ABB EPX-XT5N-E1-4004 is a 400 A four-pole moulded case circuit breaker with 36 kA breaking capacity at 380–415 V AC and an Ekip Dip LS/I electronic trip unit providing adjustable overload and selectable short-circuit protection for high-current low-voltage electrical distribution.
£1,788.18
The ABB EPX-XT5N-E1-4004 is a high-performance 400 A four-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems. Featuring a 36 kA breaking capacity and an Ekip Dip LS/I electronic trip unit, this circuit breaker delivers configurable protection for commercial, industrial and infrastructure electrical installations.
As part of the ABB Protecta Power Devices range, the EPX-XT5N-E1-4004 incorporates proven ABB SACE Tmax XT5N circuit breaker technology. Its electronic protection system provides adjustable long-time overload protection (L), together with selectable short-time delayed (S) or instantaneous (I) short-circuit protection. This enables electrical engineers to configure protection characteristics according to the requirements of the distribution system, connected conductors and downstream equipment.
With a 400 A rated current, four-pole configuration and 36 kA short-circuit breaking capacity at 380–415 V AC, the EPX-XT5N-E1-4004 is suitable for three-phase electrical distribution systems requiring high-current electronic circuit protection. Its XT5N 400 frame, fixed-mounted construction and front connection terminals make it a practical solution for electrical panel builders, contractors and industrial maintenance engineers.
Moulded case circuit breakers such as the ABB EPX-XT5N-E1-4004 protect electrical distribution circuits against overload currents and short-circuit faults. The integrated Ekip Dip LS/I electronic trip unit provides adjustable long-time overload protection and selectable short-time delayed or instantaneous short-circuit protection. This flexibility allows electrical engineers to coordinate circuit breaker operation with the characteristics of electrical feeders, downstream protective devices and connected equipment.
The ABB SACE Tmax XT5N platform combines robust electrical protection with dependable mechanical construction suitable for modern switchgear assemblies. With its 400 A rated current, four-pole switching arrangement and 36 kA breaking capacity at 380–415 V AC, the EPX-XT5N-E1-4004 supports reliable protection of distribution feeders, switchboard circuits and industrial electrical installations. Its compatibility with ABB Protecta Power systems makes it particularly suitable for panel builders and electrical contractors requiring configurable electronic protection in high-current low-voltage distribution equipment.
| Product range | Protecta Power Devices |
|---|---|
| Circuit breaker family | SACE Tmax XT |
| Series | XT5N |
| ABB order code | 1SDX254018R1 |
| ABB base circuit breaker reference | 1SDA100396R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current (In) | 400 A |
| Rated uninterrupted current (Iu) | 400 A |
| Number of poles | 4 |
| Rated ultimate short-circuit breaking capacity (Icu) | 36 kA at 380–415 V AC |
| Trip unit | Ekip Dip LS/I electronic release |
| Release type | Electronic |
| Long-time protection (L) | Adjustable overload protection |
| Short-time protection (S) | Adjustable delayed short-circuit protection |
| Instantaneous protection (I) | Short-circuit protection without intentional delay |
| Short-circuit protection selection | S or I |
| Frame size | XT5 |
| Frame designation | XT5N 400 |
| Frame current rating | 400 A |
| Breaking capacity class | N |
| Rated operational voltage (Ue) | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1,000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated short-time withstand current (Icw) | 5 kA |
| Mounting arrangement | Fixed installation |
| Terminal arrangement | Front terminals |
| Operating mechanism | Manual toggle |
| Application | Low-voltage power distribution and circuit protection |
| Applicable standard | IEC 60947-2 |
The ABB EPX-XT5N-E1-4004 is a 400 A four-pole moulded case circuit breaker used to protect low-voltage electrical distribution circuits against overloads and short circuits in commercial, industrial and infrastructure installations.
The circuit breaker has a rated current of 400 A and uses an ABB SACE Tmax XT5N 400 frame. The electronic protection release and rated uninterrupted current are both rated at 400 A.
The EPX-XT5N-E1-4004 has a 36 kA short-circuit breaking capacity at 380–415 V AC. The installation must be designed so that the prospective fault current does not exceed the applicable circuit breaker breaking capacity.
LS/I identifies an electronic protection release providing long-time overload protection (L) together with selectable short-time delayed short-circuit protection (S) or instantaneous short-circuit protection (I). The S and I functions are selectable alternatives rather than simultaneously active protection functions.
The Ekip Dip LS/I electronic trip unit uses electronic protection technology to provide adjustable overload and short-circuit protection characteristics. Conventional thermal-magnetic trip units use thermal and magnetic elements to detect overcurrent conditions. Electronic protection offers greater flexibility when configuring protection characteristics for electrical distribution systems.
Yes. The Ekip Dip LS/I electronic trip unit provides adjustable long-time overload protection and configurable short-circuit protection. Engineers can select the appropriate short-time delayed or instantaneous protection function according to the installation requirements and ABB's setting instructions.
Yes. The EPX-XT5N-E1-4004 is a four-pole (4P) MCCB designed for applications requiring four-pole switching and circuit protection in three-phase electrical distribution systems.
The EPX-XT5N-E1-4004 uses ABB SACE Tmax XT5N circuit breaker technology and belongs to the ABB Protecta Power Devices product range. The corresponding ABB base circuit breaker reference is 1SDA100396R1.
An LS/I trip unit provides long-time overload protection with a selectable short-time delayed or instantaneous short-circuit protection function. An LSI trip unit provides long-time, short-time delayed and instantaneous protection functions together, allowing all three protection characteristics to be configured within the same release.
This MCCB is typically installed in low-voltage distribution boards, industrial switchboards and electrical panel assemblies, including compatible ABB Protecta Power distribution systems. Its fixed-mounted construction and front connection terminals support integration into suitable electrical enclosures.
ABB SACE Tmax XT moulded case circuit breakers are widely specified by electrical engineers, panel builders, industrial maintenance teams and electrical contractors for dependable overload and short-circuit protection. The ABB EPX-XT5N-E1-4004 combines a 400 A rated current, four-pole configuration and 36 kA breaking capacity with advanced Ekip Dip LS/I electronic protection, making it a practical choice for reliable high-current low-voltage electrical distribution.