Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB EPX-XT2N-E2-1604 is a 160 A four-pole moulded case circuit breaker from the Protecta Power Devices range, featuring a 36 kA breaking capacity at 415 V AC and an Ekip Dip LSI electronic trip unit providing long-time, short-time and instantaneous protection for low-voltage electrical distribution systems.
£1,793.82
The ABB EPX-XT2N-E2-1604 is a high-performance 160 A four-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in low-voltage electrical distribution systems. Part of the ABB Protecta Power Devices range, this circuit breaker incorporates the established ABB SACE Tmax XT2N160 platform, delivering dependable electrical protection for commercial buildings, industrial facilities and electrical infrastructure.
Equipped with an ABB Ekip Dip LSI electronic trip unit, the EPX-XT2N-E2-1604 provides three essential protection functions: long-time overload protection (L), short-time short-circuit protection (S) and instantaneous short-circuit protection (I). Its electronic trip technology enables configurable protection characteristics, supporting coordination between protective devices and helping safeguard distribution cables, switchgear and connected equipment.
With a 160 A rated current, four-pole construction and 36 kA breaking capacity at 415 V AC, this MCCB is suitable for three-phase electrical distribution systems incorporating a neutral conductor. Its compact XT2N160 frame, fixed-mounted construction and front terminal arrangement support integration into compatible ABB Protecta Power distribution boards and low-voltage switchgear assemblies.
Moulded case circuit breakers such as the ABB EPX-XT2N-E2-1604 protect electrical installations by automatically interrupting current when overload or short-circuit faults occur. Its Ekip Dip LSI electronic trip unit provides long-time protection against sustained overloads, short-time protection for controlled fault clearance and instantaneous protection for rapid interruption of severe short circuits. These functions help protect distribution cables, electrical equipment and connected circuits while supporting effective coordination with other protective devices.
The ABB SACE Tmax XT2 circuit breaker family is designed for dependable performance in modern low-voltage electrical distribution systems. Its compact construction, electronic protection technology and compatibility with suitable ABB accessories support integration into commercial and industrial electrical infrastructure. The EPX-XT2N-E2-1604 is particularly suited to installations requiring 160 A four-pole circuit protection and a 36 kA fault-breaking rating at 415 V AC, subject to verification of operating voltage, prospective fault current, cable characteristics and protection coordination requirements.
| Product group | Protecta Power Devices |
|---|---|
| Product series | SACE Tmax XT |
| Frame designation | XT2N160 |
| ABB order code | 1SDX254832R1 |
| Corresponding ABB circuit breaker reference | 1SDA067107R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current (In) | 160 A |
| Number of poles | 4 |
| Rated ultimate short-circuit breaking capacity (Icu) | 36 kA at 415 V AC |
| Trip unit | Ekip Dip LSI |
| Trip unit technology | Electronic |
| Long-time protection (L) | Adjustable overload protection |
| Short-time protection (S) | Short-circuit protection with time-delay functionality |
| Instantaneous protection (I) | Short-circuit protection without intentional delay |
| Protection functions | L, S and I |
| Neutral protection | 100% of phase rating |
| Frame family | XT2N160 |
| Maximum frame rating | 160 A |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50/60 Hz |
| Mounting type | Fixed mounting |
| Terminal arrangement | Front terminals |
| Operating mechanism | Manual toggle operation |
| Application | Low-voltage three-phase electrical distribution |
| Installation | Compatible electrical distribution boards and switchgear assemblies |
| Applicable circuit breaker standard | IEC/EN 60947-2 |
The ABB EPX-XT2N-E2-1604 is a four-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for commercial and industrial three-phase electrical systems incorporating a neutral conductor.
The circuit breaker has a 160 A rated current and uses the ABB Tmax XT2N160 frame. Its Ekip Dip LSI electronic trip unit provides configurable protection characteristics for appropriately designed electrical distribution circuits.
The EPX-XT2N-E2-1604 has a rated ultimate short-circuit breaking capacity of 36 kA at 415 V AC. The applicable breaking capacity must be checked against the installation voltage and prospective short-circuit current before selection.
The ABB Ekip Dip LSI electronic trip unit provides three protection functions: long-time overload protection (L), short-time short-circuit protection (S) and instantaneous short-circuit protection (I). These functions support configurable fault protection and coordination between protective devices in electrical distribution systems.
This MCCB is typically installed in low-voltage electrical distribution boards, industrial switchboards and compatible ABB Protecta Power assemblies, where four-pole electronic circuit protection is required. Its fixed-mounted construction and front terminal connections support integration into suitable electrical distribution panels.
ABB SACE Tmax XT moulded case circuit breakers are engineered to deliver dependable overload and short-circuit protection in modern electrical distribution systems. The ABB EPX-XT2N-E2-1604 combines a 160 A rating, four-pole construction, 36 kA breaking capacity and advanced Ekip Dip LSI electronic protection in a compact circuit breaker suitable for commercial, industrial and infrastructure power distribution applications.
We use cookies