ABB EPX-XT4N-E2-1003 is a 100 A three-pole 36 kA electronic moulded case circuit breaker from the Protecta Power Devices range, featuring an Ekip LSI trip unit with long-time, short-time and instantaneous protection for low-voltage electrical distribution systems.
£1,403.31
The ABB EPX-XT4N-E2-1003 is a high-performance 100 A three-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems. Part of the ABB Protecta Power Devices range, this circuit breaker incorporates the established ABB SACE Tmax XT4N 160 A frame platform, combining robust construction with electronic protection technology for commercial buildings, industrial facilities and electrical distribution assemblies.
Equipped with an ABB Ekip LSI electronic trip unit, the EPX-XT4N-E2-1003 provides three important protection functions: long-time overload protection (L), short-time delayed short-circuit protection (S) and instantaneous short-circuit protection (I). These electronic protection characteristics enable engineers to configure suitable trip settings for electrical circuits and support coordination with other protective devices.
With a rated current of 100 A, a three-pole configuration and a specified 36 kA short-circuit breaking capacity, this MCCB is suitable for protecting three-phase outgoing feeders and distribution circuits. Its compact 110 mm-wide XT4 frame facilitates integration into compatible ABB Protecta Power distribution boards, making it a practical solution for electrical contractors, panel builders and maintenance engineers requiring reliable electronic circuit protection.
The ABB EPX-XT4N-E2-1003 uses electronic current monitoring to protect electrical circuits against abnormal operating conditions. Its long-time (L) protection responds to sustained overloads that could otherwise lead to excessive cable temperatures or damage connected equipment. The short-time (S) protection introduces a controlled delay for selected short-circuit conditions, supporting coordination with downstream protective devices. The instantaneous (I) protection provides rapid circuit interruption when high-current faults exceed the configured protection threshold.
A significant advantage of the ABB Ekip LSI trip unit is that all three protection characteristics are available within the same electronic protection system. Unlike LS/I configurations, where short-time and instantaneous protection are selected as alternatives, LSI protection offers greater flexibility when configuring circuit protection. This can help improve selectivity, minimise unnecessary upstream interruptions and support more effective fault management in appropriately engineered electrical distribution networks.
The ABB SACE Tmax XT4N platform combines these electronic protection capabilities with robust moulded case construction. Its three-pole arrangement is suitable for protecting three-phase electrical circuits, while its compact frame facilitates integration into compatible ABB Protecta Power distribution assemblies. Correct selection of trip settings, cable ratings, operating voltage, prospective short-circuit current and protective device coordination remains essential for safe and reliable operation.
| Product group | Protecta Power Devices |
|---|---|
| Product series | SACE Tmax XT4 |
| Product model | EPX-XT4N-E2-1003 |
| ABB order code | 1SDX254835R1 |
| Corresponding ABB circuit breaker reference | 1SDA068134R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame designation | XT4N 160 |
| Frame current class | 160 A |
| Rated current (In) | 100 A |
| Number of poles | 3 |
| Specified short-circuit breaking capacity | 36 kA |
| Trip unit technology | Electronic |
| Trip unit | ABB Ekip LSI |
| Long-time protection (L) | Overload protection |
| Short-time protection (S) | Delayed short-circuit protection |
| Instantaneous protection (I) | Instantaneous short-circuit protection |
| Protection characteristics | LSI |
| Rated insulation voltage (Ui), XT4 series | 1000 V |
| Rated impulse withstand voltage (Uimp), XT4 series | 8 kV |
| Electrical system | Low-voltage AC distribution |
| Phase configuration | Three-phase |
| Nominal device width | 110 mm |
| Operating mechanism | Manual toggle operation |
| Primary function | Overload and short-circuit protection |
| Additional function | Circuit switching and isolation in accordance with manufacturer installation requirements |
| Product family standard | IEC/EN 60947-2 |
The ABB EPX-XT4N-E2-1003 is a 100 A three-pole electronic moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for compatible ABB Protecta Power distribution boards and commercial or industrial switchgear assemblies.
The EPX-XT4N-E2-1003 has a 100 A rated current. It uses the ABB SACE Tmax XT4N 160 A frame platform, but the rated current of this individual circuit breaker is 100 A rather than the maximum current class of the frame.
The circuit breaker has a specified 36 kA short-circuit breaking capacity. The applicable operating voltage, manufacturer short-circuit rating conditions and installation prospective fault current should be checked when selecting the device.
Ekip LSI is an electronic trip system incorporating long-time overload protection (L), short-time delayed short-circuit protection (S) and instantaneous short-circuit protection (I). These functions provide flexible protection characteristics for low-voltage electrical distribution applications.
Ekip LSI incorporates long-time, short-time and instantaneous protection characteristics within the same electronic trip system. Ekip LS/I provides long-time protection together with a choice between short-time and instantaneous protection. LSI therefore offers additional flexibility when coordinating protective devices.
Yes. The EPX-XT4N-E2-1003 has a three-pole configuration designed for switching and protecting three phase conductors. It is suitable for appropriately designed three-phase low-voltage electrical distribution circuits where neutral switching is not required through the breaker.
Yes. The EPX-XT4N-E2-1003 belongs to the ABB Protecta Power Devices range and is intended for integration into compatible distribution assemblies. The appropriate XT4 mounting arrangement, electrical connections, enclosure compatibility and electronic protection settings should be verified before installation.
ABB SACE Tmax XT electronic moulded case circuit breakers provide established protection technology for commercial and industrial electrical distribution, combining adjustable electronic trip functionality, robust construction and dependable overload and short-circuit protection for modern low-voltage power systems.