Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 2CTB803871R1200 OVR T2 40-440 P QS is a single-pole pluggable QuickSafe Type 2 surge protective device with 440 V AC maximum continuous operating voltage, 40 kA maximum discharge current, 20 kA nominal discharge current and 1.8 kV voltage protection level.
£77.24
The ABB OVR T2 40-440 P QS 2CTB803871R1200 is a single-pole Type 2 surge protective device (SPD) from ABB's OVR range, designed to protect low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and switching events. Its compact modular format makes it suitable for installation in main and sub-distribution boards.
The OVR T2 40-440 P QS has a maximum continuous operating voltage Uc of 440 V AC, a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA, based on the standard 8/20 µs surge-current waveform. Its voltage protection level Up is 1.8 kV, helping limit transient voltage reaching downstream equipment.
ABB's QuickSafe (QS) design combines pluggable construction with improved safety and convenient maintenance. The device occupies only 17.8 mm of DIN-rail width, features a response time below 25 ns and uses the replaceable ABB OVR T2 40-440 C QS cartridge, making it a practical solution for commercial, industrial and building electrical distribution systems.
Type 2 surge protective devices are designed to discharge surge currents generated by indirect lightning strikes and other transient events affecting low-voltage power distribution networks. They are typically installed in main distribution switchboards and sub-distribution boards, where they limit transient voltage before it reaches sensitive downstream equipment.
The ABB OVR T2 40-440 P QS combines a 40 kA Imax, 20 kA In and 1.8 kV Up with ABB QuickSafe technology. Its single-module pluggable design enables a worn cartridge to be replaced without changing the complete base assembly, supporting efficient maintenance throughout the installation's service life.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 1-pole | |
| Series | OVR T2 QuickSafe | |
| Order code | 2CTB803871R1200 | |
| EAN | 3660308519627 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| Arrester class | Class II | |
| Number of protected poles | 1 | |
| Compatible distribution systems | TT / TN-C / TN-S / IT | |
| Nominal AC system voltage | 400/690 V AC | |
| Maximum continuous operating voltage Uc | 440 V AC | |
| Maximum discharge current Imax (8/20 µs) | 40 kA | |
| Nominal discharge current In (8/20 µs) | 20 kA | |
| Total discharge current | 40 kA | |
| Voltage protection level Up (L-PE) | 1.8 kV | |
| Short-circuit withstand rating | 100 kA | |
| Response time | <25 ns | |
| Ground residual current | <70 µA | |
| Construction | Pluggable | |
| Technology | QuickSafe (QS) | |
| Replacement cartridge | OVR T2 40-440 C QS, 2CTB803876R0400 | |
| Mounting | 35 mm DIN rail | |
| Solid conductor range | 2.5–25 mm² | |
| Stranded conductor range | 2.5–16 mm² | |
| Maximum backup protection | 125 A | |
| Maximum installation altitude | 2000 m | |
| Fire resistance | UL 94 V-0 | |
| Dimensions (H × W × D) | 88 × 17.8 × 58 mm | |
| Net weight | 120 g | |
| Standards | IEC 61643-11 / EN 61643-11 |
The ABB 2CTB803871R1200 is a single-pole Type 2 / Class II surge protective device with QuickSafe pluggable construction, designed to protect compatible low-voltage distribution systems against transient overvoltages.
The device has a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA, both based on an 8/20 µs surge-current waveform.
The ABB 2CTB803871R1200 has a maximum continuous operating voltage Uc of 440 V AC.
Yes. The SPD has a pluggable QuickSafe construction and uses the ABB OVR T2 40-440 C QS replacement cartridge, order code 2CTB803876R0400.
The ABB OVR T2 40-440 P QS is specified for compatible TT, TN-C, TN-S and IT low-voltage distribution systems and provides a voltage protection level of 1.8 kV.
ABB OVR QuickSafe surge protective devices provide electrical designers, installers and maintenance professionals with compact, pluggable protection against transient overvoltages, combining robust surge-current capability with straightforward DIN-rail integration and servicing.