ABB EPX-XT2N-E1-0254 is a 25 A four-pole SACE Tmax XT2N160 moulded case circuit breaker with 36 kA breaking capacity and Ekip LS/I electronic overload and short-circuit protection for commercial and industrial low-voltage electrical distribution systems.
£907.21
The ABB EPX-XT2N-E1-0254 is a compact 25 A four-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in commercial and industrial low-voltage electrical distribution systems. Part of the ABB Protecta Power Devices range, this circuit breaker uses the ABB SACE Tmax XT2N160 platform with an Ekip LS/I electronic trip unit, offering configurable circuit protection for compatible electrical distribution assemblies.
Featuring a 36 kA short-circuit breaking capacity, the EPX-XT2N-E1-0254 helps protect electrical conductors, distribution equipment and connected loads against fault conditions. Its electronic protection arrangement provides long-time overload protection (L) with a choice between short-time delayed (S) and instantaneous (I) short-circuit protection, supporting effective protection coordination in appropriately designed installations.
With a 25 A rated current, four-pole configuration and compact 120 mm nominal width, this MCCB is particularly suitable for three-phase and neutral distribution circuits requiring four-pole switching. Its ABB Tmax XT2N construction makes it a practical choice for electrical contractors, panel builders and maintenance engineers working with ABB Protecta Power distribution boards.
The ABB EPX-XT2N-E1-0254 incorporates an Ekip LS/I electronic trip unit designed to protect electrical installations against sustained overloads and short-circuit faults. Electronic protection technology uses current sensing and electronic processing to deliver defined protective characteristics, helping electrical designers achieve suitable protection coordination within low-voltage distribution systems.
The L (long-time) protection function responds to sustained excessive current, helping prevent overheating of conductors and connected equipment. The S/I protection arrangement provides a choice between short-time delayed short-circuit protection and instantaneous short-circuit protection. Short-time delay can assist coordination with downstream protective devices, while instantaneous protection enables rapid interruption of high fault currents.
The four-pole construction supports installations where three phase conductors and a neutral conductor must be switched together. This arrangement is particularly useful in compatible three-phase and neutral distribution systems. The neutral pole's protection characteristics and suitability must be checked against the specific circuit breaker configuration and installation requirements.
The ABB SACE Tmax XT2N160 platform combines compact moulded case construction with electronic protection. Its 120 mm nominal four-pole width provides a space-efficient footprint for compatible distribution boards and switchboards.
When installing the EPX-XT2N-E1-0254 within an ABB Protecta Power distribution board, suitable mounting components, terminal connections and protective covers must be selected. Electrical designers should verify prospective fault current, conductor ratings, neutral arrangements, electronic trip settings and protective device coordination before commissioning.
| Product range | Protecta Power Devices |
|---|---|
| Circuit breaker series | SACE Tmax XT |
| Circuit breaker frame | XT2 |
| Performance level | XT2N |
| Frame configuration | XT2N160 |
| ABB order code | 1SDX254005R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 25 A |
| Maximum frame rating | 160 A |
| Number of poles | 4P (four pole) |
| Short-circuit breaking capacity | 36 kA |
| Trip unit | Ekip LS/I |
| Trip technology | Electronic |
| Overload protection | L – long-time protection |
| Short-circuit protection | S/I – selectable short-time delayed or instantaneous protection |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50/60 Hz |
| Nominal width | 120 mm |
| Applicable standard | IEC 60947-2 |
| Installation type | Electrical distribution board / switchboard mounting |
| Compatible system | ABB Protecta Power |
| Product category | Protecta Power Devices |
The ABB EPX-XT2N-E1-0254 is a 25 A four-pole moulded case circuit breaker designed to protect commercial and industrial low-voltage electrical distribution circuits against overloads and short circuits using an Ekip LS/I electronic trip unit.
The EPX-XT2N-E1-0254 has a 25 A rated current and uses the ABB SACE Tmax XT2N160 platform, which has a maximum frame rating of 160 A. The frame rating does not change the specified 25 A rating of this device.
The EPX-XT2N-E1-0254 is specified with a 36 kA short-circuit breaking capacity. The applicable breaking capacity must be checked against the operating voltage and prospective fault current of the electrical installation.
LS/I identifies an electronic protection arrangement providing L (long-time overload protection) with a choice between S (short-time delayed short-circuit protection) and I (instantaneous short-circuit protection). The S and I functions are selectable alternatives rather than simultaneous independent functions.
Ekip LS/I provides long-time overload protection with a choice between short-time delayed and instantaneous short-circuit protection. Ekip LSI provides long-time, short-time delayed and instantaneous protection functions together, offering additional flexibility for protection coordination.
Both circuit breakers use the ABB SACE Tmax XT2N160 platform and are rated at 25 A with 36 kA breaking capacity and Ekip LS/I electronic protection. The EPX-XT2N-E1-0253 has a three-pole configuration, while the EPX-XT2N-E1-0254 has a four-pole configuration suitable for applications requiring four-pole switching.
The ABB EPX-XT2N-E1-0254 uses the four-pole XT2 frame arrangement with a nominal width of 120 mm. Additional installation clearance may be required depending on the mounting arrangement, terminals and accessories.
Yes. The EPX-XT2N-E1-0254 belongs to the ABB Protecta Power Devices range and is intended for compatible electrical distribution assemblies. Appropriate XT2 mounting components, terminal connections, covers and installation accessories must be selected according to the switchboard configuration.
ABB SACE Tmax XT moulded case circuit breakers provide dependable overload and short-circuit protection for commercial and industrial electrical installations. The EPX-XT2N-E1-0254 combines a 25 A four-pole XT2N160 circuit breaker with 36 kA breaking capacity and Ekip LS/I electronic protection, delivering a compact and configurable solution for compatible ABB Protecta Power distribution assemblies.
We use cookies