ABB EPX-XT4S-TM0633 is a 63 A three-pole moulded case circuit breaker from the Protecta Power Devices range, featuring a 50 kA short-circuit breaking capacity and a TMA thermal-magnetic trip unit with adjustable magnetic protection for low-voltage electrical distribution systems.
£678.40
The ABB EPX-XT4S-TM0633 is a high-performance 63 A three-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems. Part of the ABB Protecta Power Devices range, this circuit breaker incorporates the proven ABB SACE Tmax XT4S160 platform, offering reliable electrical protection for commercial buildings, industrial facilities and electrical infrastructure.
Equipped with an ABB TMA thermal-magnetic trip unit, the EPX-XT4S-TM0633 combines thermal overload protection with adjustable magnetic short-circuit protection. The thermal element responds to sustained excessive current, while the magnetic element provides rapid interruption when short-circuit current reaches the selected trip threshold. These complementary protection functions help safeguard electrical cables, switchgear and connected equipment against damaging fault conditions.
With a 63 A rated current, three-pole construction and 50 kA short-circuit breaking capacity, this MCCB is suitable for three-phase electrical distribution circuits requiring substantial fault-interruption capability. Its XT4S160 frame, fixed-mounted construction and front terminal connections support integration into compatible ABB Protecta Power distribution boards and low-voltage switchgear assemblies.
Moulded case circuit breakers such as the ABB EPX-XT4S-TM0633 protect electrical installations by automatically interrupting current during overload and short-circuit conditions. Its TMA thermal-magnetic trip unit incorporates thermal protection against sustained overcurrent and an adjustable magnetic element for rapid short-circuit fault interruption. The magnetic setting range of 315–630 A allows the short-circuit trip threshold to be configured according to the electrical circuit and protection coordination requirements.
The ABB SACE Tmax XT4 circuit breaker family is engineered for dependable protection in modern low-voltage distribution assemblies. The EPX-XT4S-TM0633 is particularly suitable for installations requiring 63 A three-pole circuit protection and a 50 kA short-circuit breaking rating. Circuit breaker selection should account for operating voltage, prospective fault current, conductor characteristics, load requirements and protective device coordination. Where the MCCB supplies a motor circuit, dedicated motor overload protection may also be necessary depending on the installation design.
| Product group | Protecta Power Devices |
|---|---|
| Product series | SACE Tmax XT |
| Frame designation | XT4S160 |
| ABB order code | 1SDX254966R1 |
| Corresponding ABB circuit breaker reference | 1SDA068305R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current (In) | 63 A |
| Number of poles | 3 |
| Short-circuit breaking capacity | 50 kA |
| Trip unit | TMA |
| Trip unit technology | Thermal-magnetic |
| Overload protection | Thermal trip element |
| Short-circuit protection | Adjustable magnetic trip element |
| Magnetic short-circuit protection setting | 315–630 A |
| Magnetic adjustment | 5–10 × In |
| Protection functions | Thermal overload and magnetic short-circuit protection |
| Frame family | XT4S160 |
| Maximum frame rating | 160 A |
| Rated operational voltage | Up to 690 V AC |
| Mounting type | Fixed mounting |
| Terminal arrangement | Front terminals |
| Operating mechanism | Manual operation |
| Application | Low-voltage three-phase electrical distribution |
| Installation | Compatible electrical distribution boards and switchgear assemblies |
| Applicable circuit breaker standard | IEC/EN 60947-2 |
The ABB EPX-XT4S-TM0633 is a three-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for appropriately designed commercial and industrial three-phase electrical installations.
The circuit breaker has a 63 A rated current and uses the ABB Tmax XT4S160 frame, which has a maximum frame rating of 160 A. The rated current of this specific MCCB is 63 A, not the maximum rating of its frame.
The EPX-XT4S-TM0633 has a specified 50 kA short-circuit breaking capacity. The applicable breaking capacity at the installation's operating voltage must be verified against ABB technical documentation and the prospective fault current before selection.
The ABB TMA thermal-magnetic trip unit provides thermal overload protection and adjustable magnetic short-circuit protection. For this 63 A configuration, the magnetic trip setting can be adjusted from 315–630 A, equivalent to 5–10 times the rated current.
This MCCB is typically installed in low-voltage electrical distribution boards, industrial switchboards and compatible ABB Protecta Power assemblies. Its fixed-mounted construction, front terminal connections and three-pole configuration support integration into suitable three-phase electrical distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are engineered to deliver dependable overload and short-circuit protection in modern electrical distribution systems. The ABB EPX-XT4S-TM0633 combines a 63 A rating, three-pole construction, 50 kA breaking capacity and TMA thermal-magnetic protection in a robust circuit breaker suitable for commercial, industrial and infrastructure power distribution applications.