ABB EPX-XT4N-TM2004 is a 200 A four-pole moulded case circuit breaker with 36 kA breaking capacity at 380–415 V AC and adjustable TMA thermal-magnetic protection, designed for reliable low-voltage electrical distribution systems.
£1,159.58
The ABB EPX-XT4N-TM2004 is a high-performance 200 A 4-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in low-voltage electrical distribution systems. Featuring a 36 kA breaking capacity and a TMA adjustable thermal-magnetic trip unit, this circuit breaker delivers dependable protection for commercial, industrial and infrastructure electrical installations.
As part of the ABB Protecta Power distribution range, the EPX-XT4N-TM2004 incorporates proven ABB SACE Tmax XT4N circuit breaker technology. Its thermal-magnetic protection system combines adjustable thermal overload protection with magnetic short-circuit protection, helping protect electrical cables, distribution equipment and connected circuits against excessive current and electrical faults.
With a 200 A rated current, four-pole configuration and 36 kA short-circuit breaking capacity at 380–415 V AC, the EPX-XT4N-TM2004 is suitable for three-phase electrical distribution systems requiring four-pole circuit switching and protection. Its compact XT4 frame and compatibility with Protecta Power distribution equipment make it an effective solution for electrical panel builders, contractors and industrial maintenance engineers.
Moulded case circuit breakers such as the ABB EPX-XT4N-TM2004 protect electrical distribution circuits against overload currents and short-circuit faults. The integrated TMA thermal-magnetic trip unit uses thermal protection to respond to sustained overload conditions and magnetic protection to respond rapidly to high fault currents. Adjustable protection settings allow engineers to configure the breaker according to the requirements of the installation and the associated electrical equipment.
The ABB SACE Tmax XT4N platform combines robust electrical protection with a compact mechanical design suitable for modern switchgear assemblies. With its 200 A rating, four-pole switching arrangement and 36 kA breaking capacity at 380–415 V AC, the EPX-XT4N-TM2004 supports reliable protection of distribution feeders, switchboard circuits and industrial electrical installations. Its integration into ABB Protecta Power systems makes it particularly suitable for panel builders and electrical contractors requiring dependable low-voltage distribution equipment.
| Product range | Protecta Power Devices |
|---|---|
| Circuit breaker family | SACE Tmax XT |
| Series | XT4N |
| ABB order code | 1SDX253956R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current (In) | 200 A |
| Number of poles | 4 |
| Rated ultimate short-circuit breaking capacity (Icu) | 36 kA at 380–415 V AC |
| Trip unit | TMA adjustable thermal-magnetic |
| Thermal protection | Adjustable overload protection |
| Magnetic protection | Adjustable instantaneous short-circuit protection |
| Thermal adjustment range | 140–200 A |
| Magnetic adjustment range | 1,000–2,000 A |
| Frame size | XT4 |
| Frame current rating | 250 A |
| Breaking capacity class | N |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1,000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Mounting arrangement | Fixed installation |
| Terminal arrangement | Front terminals |
| Application | Low-voltage power distribution and circuit protection |
| Applicable standard | IEC 60947-2 |
The ABB EPX-XT4N-TM2004 is a 200 A four-pole moulded case circuit breaker used to protect low-voltage electrical distribution circuits against overloads and short circuits in commercial and industrial installations.
The circuit breaker has a rated current of 200 A, making it suitable for appropriately designed electrical distribution circuits requiring this current rating.
The EPX-XT4N-TM2004 has a 36 kA rated ultimate short-circuit breaking capacity at 380–415 V AC. This indicates the maximum prospective short-circuit current the breaker is rated to interrupt under the specified test conditions.
TMA identifies an adjustable thermal-magnetic trip unit. The thermal element provides overload protection, while the magnetic element provides short-circuit protection. The adjustable settings allow the protection characteristics to be matched to the electrical installation.
Yes. The EPX-XT4N-TM2004 is a four-pole (4P) MCCB designed for applications requiring four-pole switching and circuit protection in three-phase electrical distribution systems.
The EPX-XT4N-TM2004 uses ABB SACE Tmax XT4N circuit breaker technology and is supplied within the ABB Protecta Power Devices product range for electrical distribution applications.
Yes. The TMA trip unit provides adjustable thermal overload protection and magnetic short-circuit protection. The corresponding XT4N 200 A TMA configuration provides a thermal adjustment range of 140–200 A and a magnetic adjustment range of 1,000–2,000 A.
This MCCB is typically installed in low-voltage distribution boards, industrial switchboards and electrical panel assemblies, including compatible ABB Protecta Power distribution systems.
ABB SACE Tmax XT moulded case circuit breakers are trusted by electrical engineers, panel builders, industrial maintenance teams and electrical contractors for dependable overload and short-circuit protection. The ABB EPX-XT4N-TM2004 combines a 200 A rating, four-pole configuration and 36 kA breaking capacity with adjustable thermal-magnetic protection, making it a practical choice for reliable low-voltage power distribution.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.