Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB EPX-XT2S-E1-0633 is a 63 A three-pole electronic moulded case circuit breaker from the Protecta Power Devices range, featuring a 50 kA breaking capacity at 415 V AC and an Ekip Dip LS/I electronic trip unit with configurable overload and short-circuit protection for low-voltage electrical distribution systems.
£661.37
The ABB EPX-XT2S-E1-0633 is a high-performance 63 A three-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems. Part of the ABB Protecta Power Devices range, this circuit breaker incorporates the established ABB SACE Tmax XT2S160 platform, offering electronic protection technology for commercial buildings, industrial facilities and electrical infrastructure.
Equipped with an ABB Ekip Dip LS/I electronic trip unit, the EPX-XT2S-E1-0633 provides configurable protection characteristics for electrical distribution circuits. Its electronic release incorporates long-time overload protection (L) and a selectable short-circuit protection function, allowing the use of short-time delayed protection (S) or instantaneous protection (I) according to the selected configuration. This flexibility supports electrical protection coordination and helps safeguard cables, switchgear and connected equipment against damaging fault conditions.
With a 63 A rated current, three-pole construction and 50 kA short-circuit breaking capacity, this MCCB is suitable for demanding three-phase electrical distribution applications. Its compact XT2S160 frame, electronic trip technology and fixed-mounted construction make it a practical choice for compatible ABB Protecta Power distribution boards and low-voltage switchgear assemblies where reliable circuit protection and adjustable trip characteristics are required.
Moulded case circuit breakers such as the ABB EPX-XT2S-E1-0633 protect electrical installations by automatically interrupting current during overload and short-circuit conditions. Unlike conventional thermal-magnetic circuit breakers, this model uses an ABB Ekip Dip electronic trip unit to evaluate electrical current and initiate tripping according to its configured protection settings. Its LS/I functionality provides long-time overload protection together with a selectable short-time delayed or instantaneous short-circuit protection function, allowing protection characteristics to be matched to the requirements of the electrical installation.
The ABB SACE Tmax XT2 circuit breaker family is engineered for dependable protection in modern low-voltage electrical distribution assemblies. The EPX-XT2S-E1-0633 is particularly suitable for installations requiring 63 A three-pole electronic circuit protection and a 50 kA breaking capacity at 415 V AC. Its configurable electronic release supports protection coordination between upstream and downstream devices, subject to the selected settings and ABB coordination data. Circuit breaker selection should consider operating voltage, prospective fault current, conductor characteristics, load requirements and the applicable protection study. Where the MCCB supplies a motor circuit, dedicated motor overload protection may also be necessary depending on the installation design.
| Product group | Protecta Power Devices |
|---|---|
| Product series | SACE Tmax XT |
| Frame designation | XT2S160 |
| ABB order code | 1SDX255140R1 |
| ABB base circuit breaker reference | 1SDA067802R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current (In) | 63 A |
| Number of poles | 3 |
| Rated ultimate short-circuit breaking capacity (Icu) | 50 kA at 415 V AC |
| Rated service short-circuit breaking capacity (Ics) | 50 kA at 415 V AC |
| Trip unit | Ekip Dip LS/I |
| Trip unit technology | Electronic |
| Long-time protection | L – overload protection |
| Short-time protection | S – delayed short-circuit protection, selectable |
| Instantaneous protection | I – instantaneous short-circuit protection, selectable |
| Protection configuration | LS/I |
| Frame family | XT2S160 |
| Maximum frame rating | 160 A |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Mounting type | Fixed mounting |
| Terminal arrangement | Front terminals |
| Operating mechanism | Manual operation |
| Application | Low-voltage three-phase electrical distribution |
| Installation | Compatible electrical distribution boards and switchgear assemblies |
| Applicable circuit breaker standard | IEC/EN 60947-2 |
The ABB EPX-XT2S-E1-0633 is a three-pole electronic moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for appropriately designed commercial and industrial installations requiring configurable electronic protection.
The circuit breaker has a 63 A rated current and uses the ABB Tmax XT2S160 frame, which has a maximum frame rating of 160 A. The rated current of this specific MCCB is 63 A, not the maximum rating of its frame.
The EPX-XT2S-E1-0633 has a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC. The corresponding ABB XT2S electronic breaker also has a rated service short-circuit breaking capacity of 50 kA at 415 V AC. The applicable ratings must be checked against the installation voltage and prospective fault current before selection.
LS/I identifies an electronic trip unit providing long-time overload protection (L) together with a selectable short-circuit protection function. The unit can be configured to use short-time delayed protection (S) or instantaneous protection (I). Unlike an LSI trip unit, LS/I does not provide independently active S and I functions simultaneously.
An Ekip LS/I electronic MCCB uses an electronic release to evaluate current and apply configurable overload and short-circuit protection settings. A TMA thermal-magnetic MCCB uses thermal and magnetic trip elements to respond to electrical faults. Electronic protection provides additional flexibility when configuring trip characteristics and coordinating protective devices within an electrical distribution system.
ABB SACE Tmax XT moulded case circuit breakers are engineered to deliver dependable overload and short-circuit protection in modern electrical distribution systems. The ABB EPX-XT2S-E1-0633 combines a 63 A rating, three-pole construction, 50 kA breaking capacity at 415 V AC and configurable Ekip Dip LS/I electronic protection in a compact circuit breaker suitable for commercial, industrial and infrastructure power distribution applications.