ABB EPX-XT2N-TM1254 is a 125 A four-pole 36 kA TMA thermal-magnetic moulded case circuit breaker from the Protecta Power Devices range, designed for adjustable overload and short-circuit protection in low-voltage electrical distribution systems.
£796.42
The ABB EPX-XT2N-TM1254 is a robust and compact 125 A four-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems. As part of the ABB Protecta Power Devices range, incorporating the established ABB SACE Tmax XT2N circuit breaker platform, it offers reliable circuit protection for commercial, industrial and building infrastructure applications.
This circuit breaker incorporates TMA thermal-magnetic protection technology, combining thermal overload protection with magnetic short-circuit protection. Its four-pole construction supports the switching and isolation of three-phase circuits incorporating a neutral conductor. The XT2N platform is designed to provide effective electrical protection while maintaining a compact footprint within modern distribution boards and electrical panel assemblies.
With a rated current of 125 A, a four-pole configuration and a 36 kA short-circuit breaking capacity at 415 V AC, the EPX-XT2N-TM1254 is suitable for protecting outgoing feeders and distribution circuits in demanding electrical installations. Its compact 120 mm-wide XT2 frame enables space-efficient integration into compatible ABB Protecta Power distribution boards and low-voltage electrical enclosures.
Moulded case circuit breakers such as the ABB EPX-XT2N-TM1254 protect electrical installations by automatically interrupting current when overload or short-circuit conditions occur. The thermal protection element responds to sustained excessive current, helping prevent overheating of cables and connected equipment. The magnetic protection element provides rapid operation during high-current faults, helping limit potential equipment damage and improve the reliability of electrical distribution systems.
The ABB SACE Tmax XT2N platform combines compact construction with established circuit protection technology. Its adjustable thermal protection allows the breaker to be configured within the supported setting range to suit the protected circuit. The four-pole arrangement provides coordinated switching of three phase conductors and a neutral conductor, while the compact frame supports efficient installation in distribution boards where available space is limited. Correct selection of protective settings, cable ratings and short-circuit coordination remains essential for safe and effective operation.
| Product range | Protecta Power Devices |
|---|---|
| Series | SACE Tmax XT2 |
| ABB order code | 1SDX253704R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame designation | XT2N |
| Frame size | 160 A |
| Rated current (In) | 125 A |
| Number of poles | 4 |
| Rated ultimate short-circuit breaking capacity (Icu) | 36 kA at 415 V AC |
| Trip unit type | TMA thermal-magnetic |
| Thermal protection setting range | 87.5–125 A |
| Magnetic trip setting | 1250 A |
| Neutral protection | 100% of rated current on the corresponding XT2N TMA configuration |
| Protection functions | Overload and short-circuit protection |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Electrical system | Low-voltage AC distribution |
| Mounting arrangement | Fixed installation |
| Nominal width | 120 mm |
| Operating mechanism | Manual toggle operation |
| Application | Circuit protection, switching and isolation |
| Product family standard | IEC/EN 60947-2 |
The ABB EPX-XT2N-TM1254 is a four-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for commercial and industrial distribution boards, including compatible ABB Protecta Power assemblies.
The circuit breaker has a 125 A rated current and belongs to the ABB Tmax XT2N 160 A frame family. The frame rating identifies the current class of the circuit breaker platform rather than the rated current of this individual device.
The EPX-XT2N-TM1254 has a 36 kA rated ultimate short-circuit breaking capacity at 415 V AC. The prospective short-circuit current and applicable operating voltage must be considered when selecting the breaker for an electrical installation.
The breaker incorporates a TMA thermal-magnetic trip unit. The thermal element provides adjustable overload protection, while the magnetic element responds to short-circuit faults. The corresponding XT2N 125 A TMA configuration has a thermal adjustment range of 87.5–125 A and a nominal magnetic trip setting of 1250 A.
The four-pole (4P) configuration provides switching of three phase conductors and a neutral conductor, making the breaker suitable for appropriately designed three-phase distribution systems requiring four-pole isolation. The corresponding XT2N 125 A TMA configuration provides neutral protection rated at 100% of the phase current.
Yes. The EPX-XT2N-TM1254 belongs to the ABB Protecta Power Devices range and is intended for integration into compatible electrical distribution assemblies. Appropriate mounting hardware, electrical connections and enclosure compatibility should be verified before installation.
ABB SACE Tmax XT moulded case circuit breakers provide established thermal-magnetic protection technology for commercial and industrial electrical distribution, supporting dependable circuit protection, flexible installation and efficient integration into modern low-voltage distribution assemblies.