ABB EPX-XT5N-TM3204 (1SDX253959R1) is a 320 A four-pole moulded case circuit breaker with a 36 kA breaking capacity at 415 V AC, an adjustable TMA thermal-magnetic trip unit and an XT5N 400 frame for overload and short-circuit protection in Protecta Power distribution systems.
£1,710.26
The ABB EPX-XT5N-TM3204 (1SDX253959R1) is a robust and reliable 320 A four-pole moulded case circuit breaker (MCCB) designed to provide overload and short-circuit protection in low-voltage electrical distribution systems. As part of the ABB Protecta Power Devices range, this circuit breaker uses the proven ABB SACE Tmax XT5N platform to deliver dependable circuit protection for commercial buildings, industrial facilities and power distribution assemblies.
Featuring a thermal-magnetic adjustable (TMA) trip unit, the EPX-XT5N-TM3204 combines thermal overload protection with magnetic short-circuit protection. The thermal element responds to sustained overcurrent conditions, while the magnetic element provides rapid tripping during significant fault currents. This protection arrangement helps safeguard electrical cables, distribution equipment and connected installations against the potentially damaging effects of electrical faults.
With a rated current of 320 A, a four-pole configuration and a rated ultimate short-circuit breaking capacity of 36 kA at 415 V AC, the ABB EPX-XT5N-TM3204 is suitable for three-phase distribution circuits requiring simultaneous switching of all four poles. The device uses an XT5N 400 frame with a fully rated neutral pole and is designed for integration into compatible ABB Protecta Power distribution assemblies.
Moulded case circuit breakers are essential components in modern electrical distribution systems, providing protection against excessive current and short-circuit faults. The ABB EPX-XT5N-TM3204 is designed to interrupt fault currents before they cause unacceptable damage to electrical conductors, distribution equipment and connected circuits.
The circuit breaker incorporates a TMA thermal-magnetic trip unit that combines two complementary protection functions. The thermal element provides inverse-time overload protection, allowing the device to respond to sustained overcurrent conditions. The magnetic element provides rapid short-circuit protection, with an adjustable instantaneous trip setting that supports coordination with the electrical installation.
The ABB SACE Tmax XT5N 400 frame provides a robust platform for the 320 A protective device. Its 36 kA breaking capacity at 415 V AC makes it suitable for electrical distribution points where the prospective fault current does not exceed the circuit breaker's rated capability under the applicable operating conditions.
The four-pole configuration allows the three phase conductors and neutral conductor to be switched together. The fully rated neutral pole provides a neutral current rating equal to the phase current rating, making the device suitable for appropriately designed three-phase and neutral distribution systems.
As part of the ABB Protecta Power Devices range, the EPX-XT5N-TM3204 is intended for integration into compatible low-voltage distribution assemblies. The appropriate mounting arrangement, cable connections, protection settings and associated accessories must be selected according to the complete switchboard design and installation requirements.
The ABB EPX-XT5N-TM3204 is a 320 A four-pole moulded case circuit breaker used to protect low-voltage electrical distribution circuits against overloads and short circuits. It is designed for compatible ABB Protecta Power distribution assemblies and industrial electrical installations.
The circuit breaker has a rated current of 320 A and a rated ultimate short-circuit breaking capacity of 36 kA at 415 V AC. It uses the ABB SACE Tmax XT5N 400 frame.
The EPX-XT5N-TM3204 incorporates an adjustable TMA thermal-magnetic trip unit. Thermal protection responds to sustained overload conditions, while magnetic protection provides rapid tripping during short circuits. The magnetic trip setting is adjustable over a range of 1600–3200 A.
Yes. The EPX-XT5N-TM3204 is a four-pole (4P) MCCB designed for three-phase and neutral electrical distribution circuits. It features a fully rated neutral pole, allowing all four conductors to be switched together.
The EPX-XT5N-TM3204 belongs to the ABB Protecta Power Devices range and is designed for integration into compatible ABB Protecta Power distribution assemblies. Installation requires the appropriate outgoing MCCB mounting arrangement, electrical connections and accessories specified for the switchboard configuration.
ABB SACE Tmax XT circuit breakers are widely specified by electrical engineers, switchboard manufacturers and industrial contractors for dependable low-voltage circuit protection. The ABB EPX-XT5N-TM3204 320 A four-pole MCCB combines adjustable thermal-magnetic protection, a 36 kA breaking capacity and robust XT5N construction to support safe, reliable and efficient electrical distribution in commercial and industrial installations.