ABB EPX-XT4S-TM1253 is a 125 A three-pole 50 kA moulded case circuit breaker from the Protecta Power Devices range, featuring adjustable TMA thermal-magnetic overload and short-circuit protection for low-voltage electrical distribution systems.
£728.99
The ABB EPX-XT4S-TM1253 is a high-performance 125 A three-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems. Part of the ABB Protecta Power Devices range, this circuit breaker uses the established ABB SACE Tmax XT4S platform, combining robust construction, adjustable thermal-magnetic protection and substantial short-circuit interruption capability for commercial and industrial installations.
Equipped with an ABB TMA thermal-magnetic trip unit, the EPX-XT4S-TM1253 provides adjustable thermal overload protection and magnetic short-circuit protection. The thermal element responds to sustained excessive current, helping protect cables and connected equipment against overheating. The magnetic element responds rapidly to short-circuit conditions, enabling the breaker to interrupt fault currents according to its protection characteristics.
With a rated current of 125 A, a three-pole configuration and a specified 50 kA short-circuit breaking capacity, this MCCB is suitable for protecting three-phase outgoing feeders and distribution circuits. Its 110 mm-wide XT4S format supports integration into compatible ABB Protecta Power distribution boards, making it a practical solution for electrical contractors, switchboard manufacturers, consulting engineers and maintenance professionals.
The ABB EPX-XT4S-TM1253 uses thermal and magnetic trip mechanisms to protect electrical circuits against abnormal current conditions. During sustained overloads, the thermal protection element responds to excessive current according to its time-current characteristics, helping prevent prolonged overheating of electrical conductors and connected equipment. During short-circuit conditions, the magnetic protection element responds rapidly when fault current reaches the configured threshold, initiating circuit interruption to reduce the consequences of electrical faults.
The ABB TMA trip unit provides adjustable thermal-magnetic protection characteristics. For the corresponding ABB XT4S TMA 125 A configuration, the magnetic protection setting can be adjusted within a range of 625–1250 A. This flexibility helps electrical engineers select appropriate short-circuit protection characteristics for the installation. Thermal settings must also be coordinated with conductor ratings, connected loads and the actual protection adjustment range marked on the supplied device.
The ABB SACE Tmax XT4S platform combines robust moulded case construction with a specified 50 kA short-circuit breaking capacity, making this MCCB suitable for appropriately engineered electrical distribution systems requiring substantial fault interruption capability. Its three-pole design supports three-phase feeder protection, while its compatibility with ABB Protecta Power assemblies provides a practical solution for distribution board construction and maintenance. Correct selection requires verification of the applicable operating voltage, prospective fault current, cable protection requirements and coordination with upstream and downstream protective devices.
| Product group | Protecta Power Devices |
|---|---|
| Product series | SACE Tmax XT4 |
| Product model | EPX-XT4S-TM1253 |
| ABB order code | 1SDX254971R1 |
| Corresponding ABB XT4S circuit breaker reference | 1SDA068308R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame designation | XT4S 160 |
| Frame current class | 160 A |
| Rated current (In) | 125 A |
| Number of poles | 3 |
| Specified short-circuit breaking capacity | 50 kA |
| Rated ultimate short-circuit breaking capacity (Icu), corresponding XT4S configuration | 50 kA at 415 V AC |
| Trip unit technology | Thermal-magnetic |
| Trip unit designation | TMA |
| Overload protection | Adjustable thermal trip |
| Short-circuit protection | Adjustable magnetic trip |
| Magnetic adjustment range, corresponding XT4S TMA 125 A configuration | 625–1250 A |
| Electrical system | Low-voltage AC distribution |
| Phase configuration | Three-phase |
| Nominal device width | 110 mm |
| Operating mechanism | Manual toggle operation |
| Primary function | Overload and short-circuit protection |
| Additional function | Circuit switching and isolation in accordance with manufacturer requirements |
| Product family standard | IEC/EN 60947-2 |
The ABB EPX-XT4S-TM1253 is a 125 A three-pole thermal-magnetic moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for compatible ABB Protecta Power distribution boards and commercial or industrial electrical panels.
The EPX-XT4S-TM1253 has a 125 A rated current and uses the ABB SACE Tmax XT4S 160 A frame platform. The 160 A frame designation identifies the current class of the circuit breaker platform rather than the rated current of this individual device.
The EPX-XT4S-TM1253 has a specified 50 kA short-circuit breaking capacity. The corresponding ABB XT4S circuit breaker configuration provides a rated ultimate short-circuit breaking capacity of 50 kA at 415 V AC. The prospective fault current and operating voltage must be verified when selecting the device.
TMA identifies a thermal-magnetic trip unit combining adjustable thermal overload protection with adjustable magnetic short-circuit protection. The thermal element responds to sustained excessive current, while the magnetic element provides rapid tripping during short-circuit conditions.
Yes. The corresponding ABB XT4S TMA 125 A circuit breaker configuration provides a magnetic adjustment range of 625–1250 A. The applicable settings should be confirmed against the supplied device and selected according to the electrical installation's protection requirements.
XT4N and XT4S identify different short-circuit performance versions within the ABB SACE Tmax XT4 family. The corresponding ABB Protecta Power XT4N devices are specified at 36 kA, while XT4S versions are specified at 50 kA. Selection should be based on the prospective fault current and applicable operating voltage.
Yes. The EPX-XT4S-TM1253 has a three-pole configuration designed for switching and protecting three phase conductors. It is suitable for appropriately designed three-phase low-voltage distribution circuits where neutral switching through the breaker is not required.
Yes. The EPX-XT4S-TM1253 belongs to the ABB Protecta Power Devices range and is intended for integration into compatible distribution assemblies. The correct XT4 mounting arrangement, electrical connections, enclosure compatibility and protection settings should be verified before installation.
ABB SACE Tmax XT moulded case circuit breakers provide established protection technology for commercial and industrial electrical distribution, combining robust construction, adjustable thermal-magnetic protection and dependable short-circuit interruption capability for modern low-voltage power systems.