ABB EPX-XT2S-TM0804 is an 80 A four-pole moulded case circuit breaker with a specified 50 kA short-circuit breaking capacity and an adjustable TMA thermal-magnetic trip unit. Part of the ABB Protecta Power Devices range, it provides thermal overload and instantaneous magnetic short-circuit protection for commercial and industrial low-voltage electrical distribution systems.
£666.50
The ABB EPX-XT2S-TM0804 is a high-performance 80 A four-pole moulded case circuit breaker (MCCB) designed to deliver reliable overload and short-circuit protection in commercial and industrial low-voltage electrical distribution systems. Featuring a 50 kA short-circuit breaking capacity and an adjustable TMA thermal-magnetic trip unit, this circuit breaker forms part of the ABB Protecta Power Devices range and uses the established ABB SACE Tmax XT2S circuit breaker platform.
Engineered for installations requiring dependable overcurrent protection and substantial fault-current interruption capability, the EPX-XT2S-TM0804 combines adjustable thermal overload protection with adjustable instantaneous magnetic short-circuit protection. Its thermal-magnetic operating principle offers straightforward protection configuration without requiring a separate electronic trip-unit power supply, making it a practical choice for professionally designed three-phase electrical distribution systems.
With its 80 A rated current, four-pole configuration and 50 kA breaking capacity, the ABB EPX-XT2S-TM0804 is suitable for appropriately designed outgoing circuits in commercial distribution boards, industrial electrical panels and compatible ABB Protecta Power assemblies. The four-pole arrangement supports coordinated switching of three phase conductors and a neutral conductor where required by the installation design. Supplied under ABB order code 1SDX255114R1, this MCCB provides robust, adjustable thermal-magnetic circuit protection for demanding low-voltage applications.
The ABB EPX-XT2S-TM0804 combines the mechanical switching and fault-interruption capabilities of the ABB SACE Tmax XT2S platform with an adjustable TMA thermal-magnetic protection release. This arrangement provides protection against sustained overload conditions and short-circuit faults, helping protect electrical conductors, connected equipment and distribution infrastructure against excessive current.
The thermal overload protection function responds to current flowing above the selected protection threshold for a sustained period. Its inverse-time operating characteristic means that larger overload currents generally result in faster tripping. This helps protect conductors against overheating while accommodating appropriate operating conditions within the electrical circuit's design limits.
The adjustable thermal element allows the overload protection threshold to be selected according to the connected circuit's requirements. The chosen setting must be compatible with conductor current-carrying capacity, expected load, installation conditions and the manufacturer's time-current characteristics. The precise thermal adjustment range for the supplied 80 A four-pole configuration should be confirmed against ABB's technical documentation before commissioning.
The magnetic short-circuit protection function provides rapid tripping when the current reaches the selected magnetic operating threshold. For the corresponding 80 A XT2S TMA release, the magnetic protection range is 400–800 A, equivalent to 5–10 times the rated current. This allows the magnetic threshold to be selected with regard to the installation's fault-current conditions and the coordination requirements of other protective devices.
The TMA thermal-magnetic trip unit provides a practical alternative to electronic protection releases. It uses thermal and magnetic operating principles rather than electronic sensing and processing, and it does not require a separate electronic trip-unit power supply. Unlike an electronic LSI release, the TMA arrangement does not provide an independently adjustable short-time delayed short-circuit protection function.
A major advantage of the XT2S breaking-capacity classification is its specified 50 kA short-circuit breaking capacity. This provides greater fault-interruption capability than corresponding XT2N configurations specified at 36 kA under the relevant reference conditions. The higher breaking capacity can be particularly useful where the circuit is located relatively close to a transformer, main switchboard or other supply point with substantial prospective fault current.
The corresponding ABB SACE Tmax XT2S IEC breaker platform has a 50 kA ultimate short-circuit breaking capacity at 415 V AC. However, the available breaking capacity varies with operating voltage. The installation's calculated prospective short-circuit current must therefore be compared with the applicable voltage-dependent rating, and the relevant ultimate and service breaking capacities should be checked against ABB's published technical data.
The four-pole configuration enables coordinated switching of four conductors, typically the three phase conductors and a neutral conductor in a suitably designed three-phase distribution system. This can be particularly valuable where the electrical installation requires neutral isolation alongside phase switching. However, the presence of a fourth pole does not automatically establish the neutral conductor's overcurrent protection characteristics. The exact neutral-pole arrangement must be verified against the manufacturer's technical information.
The ABB SACE Tmax XT2 160 A frame platform provides the mechanical foundation for the 80 A TMA configuration. Although the XT2 frame family supports ratings up to 160 A, the EPX-XT2S-TM0804 is specifically an 80 A rated protective device. The frame rating must not be confused with the rated current of the installed protection release or the permissible current of the protected circuit.
