ABB EPX-XT4S-E2-0403 is a 40 A three-pole moulded case circuit breaker with 50 kA breaking capacity and an Ekip LSI electronic trip unit providing long-time overload, short-time delayed and instantaneous short-circuit protection for commercial and industrial three-phase electrical distribution systems.
£1,597.96
The ABB EPX-XT4S-E2-0403 is a high-performance 40 A three-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in commercial and industrial electrical distribution systems. Featuring a 50 kA short-circuit breaking capacity and an advanced electronic LSI trip unit, this circuit breaker delivers configurable protection for demanding low-voltage applications. It belongs to the ABB Protecta Power Devices range and uses the established ABB SACE Tmax XT4S160 circuit breaker platform.
The EPX-XT4S-E2-0403 combines three electronic protection functions: long-time overload protection (L), short-time delayed short-circuit protection (S) and instantaneous short-circuit protection (I). These functions allow electrical designers to configure the circuit breaker's response to different fault conditions, helping protect cables and connected equipment while supporting coordination between upstream and downstream protective devices.
With a 40 A rated current, three-pole (3P) configuration and 50 kA breaking capacity, the ABB EPX-XT4S-E2-0403 is particularly suitable for three-phase outgoing circuits, industrial distribution panels and commercial electrical installations. Its compact XT4S construction supports efficient integration into compatible ABB Protecta Power assemblies. The product is identified by ABB order code 1SDX255179R1.
The ABB EPX-XT4S-E2-0403 uses an electronic trip unit to monitor electrical current and initiate protective tripping when an overload or short-circuit condition exceeds the configured protection thresholds. Compared with conventional thermal-magnetic releases, electronic protection offers greater flexibility when selecting protection characteristics for commercial and industrial electrical distribution systems.
The long-time (L) protection function responds to sustained overload conditions that can cause excessive heating in electrical cables and connected equipment. By monitoring current over time, the electronic release initiates tripping when its configured overload protection characteristic is exceeded. Appropriate long-time settings help protect circuit conductors while accommodating normal operating loads.
The short-time delayed (S) protection function provides short-circuit protection with an intentional delay. When properly coordinated with downstream protective devices, this function can improve selectivity by allowing the protective device closest to a fault to operate first. This may help reduce unnecessary interruption to unaffected circuits within a larger electrical distribution system.
The instantaneous (I) protection function provides rapid tripping when a sufficiently high short-circuit current is detected. This helps limit fault duration and reduce the potential effects of severe short circuits on electrical cables, distribution equipment and connected loads.
A significant advantage of the ABB Ekip LSI electronic release is the inclusion of all three protection functions: L, S and I. Unlike an LS/I trip unit, which provides long-time protection with selectable short-time or instantaneous characteristics, an LSI release provides the three distinct protection functions required for more flexible coordination strategies.
The three-pole configuration provides simultaneous switching of the three phase conductors without a switched neutral pole. This makes the EPX-XT4S-E2-0403 suitable for appropriately designed three-phase circuits where three-pole switching and protection are required. Where the installation requires neutral switching or four-pole isolation, a compatible four-pole circuit breaker should be selected instead.
The ABB SACE Tmax XT4S160 platform combines compact construction with advanced electronic protection. With a 40 A rated current and 50 kA breaking capacity, the EPX-XT4S-E2-0403 is particularly useful for circuits with relatively modest continuous current requirements but high prospective short-circuit levels. Correct selection must account for operating voltage, prospective fault current, cable ratings and protective device coordination.
