2CTB802345R2500 ABB OVR T2 3L 40-320 P TS U Type 2 Surge Protective Device

2CTB802345R2500 ABB OVR T2 3L 40-320 P TS U Type 2 Surge Protective Device

ABB OVR T2 3L 40-320 P TS U three-pole Type 2 pluggable surge protective device for three-phase delta systems, with 40 kA maximum discharge current, 20 kA nominal discharge current, 320 V AC MCOV and remote signalling.

SKU: 2CTB802345R2500MPN: 2CTB802345R2500
Price
List Price £394.33 ex VAT
Your Price (ex VAT) Save 25%
£295.75 25% OFF
You save £98.58 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £295.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£295.75

Why Choose the ABB OVR T2 3L 40-320 P TS U Surge Protective Device?

The ABB OVR T2 3L 40-320 P TS U is a robust Type 2 surge protective device (SPD) designed to protect three-phase delta electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning effects and switching events. Part of the ABB OVR surge protection range, this three-pole device provides coordinated protection across all three phases of a delta network.

The OVR T2 3L 40-320 P TS U provides a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA using the standard 8/20 µs surge-current waveform. It is designed for a 277 V AC nominal system voltage with a 320 V AC maximum continuous operating voltage (MCOV), providing dependable protection for compatible three-phase delta power systems.

Its pluggable construction allows the protection cartridges to be serviced or replaced without replacing the complete device base, while the TS remote signalling function enables external monitoring of SPD status. With three protected poles and a compact three-module DIN-rail format, the device is well suited to industrial distribution boards, switchboards and electrical control panels.

Key Advantages

  • Type 2 surge protection designed for three-phase delta electrical systems.
  • Three protected poles provide surge protection across all three phases.
  • 40 kA maximum discharge current (Imax) for robust transient surge handling.
  • 20 kA nominal discharge current (In) with an 8/20 µs waveform.
  • 277 V AC nominal system voltage with 320 V AC maximum continuous operating voltage.
  • 1 kV voltage protection rating helps limit transient voltage reaching downstream equipment.
  • Pluggable construction simplifies maintenance and cartridge replacement.
  • Remote signalling supports external monitoring of surge protection status.

Key Features

  • ABB OVR Type 2 surge protective device.
  • Three-phase delta network configuration.
  • 3 protected poles.
  • 40 kA Imax maximum discharge current.
  • 20 kA In nominal discharge current.
  • 277 V AC nominal system voltage.
  • 320 V AC MCOV maximum continuous operating voltage.
  • 1 kV voltage protection rating.
  • Pluggable protection cartridges for straightforward servicing.
  • Remote signalling contact for status monitoring.
  • DIN-rail mounting with a compact three-module footprint.

Reliable Surge Protection for Three-Phase Delta Networks

Type 2 surge protective devices are installed in low-voltage distribution systems to safely divert transient surge currents and limit the overvoltage reaching connected electrical and electronic equipment. The ABB OVR T2 delta range is specifically configured to provide the protection required across the three phases of a delta network and safely discharge surge currents with an 8/20 µs waveform.

With its 40 kA maximum discharge capability, 20 kA nominal discharge current and three-pole configuration, the ABB OVR T2 3L 40-320 P TS U provides effective surge protection for compatible three-phase installations. Its pluggable construction and remote signalling capability also support efficient maintenance and condition monitoring within industrial electrical systems.

Typical Applications

  • Three-phase delta electrical distribution systems.
  • Industrial distribution boards and switchboards.
  • Machinery and automation control panels.
  • Commercial and industrial electrical installations.
  • Protection of sensitive electronic and control equipment.
  • Power distribution systems requiring three-pole Type 2 surge protection.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal Yes
SPD Type Type 2
Poles 3-pole
Earthing System TN-C
Device Type Surge protection device
Series OVR T2
ABB order code 2CTB802345R2500
Product group Surge Protection Devices
Product type Type 2 surge protective device
Network configuration Three-phase delta
Number of protected poles 3
Nominal system voltage 277 V AC
Maximum continuous operating voltage (MCOV) 320 V AC
Maximum discharge current (Imax, 8/20 µs) 40 kA
Nominal discharge current (In, 8/20 µs) 20 kA
Voltage protection rating 1 kV
Arrester class Class II
Version Plug-in
Remote signalling Yes
Mounting type DIN rail
Width 53.4 mm
Height 98.5 mm
Depth 64.8 mm
Width in modular spacings 3
Weight approx. 0.36 kg
Standard UL 1449 Ed. 3

Frequently Asked Questions

What is the ABB OVR T2 3L 40-320 P TS U used for?

It is a Type 2 surge protective device designed to protect three-phase delta electrical installations and connected equipment against transient overvoltages caused by switching events and indirect lightning effects.

How many poles does the OVR T2 3L 40-320 P TS U protect?

The device provides protection for three poles, making it suitable for three-phase delta network applications.

What is the maximum discharge current of this ABB surge protective device?

The OVR T2 3L 40-320 P TS U has a maximum discharge current (Imax) of 40 kA using an 8/20 µs surge-current waveform.

What is the nominal discharge current?

The device has a nominal discharge current (In) of 20 kA using an 8/20 µs waveform.

Does the ABB OVR T2 3L 40-320 P TS U provide remote signalling?

Yes. The TS configuration provides remote signalling, enabling the operating status of the surge protective device to be monitored by an external system.

Trusted Surge Protection from ABB

ABB OVR surge protective devices provide dependable transient overvoltage protection for industrial and commercial power systems, combining high surge discharge capability with practical pluggable construction and status monitoring.