As part of the ABB Protecta Power Devices range, the EPX-XT2S-TM0804 is intended for installation in compatible distribution assemblies. Correct selection of mounting arrangements, cable terminations, enclosure components and protection settings is essential. The standard TMA release provides overload and short-circuit protection rather than residual-current or earth-leakage protection, so any required additional protective functions must be specified separately.
| Product group | Protecta Power Devices |
|---|---|
| Product reference | EPX-XT2S-TM0804 |
| ABB order code | 1SDX255114R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Series | SACE Tmax XT2 / Protecta Power |
| Circuit breaker designation | XT2S |
| Rated current (In) | 80 A |
| Number of poles | 4 |
| Pole configuration | 4P |
| Specified short-circuit breaking capacity | 50 kA |
| Corresponding XT2S IEC breaker breaking capacity | 50 kA at 415 V AC |
| Breaking-capacity classification | S |
| Trip unit type | TMA adjustable thermal-magnetic |
| Protection technology | Thermal-magnetic overcurrent release |
| Overload protection | Adjustable thermal |
| Thermal operating characteristic | Inverse-time |
| Thermal setting range | Confirm against the exact ABB trip-unit documentation |
| Short-circuit protection | Adjustable instantaneous magnetic |
| Magnetic protection adjustment | 5–10 × In |
| Magnetic short-circuit setting range | 400–800 A |
| Magnetic operating characteristic | Rapid tripping at the selected threshold |
| Trip-unit adjustment method | Mechanical setting controls |
| Separate electronic trip-unit supply | Not required |
| Frame family | XT2S |
| XT2 frame rating | 160 A |
| Rated protective current | 80 A |
| Corresponding XT2S platform operational voltage | Up to 690 V AC |
| Corresponding XT2S platform mounting | Fixed |
| Corresponding XT2S platform terminals | Front terminals |
| Operating mechanism | Manual toggle-operated circuit breaker |
| Switching arrangement | Four-pole simultaneous operation |
| Neutral-pole protection | Confirm the exact neutral arrangement against ABB technical documentation |
| Applicable circuit breaker standard | IEC/EN 60947-2 |
| Application | Low-voltage electrical distribution |
| Typical electrical system | Three-phase AC distribution with four-pole switching |
The ABB EPX-XT2S-TM0804 is an 80 A four-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It uses a TMA thermal-magnetic trip unit and is suitable for compatible commercial and industrial distribution assemblies, including ABB Protecta Power systems.
The EPX-XT2S-TM0804 has an 80 A rated current. It is intended for appropriately designed electrical circuits where the conductor ratings, expected load and protection characteristics are compatible with the circuit breaker.
The ABB EPX-XT2S-TM0804 has a specified 50 kA short-circuit breaking capacity. The corresponding XT2S IEC breaker platform has a 50 kA ultimate breaking capacity at 415 V AC. The applicable rating must be checked against the installation voltage and prospective fault current.
TMA identifies an adjustable thermal-magnetic trip unit. It combines thermal protection against sustained overloads with instantaneous magnetic protection against short-circuit currents. The protection thresholds can be configured within the adjustment ranges applicable to the exact release.
The corresponding 80 A XT2S TMA release provides a magnetic short-circuit adjustment range of 400–800 A, equivalent to 5–10 times the rated current. The setting should be selected according to the installation's fault-current conditions and protection coordination requirements.
Yes. The TMA thermal-magnetic trip unit provides adjustable thermal overload protection. The available settings for the exact supplied configuration should be confirmed against ABB's technical documentation, and the selected threshold must suit the conductor ratings and expected circuit load.
XT2S and XT2N identify different breaking-capacity variants within the ABB SACE Tmax XT2 range. Corresponding Protecta Power XT2S configurations are specified at 50 kA, compared with 36 kA for XT2N configurations under the relevant reference conditions. The correct selection depends on the installation voltage and prospective short-circuit current.
The four-pole (4P) configuration enables coordinated switching of four conductors, typically the three phase conductors and a neutral conductor in a three-phase electrical distribution system. This is useful where neutral isolation is required, subject to the manufacturer's neutral-pole arrangement and applicable electrical regulations.
The standard TMA thermal-magnetic trip unit provides overload and short-circuit protection rather than residual-current or earth-leakage protection. Where earth-leakage protection is required, an appropriate additional protective device or compatible arrangement must be specified.
The 80 A rating identifies the circuit breaker's rated protective current, while the 160 A frame rating identifies the current rating of the XT2 platform. The EPX-XT2S-TM0804 is an 80 A protective device and must not be treated as a 160 A rated circuit breaker.
The ABB manufacturer order code is 1SDX255114R1. The corresponding product reference is EPX-XT2S-TM0804, identifying the 80 A, four-pole, 50 kA TMA thermal-magnetic MCCB within the ABB Protecta Power Devices range.
The ABB EPX-XT2S-TM0804 combines an 80 A four-pole configuration, 50 kA short-circuit breaking capacity and adjustable TMA thermal-magnetic protection in a robust SACE Tmax XT2S moulded case circuit breaker. Designed for compatible ABB Protecta Power assemblies, it provides dependable overload and short-circuit protection for professionally specified commercial and industrial low-voltage electrical distribution systems.