Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA068470R1 XT4V 250 MA 200 Im=1000-2000 3 pole moulded case circuit breaker with magnetic-only release, fixed installation and front terminals for motor and low voltage circuit protection.
The ABB 1SDA068470R1 is a high-performance Tmax XT4V 250 moulded case circuit breaker (MCCB) designed for motor protection in low voltage electrical systems. Part of the advanced ABB SACE Tmax XT circuit breaker range, this three-pole breaker provides robust magnetic protection for industrial motor circuits, machinery panels and power distribution applications.
This circuit breaker features an MA magnetic-only trip unit with an adjustable threshold, making it particularly suitable for motor protection applications where overload protection is provided separately by an overload relay or dedicated motor protection device. Its fixed execution with front terminals supports straightforward installation inside switchboards, control panels and motor control centres.
With a rated current of 200 A and an adjustable magnetic trip range of 1000–2000 A, the ABB 1SDA068470R1 is designed for dependable short-circuit protection in demanding industrial environments. The three-pole configuration makes it suitable for three-phase motor circuits requiring compact, reliable and high-breaking-capacity protection.
Moulded case circuit breakers such as the ABB Tmax XT4V are used to protect electrical circuits against damaging short-circuit conditions. In motor protection applications, magnetic-only MCCBs provide rapid fault interruption while allowing separate overload protection to be selected according to the motor and application requirements.
The ABB SACE Tmax XT range is widely used by panel builders, contractors and electrical engineers in industrial control panels, switchboards and motor control centres. The 1SDA068470R1 provides a compact and dependable solution where a fixed, three-pole MCCB with adjustable magnetic protection is required.
Tick the specs you need, then view products that match.
| Mounting Type | Fixed | |
|---|---|---|
| Application | Motor protection | |
| Current | 200 A | |
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 150 kA | |
| Trip Unit | Magnetic only | |
| Manufacturer | ABB | |
| Series | SACE Tmax XT | |
| Model | XT4V 250 MA 200 Im=1000...2000 3p F F | |
| Product type | Moulded case circuit breaker | |
| SKU / MPN | 1SDA068470R1 | |
| EAN | 8015644023768 | |
| Frame size | XT4 | |
| Rated frame current | 250 A | |
| Rated current | 200 A | |
| Number of poles | 3 pole | |
| Release type | Magnetic MA | |
| Magnetic trip range | 1000–2000 A | |
| Breaking capacity | Icu 415 V AC = 150 kA | |
| Installation type | Fixed | |
| Terminal type | Front terminals | |
| Application | Motor and low voltage circuit protection |
The ABB 1SDA068470R1 is used for short-circuit protection in low voltage motor circuits, industrial control panels and three-phase electrical distribution systems.
It is an ABB Tmax XT4V 250 moulded case circuit breaker with a three-pole fixed design and front terminals.
The breaker has a rated current of 200 A within the XT4 250 A frame size.
The 1SDA068470R1 uses an MA magnetic-only release, providing adjustable short-circuit protection for motor protection applications.
The adjustable magnetic trip range is 1000–2000 A, allowing the protection threshold to be set according to the circuit requirements.
ABB Tmax XT moulded case circuit breakers are trusted by panel builders, contractors and electrical engineers for reliable protection, compact installation and dependable performance in low voltage motor control and distribution systems.