2CTB803871R2300 ABB OVR T2 40-275 P QS Type 2 Surge Protective Device

2CTB803871R2300 ABB OVR T2 40-275 P QS Type 2 Surge Protective Device

ABB OVR T2 40-275 P QS 2CTB803871R2300 is a single-pole pluggable Type 2 surge protective device for 230 V AC networks with a 40 kA maximum discharge current, 20 kA nominal discharge current, 275 V maximum continuous operating voltage and 1.25 kV voltage protection level.

SKU: 2CTB803871R2300MPN: 2CTB803871R2300
Price
List Price £93.75 ex VAT
Your Price (ex VAT) Save 25%
£70.31 25% OFF
You save £23.44 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £70.31
Trade pricing is personalised to your account

Manufacturer Lead Time

£70.31

Why Choose the ABB OVR T2 40-275 P QS Surge Protective Device?

The ABB OVR T2 40-275 P QS, order code 2CTB803871R2300, is a single-pole, pluggable Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages. Part of the ABB OVR range and ABB's Surge Protection Devices product group, it is designed for use on 230 V AC networks.

The OVR T2 40-275 P QS provides a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA using an 8/20 µs surge current waveform. Its 1.25 kV voltage protection level (Up) helps limit transient voltage reaching downstream equipment, while the 275 V maximum continuous operating voltage (Uc) is suited to standard 230 V AC installations.

Featuring a replaceable pluggable cartridge and ABB QuickSafe technology, this compact SPD supports efficient installation and maintenance. With a width of just 17.8 mm and mounting on a standard 35 mm DIN rail, it integrates neatly into distribution boards, consumer units and industrial control panels.

Key Advantages

  • Dedicated Type 2 surge protection for low-voltage AC installations.
  • 40 kA maximum discharge current (Imax) with an 8/20 µs waveform.
  • 20 kA nominal discharge current (In) for robust transient surge protection.
  • 1.25 kV voltage protection level (Up) helps reduce voltage stress on downstream equipment.
  • 275 V maximum continuous operating voltage (Uc) for 230 V AC networks.
  • Pluggable protection cartridge supports straightforward servicing and replacement.
  • QuickSafe technology provides fast and reliable internal disconnection.

Key Features

  • ABB OVR Type 2 surge protection range.
  • Single-pole Type 2 SPD.
  • One protected line.
  • 230 V AC nominal voltage.
  • 275 V AC maximum continuous operating voltage.
  • 40 kA Imax maximum discharge current.
  • 20 kA In nominal discharge current.
  • 1.25 kV Up voltage protection level.
  • QuickSafe technology.
  • Replaceable pluggable protection cartridge.
  • Compact 17.8 mm module width.
  • Compatible with ABB System pro M compact installations.

Reliable Type 2 Surge Protection with QuickSafe Technology

Type 2 surge protective devices are designed to protect electrical installations and sensitive equipment against transient overvoltages, including indirect lightning-induced surges. They safely discharge surge current with an 8/20 µs waveform while maintaining a low voltage protection level to reduce electrical stress on connected equipment.

The OVR T2 40-275 P QS combines a substantial 40 kA maximum discharge capability with ABB QuickSafe technology and a replaceable pluggable cartridge. This makes it a practical choice for commercial, industrial and residential distribution systems requiring compact, serviceable Type 2 surge protection.

Typical Applications

  • 230 V AC low-voltage electrical installations.
  • Electrical distribution boards and consumer units.
  • Industrial electrical control panels.
  • Commercial building electrical systems.
  • Residential electrical distribution systems.
  • Protection of sensitive electrical and electronic equipment.
  • Secondary protection against indirect lightning and switching surges.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal No
SPD Type Type 2
Poles 1-pole
Device Type Surge protection device
Series OVR
Order code 2CTB803871R2300
Product group Surge Protection Devices
Product type Type 2 surge protective device
Number of poles 1
Protected lines 1
Nominal voltage (Un) 230 V AC
Maximum continuous operating voltage (Uc) 275 V AC
Maximum discharge current (Imax) 40 kA
Nominal discharge current (In) 20 kA
Discharge current waveform 8/20 µs
Voltage protection level (Up) 1.25 kV
Protection technology QuickSafe
Construction Pluggable cartridge
Mounting 35 mm DIN rail
Standard IEC 61643-11 / EN 61643-11
Dimensions (H × W × D) 88 × 17.8 × 58 mm
Net weight approx. 0.12 kg
EAN 3660308519580

Frequently Asked Questions

What is the ABB OVR T2 40-275 P QS used for?

The ABB OVR T2 40-275 P QS is a Type 2 surge protective device designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages, including indirect lightning-induced surges.

What is the maximum discharge current of the ABB OVR T2 40-275 P QS?

The device has a maximum discharge current (Imax) of 40 kA using an 8/20 µs surge current waveform.

What is the nominal discharge current of the ABB 2CTB803871R2300?

The OVR T2 40-275 P QS has a nominal discharge current (In) of 20 kA and a voltage protection level (Up) of 1.25 kV.

What voltage is the ABB OVR T2 40-275 P QS designed for?

The SPD is designed for a nominal voltage of 230 V AC and has a maximum continuous operating voltage (Uc) of 275 V AC.

Does the ABB OVR T2 40-275 P QS have a replaceable cartridge?

Yes. The OVR T2 40-275 P QS has a pluggable, replaceable protection cartridge, allowing the protection module to be serviced without replacing the complete installed SPD assembly.

Trusted Surge Protection from ABB

ABB OVR Type 2 surge protective devices combine robust surge current handling, compact pluggable construction and QuickSafe technology to provide practical protection for low-voltage electrical installations and sensitive equipment against transient overvoltages.