ABB EPX-XT2N-TM1004 is a 100 A four-pole moulded case circuit breaker with 36 kA short-circuit breaking capacity and adjustable thermal-magnetic TMA protection, designed for commercial and industrial low-voltage electrical distribution systems.
£646.45
The ABB EPX-XT2N-TM1004 is a compact and reliable 100 A four-pole moulded case circuit breaker (MCCB) designed to provide effective overload and short-circuit protection in commercial and industrial electrical distribution systems. As part of the ABB Protecta Power Devices range, this circuit breaker combines advanced thermal-magnetic protection technology with a 36 kA short-circuit breaking capacity, making it suitable for demanding low-voltage power distribution applications.
Based on the ABB SACE Tmax XT2N circuit breaker platform, the EPX-XT2N-TM1004 is engineered for dependable electrical protection and straightforward integration into compatible distribution assemblies. Its TMA thermal-magnetic trip unit provides adjustable overload and short-circuit protection, helping safeguard electrical installations, conductors and connected equipment. The XT2 frame combines compact dimensions with robust mechanical construction and flexible protection settings.
With a 100 A rated current, four-pole configuration and 36 kA ultimate short-circuit breaking capacity at 415 V AC, the ABB EPX-XT2N-TM1004 is suitable for appropriately designed three-phase electrical distribution circuits requiring coordinated switching of three phases and a neutral conductor. Identified by ABB order code 1SDX253703R1, this MCCB belongs to the Protecta Power range and is intended for integration into compatible ABB electrical distribution equipment.
Moulded case circuit breakers such as the ABB EPX-XT2N-TM1004 provide essential protection within low-voltage electrical distribution systems. They automatically interrupt the electrical supply when overload or short-circuit conditions cause the protective trip mechanism to operate. This helps reduce the risk of excessive conductor heating, electrical equipment damage and disruption caused by electrical faults.
The TMA thermal-magnetic protection system combines two complementary protective functions. The thermal element responds to sustained overload currents, while the magnetic element provides rapid operation during high short-circuit current conditions. For the 100 A XT2N TMA configuration, the thermal protection can be adjusted between 70–100 A, while the magnetic protection can be adjusted between 500–1,000 A. These settings allow the protective response to be coordinated with appropriately designed electrical circuits and connected equipment.
The four-pole configuration provides an important advantage in electrical distribution applications where coordinated switching of three phase conductors and a neutral conductor is required. All four poles operate through a common mechanism, supporting simultaneous circuit switching. The underlying four-pole XT2N TMA configuration uses a neutral protection arrangement that must be considered when designing the installation. Neutral switching and protection requirements depend on the earthing system, conductor arrangement and applicable electrical regulations.
The ABB SACE Tmax XT2N platform combines compact construction with dependable protective performance. Although the XT2 frame family accommodates current ratings up to 160 A, the EPX-XT2N-TM1004 is specifically rated at 100 A. Its 36 kA ultimate and service short-circuit breaking capacities at 415 V AC support applications requiring substantial fault-current protection. Circuit breaker selection must consider prospective fault current, operating voltage, conductor ratings and protection coordination requirements.
As part of the ABB Protecta Power distribution system, the EPX-XT2N-TM1004 is intended for integration into compatible electrical panelboard assemblies using appropriate mounting and connection components. Its compact 120 mm four-pole width, adjustable thermal-magnetic protection and robust XT2 construction make it a practical choice for electrical contractors, panel builders, facilities engineers and industrial maintenance professionals.
| Product group | Protecta Power Devices |
|---|---|
| Series | Protecta Power / SACE Tmax XT2N |
| ABB order code | 1SDX253703R1 |
| Underlying ABB circuit breaker reference | 1SDA067039R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 100 A |
| Number of poles | 4 |
| Electrical configuration | Three-phase and neutral switching |
| Rated ultimate short-circuit breaking capacity (Icu) | 36 kA at 415 V AC |
| Rated service short-circuit breaking capacity (Ics) | 36 kA at 415 V AC |
| Rated operational voltage (Ue), underlying breaker | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1,000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated frequency | 50/60 Hz |
| Protection technology | Thermal-magnetic |
| Trip unit designation | TMA |
| Rated trip unit current | 100 A |
| Thermal overload adjustment range | 70–100 A |
| Magnetic short-circuit adjustment range | 500–1,000 A |
| Protection functions | Adjustable overload and instantaneous short-circuit protection |
| Frame family | XT2 |
| Frame current class | 160 A |
| Frame performance designation | N |
| Number of switched poles | 4 |
| Device width | 120 mm |
| Operating mechanism | Manual switching with automatic protective tripping |
| Underlying breaker construction | Fixed moulded case circuit breaker |
| Underlying breaker terminal arrangement | Front terminals |
| Mounting application | Compatible electrical distribution assemblies |
| Application category | Low-voltage electrical power distribution |
| Typical installation | ABB Protecta Power panelboards and compatible distribution equipment |
The ABB EPX-XT2N-TM1004 is a four-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for commercial and industrial installations, including compatible ABB Protecta Power distribution assemblies.
The circuit breaker has a rated current of 100 A. Its thermal-magnetic TMA trip unit provides adjustable overload protection between 70–100 A, allowing the protection settings to be coordinated with appropriately designed electrical circuits.
The ABB EPX-XT2N-TM1004 has a 36 kA rated ultimate short-circuit breaking capacity at 415 V AC. The underlying XT2N platform also provides a rated service short-circuit breaking capacity of 36 kA at 415 V AC. Suitability must be assessed against the prospective fault current and operating conditions of the installation.
This MCCB incorporates an adjustable thermal-magnetic (TMA) trip unit. The thermal element provides protection against sustained overloads, while the magnetic element provides rapid protection against high short-circuit currents. The 100 A XT2N TMA configuration supports thermal adjustment from 70–100 A and magnetic adjustment from 500–1,000 A.
The four-pole configuration allows coordinated switching of four conductors, typically three phases and a neutral, where required by the electrical installation design. This makes the MCCB suitable for three-phase distribution systems requiring four-pole switching or isolation, subject to the applicable earthing, neutral protection and electrical installation requirements.
ABB Protecta Power protective devices combine established circuit protection technology with practical electrical distribution solutions. The EPX-XT2N-TM1004 offers a compact 100 A, four-pole XT2N MCCB configuration with adjustable thermal-magnetic TMA protection and a 36 kA breaking capacity, supporting dependable protection in commercial and industrial low-voltage distribution installations.