Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB EPX-XT4N-TM1604 is a 160 A four-pole moulded case circuit breaker with 36 kA short-circuit breaking capacity and adjustable thermal-magnetic TMA protection, designed for commercial and industrial low-voltage electrical distribution systems.
£1,100.62
The ABB EPX-XT4N-TM1604 is a high-performance 160 A four-pole moulded case circuit breaker (MCCB) designed to protect commercial and industrial electrical distribution circuits against overloads and short circuits. Part of the ABB Protecta Power Devices range, this circuit breaker combines a 36 kA short-circuit breaking capacity with dependable thermal-magnetic protection for demanding low-voltage installations.
Built around the ABB SACE Tmax XT4N platform, the EPX-XT4N-TM1604 incorporates a TMA thermal-magnetic trip unit with adjustable overload and instantaneous short-circuit protection. This allows the breaker to respond to sustained excessive current and high fault currents while providing flexibility for electrical protection coordination. Its robust moulded case construction is suited to professional power distribution environments.
With a 160 A rated current, four-pole configuration and 36 kA breaking capacity, this MCCB is suitable for appropriately designed three-phase distribution systems requiring coordinated switching of phase and neutral conductors. Identified by ABB order code 1SDX253954R1, the EPX-XT4N-TM1604 is intended for integration into compatible ABB Protecta Power panelboards and electrical distribution assemblies.
The ABB EPX-XT4N-TM1604 provides essential protection for low-voltage electrical distribution circuits. Its protective mechanism automatically interrupts the circuit when excessive current conditions exceed the configured trip characteristics. This helps protect conductors and connected equipment against damage caused by sustained overloads and short-circuit faults.
The TMA thermal-magnetic trip unit combines thermal overload protection with instantaneous magnetic short-circuit protection. In the corresponding XT4N 160 A configuration, the thermal setting is adjustable from 112–160 A, while the magnetic setting is adjustable from 800–1,600 A. These settings allow electrical designers and installers to coordinate circuit protection with conductor ratings, connected loads and other protective devices.
The four-pole arrangement supports coordinated switching of three phase conductors and a neutral conductor where required by the installation design. The corresponding XT4N TMA configuration incorporates a 100% rated neutral, providing a fully rated neutral protection arrangement. The suitability of four-pole switching and neutral protection must be assessed in accordance with the earthing system and applicable electrical installation requirements.
The ABB SACE Tmax XT4N platform combines robust mechanical construction with substantial current-carrying capability. The EPX-XT4N-TM1604 provides a 160 A current rating and a 36 kA short-circuit breaking capacity, making it suitable for appropriately designed commercial and industrial distribution circuits. Its 140 mm four-pole width also supports efficient installation within compatible electrical distribution equipment.
As part of the ABB Protecta Power range, the EPX-XT4N-TM1604 is intended for integration into compatible panelboards and distribution assemblies using the correct mounting and connection components. Final selection should consider the prospective short-circuit current, operating voltage, cable ratings, protection settings, neutral requirements and applicable electrical standards.
| Product group | Protecta Power Devices |
|---|---|
| Series | Protecta Power / SACE Tmax XT4N |
| ABB order code | 1SDX253954R1 |
| Corresponding ABB XT4N breaker reference | 1SDA068108R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 160 A |
| Number of poles | 4 |
| Electrical configuration | Three-phase and neutral switching |
| Short-circuit breaking capacity | 36 kA |
| Protection technology | Thermal-magnetic |
| Trip unit designation | TMA |
| Rated trip unit current | 160 A |
| Thermal overload adjustment range | 112–160 A |
| Magnetic short-circuit adjustment range | 800–1,600 A |
| Neutral protection rating | 100% of rated current in the corresponding XT4N configuration |
| Protection functions | Adjustable overload and instantaneous short-circuit protection |
| Frame family | XT4 |
| Frame current class | 160 A |
| Frame performance designation | N |
| Number of switched poles | 4 |
| Device width | 140 mm |
| Rated operational voltage of underlying breaker platform | Up to 690 V AC |
| Operating mechanism | Manual switching with automatic protective tripping |
| Corresponding breaker construction | Fixed moulded case circuit breaker |
| Corresponding breaker terminal arrangement | Front terminals |
| Applicable circuit breaker standard | IEC 60947-2 |
| Mounting application | Compatible electrical distribution assemblies |
| Application category | Low-voltage electrical power distribution |
| Typical installation | ABB Protecta Power panelboards and compatible distribution equipment |
The ABB EPX-XT4N-TM1604 is a four-pole moulded case circuit breaker used to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for appropriately designed commercial and industrial installations, including compatible ABB Protecta Power distribution assemblies.
The circuit breaker has a rated current of 160 A. Its corresponding XT4N thermal-magnetic TMA configuration provides adjustable thermal overload protection from 112–160 A, allowing the protection setting to be coordinated with the electrical circuit.
The ABB EPX-XT4N-TM1604 has a specified 36 kA short-circuit breaking capacity. The circuit breaker must be selected with reference to the installation's prospective fault current, operating voltage and applicable protection requirements.
This MCCB incorporates an adjustable thermal-magnetic (TMA) trip unit. The thermal element provides overload protection, while the magnetic element provides instantaneous short-circuit protection. The corresponding XT4N 160 A TMA configuration supports thermal adjustment from 112–160 A and magnetic adjustment from 800–1,600 A.
The four-pole configuration allows coordinated switching of three phase conductors and a neutral conductor where required by the electrical installation design. The corresponding XT4N 160 A TMA configuration includes a 100% rated neutral, supporting applications requiring fully rated neutral protection, subject to the installation's earthing and protection requirements.
ABB Protecta Power protective devices combine established circuit protection technology with practical electrical distribution solutions. The EPX-XT4N-TM1604 offers a robust 160 A, four-pole XT4N MCCB configuration with adjustable thermal-magnetic TMA protection and a 36 kA breaking capacity, supporting dependable protection in demanding commercial and industrial low-voltage distribution installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.