Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB EPX-XT5S-E1-2503 is a 250 A three-pole moulded case circuit breaker from the Protecta Power range, featuring a 50 kA breaking capacity at 415 V AC and Ekip LS/I electronic overload and short-circuit protection for industrial and commercial electrical distribution systems.
£1,435.37
The ABB EPX-XT5S-E1-2503 is a high-performance 250 A three-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in low-voltage electrical distribution systems. Featuring a 50 kA short-circuit breaking capacity and an advanced Ekip LS/I electronic trip unit, this circuit breaker delivers dependable protection for commercial, industrial and infrastructure electrical installations.
As part of the ABB Protecta Power Devices range, the EPX-XT5S-E1-2503 incorporates ABB's established SACE Tmax XT5S circuit breaker technology. Its electronic protection system provides adjustable long-time overload protection and selectable short-time delayed or instantaneous short-circuit protection, enabling electrical engineers to coordinate protective devices and improve the reliability of electrical distribution networks.
With a rated current of 250 A, a three-pole configuration and a 50 kA breaking capacity at 415 V AC, the EPX-XT5S-E1-2503 is suitable for demanding three-phase power distribution applications. Its compact 140 mm-wide XT5S frame supports efficient integration into electrical distribution boards, switchgear assemblies and ABB Protecta Power systems. The product is identified by ABB order code 1SDX255162R1.
Moulded case circuit breakers such as the ABB EPX-XT5S-E1-2503 protect electrical circuits by automatically interrupting current when overloads or short-circuit faults occur. This helps minimise the risk of damage to electrical cables, switchgear and connected equipment while improving the operational reliability of low-voltage electrical distribution systems.
The integrated Ekip LS/I electronic trip unit provides adjustable long-time overload protection and selectable short-time delayed or instantaneous short-circuit protection. The long-time function responds to sustained overcurrent conditions, while the short-circuit protection functions enable the circuit breaker to respond to electrical faults according to the selected protection settings.
The LS/I protection arrangement allows engineers to select either short-time delayed protection or instantaneous protection to suit the electrical installation. Short-time delayed protection can help achieve discrimination between upstream and downstream circuit breakers, while instantaneous protection enables rapid interruption of high short-circuit currents. Unlike an LSI trip unit, the LS/I configuration provides a choice between S and I protection rather than both functions operating independently at the same time.
Built on the ABB SACE Tmax XT5S platform, this 250 A three-pole MCCB combines high breaking capacity with a compact design. It is particularly suitable for industrial distribution boards, commercial switchgear and ABB Protecta Power installations where dependable fault protection, adjustable electronic tripping and efficient panel integration are essential.
| Product group | Protecta Power Devices |
|---|---|
| Series | SACE Tmax XT |
| ABB order code | 1SDX255162R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Circuit breaker platform | XT5S |
| Rated current (In) | 250 A |
| Number of poles | 3 |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 50 kA |
| Rated frequency | 50/60 Hz |
| Trip unit | Ekip LS/I |
| Trip unit technology | Electronic |
| Overload protection | Long-time (L) |
| Short-circuit protection | Selectable short-time delayed (S) or instantaneous (I) |
| Short-circuit performance class | S |
| Frame family | XT5 |
| Three-pole device width | 140 mm |
| Application | Low-voltage power distribution and circuit protection |
| Applicable circuit breaker standard | IEC 60947-2 |
The ABB EPX-XT5S-E1-2503 is a three-pole moulded case circuit breaker used to protect low-voltage electrical distribution circuits against overloads and short circuits. It is designed for industrial and commercial switchboards, distribution assemblies and three-phase electrical installations.
The circuit breaker has a 250 A rated current and a 50 kA ultimate short-circuit breaking capacity at 415 V AC, making it suitable for demanding electrical distribution applications requiring high fault-current interruption capability.
The Ekip LS/I electronic trip unit provides adjustable long-time overload protection (L) together with selectable short-time delayed (S) or instantaneous (I) short-circuit protection. This allows the circuit breaker protection characteristics to be adapted to the requirements of the electrical installation.
Yes. The EPX-XT5S-E1-2503 is a three-pole (3P) MCCB designed for three-phase electrical distribution systems. Its three-pole construction enables simultaneous switching of the three phase conductors.
The ABB Protecta Power order code is 1SDX255162R1. The corresponding product reference is EPX-XT5S-E1-2503, identifying the 250 A, three-pole, 50 kA XT5S moulded case circuit breaker with Ekip LS/I electronic protection.
ABB SACE Tmax XT moulded case circuit breakers are designed to provide reliable protection in modern low-voltage electrical installations. The ABB EPX-XT5S-E1-2503 combines a 250 A current rating, three-pole construction, 50 kA breaking capacity and Ekip LS/I electronic protection, making it a dependable choice for circuit protection within ABB Protecta Power distribution systems and industrial electrical infrastructure.