Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2-T3 20-440 P QS single-line pluggable QuickSafe Type 2 and Type 3 surge protective device for 400 V AC networks, with 20 kA maximum discharge current, 5 kA nominal discharge current and 440 V AC maximum continuous operating voltage.
£65.66
The ABB OVR T2-T3 20-440 P QS is a compact combined Type 2 and Type 3 surge protective device (SPD) designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages. Part of the ABB OVR QuickSafe surge protection range, it combines Type 2 surge-current discharge capability with the low residual voltage protection associated with Type 3 protection.
The OVR T2-T3 20-440 P QS provides a maximum discharge current (Imax) of 20 kA and a nominal discharge current (In) of 5 kA using the standard 8/20 µs waveform. Designed for 400 V AC nominal networks, it has a 440 V AC maximum continuous operating voltage (Uc) and a voltage protection level (Up) of 1.4 kV.
Its pluggable QuickSafe construction simplifies maintenance by allowing the protection cartridge to be replaced independently of the base. The single-pole format occupies only 17.8 mm of DIN-rail width, making this device particularly suitable for installation in distribution boards and close to sensitive terminal equipment where space-efficient coordinated surge protection is required.
Combined Type 2 and Type 3 surge protective devices are designed for installation in distribution systems and close to sensitive terminal equipment. Their Type 2 capability safely discharges surge currents characterised by an 8/20 µs waveform, while the Type 3 protection stage provides a low residual voltage level to help protect sensitive downstream electrical and electronic equipment.
The ABB OVR T2-T3 20-440 P QS combines these protection functions with QuickSafe technology, a replaceable cartridge and a compact single-module design. This makes it a practical solution for coordinated surge protection in industrial, commercial and building electrical installations where dependable protection and efficient use of panel space are important.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| SPD Type | Type 2+3 | |
| Device Type | Surge protection device | |
| Series | OVR T2-T3 QuickSafe | |
| ABB order code | 2CTB803871R1100 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 2 and Type 3 surge protective device | |
| Protected lines | 1L | |
| Nominal voltage (Un) | 400 V AC | |
| Maximum continuous operating voltage (Uc) | 440 V AC | |
| Maximum discharge current (Imax, 8/20 µs) | 20 kA | |
| Nominal discharge current (In, 8/20 µs) | 5 kA | |
| Voltage protection level (Up) | 1.4 kV | |
| Short-circuit current rating (Isccr) | 100 kA | |
| Maximum backup fuse | 125 A | |
| Maximum backup circuit breaker | 125 A | |
| Network types | TT / TN-S / TN-C | |
| Technology | QuickSafe | |
| Construction | Pluggable | |
| Replacement phase cartridge | OVR T2-T3 20-440 C QS | |
| Remote signalling | No | |
| Mounting type | DIN rail | |
| Dimensions (H × W × D) | 88 × 17.8 × 65.3 mm | |
| Weight | approx. 0.12 kg | |
| Standards | IEC 61643-11 / EN 61643-11 |
It is a combined Type 2 and Type 3 surge protective device designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages.
The device has a maximum discharge current (Imax) of 20 kA using an 8/20 µs surge-current waveform.
The ABB OVR T2-T3 20-440 P QS has a nominal discharge current (In) of 5 kA using an 8/20 µs waveform.
It is designed for 400 V AC nominal networks and has a maximum continuous operating voltage (Uc) of 440 V AC.
Yes. It uses a pluggable protection cartridge, allowing the cartridge to be replaced during maintenance without replacing the complete SPD base.
ABB OVR QuickSafe surge protective devices provide dependable transient overvoltage protection for low-voltage electrical systems, combining coordinated protection, compact DIN-rail installation and practical pluggable construction.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.