1SDX255118R1 ABB EPX-XT2S-TM1604 160A 4-Pole 50kA TMA MCCB

1SDX255118R1 ABB EPX-XT2S-TM1604 160A 4-Pole 50kA TMA MCCB

ABB EPX-XT2S-TM1604 is a 160 A four-pole moulded case circuit breaker with 50 kA breaking capacity and an adjustable thermal-magnetic trip unit, designed for overload and short-circuit protection in low-voltage electrical distribution systems.

SKU: 1SDX255118R1Alt SKU: EPX-XT2S-TM1604MPN: 1SDX255118R1
Price
List Price £974.08 ex VAT
Your Price (ex VAT)
£974.08
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £974.08
Trade pricing is personalised to your account

Manufacturer Lead Time

£974.08

Why Choose the ABB EPX-XT2S-TM1604 160A 4-Pole MCCB?

The ABB EPX-XT2S-TM1604 is a high-performance 160 A, 4-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in low-voltage electrical distribution systems. Featuring a 50 kA breaking capacity and a thermal-magnetic adjustable (TMA) trip unit, this circuit breaker delivers dependable electrical protection for commercial, industrial and infrastructure applications.

As part of the ABB Protecta Power Devices range, the EPX-XT2S-TM1604 incorporates proven ABB SACE Tmax XT2S160 circuit breaker technology. Its thermal-magnetic protection system combines adjustable thermal overload protection with magnetic short-circuit protection, helping safeguard electrical cables, distribution equipment and connected installations against damaging fault conditions.

With a 160 A rated current, four-pole configuration and 50 kA short-circuit breaking capacity at 415 V AC, the EPX-XT2S-TM1604 is suitable for three-phase electrical distribution systems requiring neutral conductor switching. Its compact XT2S frame design supports efficient integration into ABB Protecta Power distribution boards, electrical switchboards and compatible low-voltage switchgear assemblies.

Key Advantages

  • 160 A rated current suitable for commercial and industrial low-voltage distribution circuits.
  • 50 kA breaking capacity provides protection against high prospective short-circuit currents at 415 V AC.
  • Four-pole construction supports simultaneous switching of three phase conductors and the neutral conductor.
  • Thermal-magnetic adjustable (TMA) trip unit provides overload and short-circuit protection.
  • Adjustable thermal and magnetic protection characteristics support coordination with electrical installation requirements.
  • ABB SACE Tmax XT2S160 technology combines dependable electrical protection with compact construction.
  • Robust moulded case construction supports reliable operation in demanding electrical environments.
  • Suitable for integration into ABB Protecta Power distribution systems and compatible low-voltage switchgear.

Key Features

  • ABB Protecta Power Devices moulded case circuit breaker.
  • SACE Tmax XT2S160 circuit breaker platform.
  • 160 A rated current for electrical distribution protection.
  • 50 kA rated ultimate short-circuit breaking capacity at 415 V AC.
  • Four-pole configuration for three-phase and neutral electrical distribution.
  • TMA thermal-magnetic adjustable release providing overload and instantaneous short-circuit protection.
  • Adjustable thermal overload setting for coordination with circuit requirements.
  • Adjustable magnetic trip setting of 800–1600 A on the corresponding XT2S160 TMA release.
  • 690 V AC maximum rated operational voltage for the XT2S circuit breaker platform.
  • Compact moulded case construction suitable for low-voltage switchgear assemblies.
  • Mechanical operating mechanism with manual switching and automatic protective tripping.
  • Designed in accordance with IEC 60947-2 circuit breaker requirements.

Reliable Four-Pole Thermal-Magnetic Circuit Protection

The ABB EPX-XT2S-TM1604 provides effective electrical protection through its thermal-magnetic adjustable trip mechanism. The thermal protection element responds to sustained overload conditions, while the magnetic protection element provides rapid tripping during high-current short-circuit faults. These complementary protection functions help reduce the risk of damage to electrical conductors, connected equipment and distribution infrastructure.

The ABB SACE Tmax XT2S160 platform is engineered for reliable performance in low-voltage electrical networks. Its four-pole configuration enables coordinated switching of three phase conductors and the neutral conductor, while its adjustable protection settings support appropriate coordination with upstream and downstream electrical equipment. Combined with its 160 A current rating and 50 kA breaking capacity, this MCCB provides dependable protection for commercial and industrial power distribution systems.

Typical Applications

  • Commercial and industrial low-voltage distribution boards.
  • ABB Protecta Power electrical distribution assemblies.
  • Three-phase and neutral electrical distribution circuits.
  • Industrial machinery and equipment supply circuits.
  • Electrical switchboards and industrial control panels.
  • Building services and infrastructure power distribution.
  • Manufacturing facilities and industrial electrical installations.
  • Sub-distribution circuits requiring adjustable four-pole thermal-magnetic protection.

Technical Specifications

Product range Protecta Power Devices
Series SACE Tmax XT2S
ABB order code 1SDX255118R1
Product type Moulded case circuit breaker (MCCB)
Rated current 160 A
Number of poles 4
Rated ultimate short-circuit breaking capacity (Icu) 50 kA at 415 V AC
Trip unit type TMA – thermal-magnetic adjustable
Thermal adjustment range 112–160 A
Magnetic trip adjustment range 800–1600 A
Protection functions Thermal overload and magnetic short-circuit protection
Frame designation XT2S160
Frame rated current 160 A
Maximum rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Electrical system Three-phase with neutral
Operating mechanism Mechanical toggle operation
Application Low-voltage electrical distribution
Applicable standard IEC 60947-2
Product group Protecta Power Devices

Frequently Asked Questions

What is the ABB EPX-XT2S-TM1604 used for?

The ABB EPX-XT2S-TM1604 is a four-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits in commercial and industrial installations.

What is the rated current of the EPX-XT2S-TM1604?

The circuit breaker has a 160 A rated current and belongs to the ABB SACE Tmax XT2S160 frame family, which has a maximum frame current rating of 160 A.

What is the breaking capacity of this ABB MCCB?

The EPX-XT2S-TM1604 has a 50 kA rated ultimate short-circuit breaking capacity at 415 V AC. The prospective fault current and applicable operating conditions must be considered when selecting the circuit breaker.

What does TMA mean on the ABB EPX-XT2S-TM1604?

TMA stands for thermal-magnetic adjustable. The trip unit provides adjustable thermal overload protection and magnetic short-circuit protection. The corresponding XT2S160 TMA release provides a thermal adjustment range of 112–160 A and a magnetic trip adjustment range of 800–1600 A.

What is the advantage of the four-pole configuration?

The four-pole design allows coordinated switching of all three phase conductors and the neutral conductor, making the MCCB suitable for electrical distribution systems requiring four-pole switching and isolation.

Trusted ABB Circuit Protection Technology

ABB SACE Tmax XT moulded case circuit breakers are engineered to deliver dependable overload and short-circuit protection in commercial and industrial low-voltage electrical distribution systems. The EPX-XT2S-TM1604 combines a 160 A rated current, four-pole construction, 50 kA breaking capacity and adjustable thermal-magnetic protection in a compact XT2S160 frame for reliable electrical distribution applications.