ABB EPX-XT4N-E1-0634 (1SDX254011R1) is a 63 A four-pole SACE Tmax XT4N moulded case circuit breaker with a specified 36 kA short-circuit breaking capacity and ABB Ekip LS/I electronic protection. Designed for compatible ABB Protecta Power distribution assemblies, it provides configurable overload and short-circuit protection for three-phase outgoing circuits requiring four-pole switching.
£1,252.97
The ABB EPX-XT4N-E1-0634 is a high-performance 63 A four-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in low-voltage electrical distribution systems. Built around the established ABB SACE Tmax XT4N circuit breaker platform, this protective device combines robust construction with electronic trip technology for commercial, industrial and building services applications.
As part of the ABB Protecta Power Devices product group, the EPX-XT4N-E1-0634 is designed for integration into compatible ABB Protecta Power distribution assemblies. Its ABB Ekip LS/I electronic trip configuration provides long-time overload protection together with selectable short-circuit protection characteristics, helping electrical engineers coordinate the protective device with the requirements of the installation.
With a 63 A rated current, a specified 36 kA short-circuit breaking capacity and a four-pole (4P) configuration, the EPX-XT4N-E1-0634 is suitable for appropriately designed three-phase outgoing circuits requiring coordinated switching of three phase conductors and a neutral conductor. Its 140 mm nominal device width supports efficient use of space within compatible distribution assemblies.
Identified by ABB order code 1SDX254011R1, this electronic MCCB provides electrical contractors, consulting engineers, panel builders and facilities managers with a clearly specified solution for 63 A four-pole circuit protection within the ABB Protecta Power range.
The ABB EPX-XT4N-E1-0634 63 A electronic MCCB is designed to help maintain the safety and reliability of low-voltage electrical distribution networks. Moulded case circuit breakers interrupt current when abnormal operating conditions occur, helping protect cables, distribution equipment and connected loads against the damaging effects of overloads and short circuits.
Unlike a conventional thermal-magnetic circuit breaker, the EPX-XT4N-E1-0634 uses an electronic trip release to evaluate current conditions and initiate tripping according to the selected protection characteristics. This makes it particularly useful in installations where engineers require greater flexibility when setting overload and short-circuit protection.
The ABB Ekip LS/I trip configuration provides long-time overload protection (L), which responds to sustained excessive current that could otherwise cause overheating of electrical conductors and equipment. The short-circuit protection arrangement allows the selection of either short-time delayed protection (S) or instantaneous protection (I), depending on the requirements of the protected circuit.
The distinction between LS/I and LSI is important when specifying electronic MCCBs. An LS/I release provides long-time overload protection with a choice between short-time and instantaneous short-circuit protection modes. An LSI release incorporates long-time, short-time and instantaneous protection characteristics together. Selecting the correct release helps engineers achieve the required protection strategy and coordination with other circuit breakers.
The four-pole construction supports coordinated switching of the three phase conductors and a neutral conductor. This is valuable in three-phase distribution systems where neutral disconnection forms part of the electrical design. However, neutral switching and neutral overcurrent protection are different functions. The precise neutral protection arrangement must be confirmed against the fitted release and applicable ABB documentation.
The ABB SACE Tmax XT4N platform provides a robust basis for low-voltage electrical protection. The EPX-XT4N-E1-0634 combines this construction with a 63 A rated current, a specified 36 kA breaking capacity and a 140 mm nominal width, making it a practical choice for compatible ABB Protecta Power distribution assemblies.
Correct selection should consider the system operating voltage, prospective short-circuit current, cable sizing, electronic trip settings, neutral switching requirements, discrimination and compatibility with the distribution assembly. The applicable breaking capacity and exact Ekip LS/I adjustment ranges should be verified against ABB technical documentation before installation and commissioning.
| Product group | Protecta Power Devices |
|---|---|
| Product range | SACE Tmax XT |
| Circuit breaker platform | XT4N |
| Model / SKU | EPX-XT4N-E1-0634 |
| ABB order code | 1SDX254011R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 63 A |
| Short-circuit breaking capacity | 36 kA (specified Protecta Power application) |
| Number of poles | 4 |
| Pole configuration | Four-pole (4P) |
| Trip unit designation | Ekip LS/I |
| Trip technology | Electronic |
| Protection designation | LS/I |
| Long-time protection (L) | Overload protection |
| Short-time protection (S) | Selectable delayed short-circuit protection |
| Instantaneous protection (I) | Selectable instantaneous short-circuit protection |
| Protection arrangement | Long-time overload protection with a choice between short-time and instantaneous short-circuit protection |
| Electronic trip adjustment | Refer to the fitted ABB Ekip release documentation |
| Neutral switching | Four-pole construction |
| Neutral protection | Dependent on the fitted release and neutral pole arrangement |
| Applicable circuit breaker standard | IEC 60947-2 |
| Nominal device width | 140 mm |
| Installation type | Fixed installation within a compatible distribution assembly |
| Mounting compatibility | ABB Protecta Power, subject to appropriate mounting and connection arrangements |
| Electrical application | Three-phase low-voltage power distribution with four-pole switching |
| Typical use | Outgoing feeder and sub-distribution circuit protection |
The ABB EPX-XT4N-E1-0634 is a 63 A four-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It features an ABB Ekip LS/I electronic trip configuration and is intended for compatible ABB Protecta Power distribution assemblies.
The EPX-XT4N-E1-0634 has a 63 A rated current and a specified 36 kA short-circuit breaking capacity within the ABB Protecta Power range. It is based on the ABB SACE Tmax XT4N platform. The applicable breaking capacity must be checked against the installation operating voltage and prospective fault current.
LS/I identifies an electronic protection arrangement providing long-time overload protection (L) together with a choice of short-time delayed short-circuit protection (S) or instantaneous short-circuit protection (I). The selected protection mode and adjustment settings should be determined according to the electrical installation design and the manufacturer's instructions.
The four-pole (4P) configuration enables coordinated switching of three phase conductors and a neutral conductor. This is useful in electrical distribution systems where neutral disconnection is required by the installation design. Neutral switching does not automatically establish the neutral overcurrent protection characteristics, which must be confirmed for the specific breaker configuration.
The breaker is intended for installation within compatible ABB Protecta Power distribution boards, using the appropriate mounting and connection arrangements. The ABB XT4 four-pole platform has a nominal width of 140 mm. Installation and electronic trip configuration should be carried out by a competent electrical professional in accordance with the circuit design and applicable electrical regulations.
ABB SACE Tmax XT moulded case circuit breakers are established components in low-voltage electrical distribution, providing dependable protection for commercial and industrial installations. The ABB EPX-XT4N-E1-0634 combines a 63 A rated current, four-pole switching, specified 36 kA short-circuit breaking capacity and configurable ABB Ekip LS/I electronic protection in a robust device intended for compatible ABB Protecta Power distribution systems.