Order code | 2CTB803873R2500 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| Type / test class | T2 / Class II | |
| Number of poles | 3 | |
| Protected lines | 3 | |
| Network type | TN-C | |
| Type of current | AC, 45–65 Hz | |
| Nominal system voltage | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Maximum discharge current (Imax) | 40 kA | |
| Nominal discharge current (In) | 20 kA | |
| Discharge current waveform | 8/20 µs | |
| Voltage protection level (Up) at In | 1.25 kV | |
| Response time | ≤25 ns | |
| Short-circuit withstand capability (Isccr) | 100 kA | |
| Maximum backup fuse | 125 A | |
| Maximum circuit breaker | 125 A | |
| Protection technology | QuickSafe | |
| Construction | Pluggable | |
| Status indication | Mechanical visual indicator | |
| Auxiliary contact | Yes | |
| Solid conductor range | 2.5–25 mm² | |
| Stranded conductor range | 2.5–16 mm² | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Mounting | DIN rail | |
| Dimensions (H × W × D) | 95 × 53.4 × 58 mm | |
| Net weight | approx. 0.36 kg |
The ABB OVR T2 3L 40-275 P TS QS is a three-pole Type 2 surge protective device designed to protect 230/400 V AC TN-C electrical installations and connected equipment against transient overvoltages.
The device has a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA, using an 8/20 µs surge current waveform.
The OVR T2 3L 40-275 P TS QS is designed for 230/400 V AC three-phase TN-C networks and has a maximum continuous operating voltage (Uc) of 275 V AC.
Yes. The TS version includes an auxiliary signalling contact for remote monitoring of the surge protective device's status, in addition to local mechanical status indication.
Yes. The device uses pluggable, replaceable protection modules, allowing the protection elements to be serviced while retaining the installed SPD base and associated wiring.
ABB OVR Type 2 surge protective devices combine high surge-current handling, pluggable construction, QuickSafe technology and remote signalling options to provide practical protection and condition monitoring for three-phase low-voltage electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.