| Product group | Protecta Power Devices |
|---|---|
| Series | SACE Tmax XT4S |
| Circuit breaker platform | XT4S160 |
| ABB order code | 1SDX255179R1 |
| Corresponding ABB XT4S160 circuit breaker reference | 1SDA068481R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 40 A |
| Number of poles | 3 |
| Pole configuration | Three-pole (3-phase) |
| Short-circuit breaking capacity | 50 kA |
| Ultimate short-circuit breaking capacity (Icu), corresponding XT4S configuration | 50 kA at 415 V AC |
| Trip unit technology | Electronic |
| Trip unit type | ABB Ekip LSI |
| Long-time protection (L) | Electronic overload protection |
| Short-time protection (S) | Electronic delayed short-circuit protection |
| Instantaneous protection (I) | Electronic instantaneous short-circuit protection |
| Protection configuration | LSI — long-time, short-time and instantaneous protection |
| Frame family | XT4S160 |
| Frame current class | 160 A |
| Rated operational voltage, XT4S platform | Up to 690 V AC |
| Rated insulation voltage (Ui), XT4S platform | 1,000 V |
| Rated impulse withstand voltage (Uimp), XT4S platform | 8 kV |
| Mounting arrangement | Fixed installation |
| Terminal arrangement | Front terminals |
| Operating mechanism | Manual lever with automatic protective tripping |
| Applicable product standard | IEC 60947-2 |
| Electrical system | Low-voltage AC distribution |
| Application | Commercial and industrial three-phase circuit protection |
| Installation type | Compatible electrical distribution boards and switchgear assemblies |
| Product construction | Moulded case circuit breaker |
The ABB EPX-XT4S-E2-0403 is a three-pole moulded case circuit breaker designed to protect low-voltage three-phase electrical distribution circuits against overloads and short circuits. It uses an electronic LSI trip unit and is suitable for commercial and industrial installations, including compatible ABB Protecta Power distribution boards.
The circuit breaker has a rated current of 40 A and uses the 160 A XT4S frame class. The frame rating identifies the circuit breaker platform, while the electronic release fitted to this particular configuration is rated at 40 A.
The ABB EPX-XT4S-E2-0403 has a specified 50 kA short-circuit breaking capacity. The corresponding ABB XT4S160 electronic LSI circuit breaker has an ultimate short-circuit breaking capacity of 50 kA at 415 V AC. Suitability must be checked against the installation's operating voltage and prospective fault current.
LSI identifies three electronic protection functions: L for long-time overload protection, S for short-time delayed short-circuit protection and I for instantaneous short-circuit protection. These functions allow the circuit breaker to respond to different electrical fault conditions.
An LS/I trip unit provides long-time overload protection with a choice between short-time delayed and instantaneous short-circuit protection. An LSI trip unit, as fitted to the EPX-XT4S-E2-0403, includes all three protection characteristics, offering greater flexibility for protective device coordination.
No. The EPX-XT4S-E2-0403 uses an ABB Ekip LSI electronic trip unit rather than a conventional thermal-magnetic release. Electronic protection provides configurable overload and short-circuit protection characteristics for appropriately designed electrical installations.
No. The EPX-XT4S-E2-0403 is a three-pole MCCB designed to switch and protect three phase conductors. It does not include a fourth switched neutral pole. Applications requiring neutral switching should use a suitably specified four-pole circuit breaker.
The ABB Protecta Power manufacturer order code is 1SDX255179R1. The corresponding ABB XT4S160 electronic LSI circuit breaker reference is 1SDA068481R1. The product reference EPX-XT4S-E2-0403 identifies the 40 A, three-pole, 50 kA electronic LSI MCCB.
The product belongs to the ABB SACE Tmax XT4S series and uses the XT4S160 circuit breaker platform. This is a 160 A frame-class MCCB fitted with a 40 A electronic LSI trip unit.
This MCCB is typically installed within compatible commercial distribution boards, industrial electrical panels and low-voltage switchgear assemblies. It is particularly suitable for 40 A three-phase circuits requiring electronic LSI protection and high short-circuit interruption capability.
ABB is an established manufacturer of electrical protection and power distribution equipment. The ABB Protecta Power Devices range, including the EPX-XT4S-E2-0403 three-pole electronic LSI MCCB, provides electrical contractors, panel builders and facilities engineers with flexible circuit protection solutions for commercial and industrial low-voltage distribution systems.