ABB EPX-XT4N-TM2503 (1SDX253487R1) is a 250 A three-pole SACE Tmax XT4N moulded case circuit breaker with a 36 kA short-circuit breaking capacity at 415 V AC and thermal-magnetic adjustable protection for compatible ABB Protecta Power electrical distribution systems.
£1,025.23
The ABB EPX-XT4N-TM2503 is a high-performance 250 A three-pole moulded case circuit breaker (MCCB) designed to provide reliable overload and short-circuit protection in commercial and industrial low-voltage electrical distribution systems. Based on the established ABB SACE Tmax XT4N250 circuit breaker platform, this device combines high-current protection, robust construction and dependable thermal-magnetic trip technology.
Part of the ABB Protecta Power Devices product group, the EPX-XT4N-TM2503 is intended for integration into compatible ABB Protecta Power distribution assemblies. Its thermal-magnetic adjustable (TMA) trip unit provides protection against sustained overloads and short-circuit faults, helping protect electrical cables, connected equipment and distribution infrastructure. The three-pole construction enables coordinated switching and protection of all three phase conductors.
With a rated current of 250 A, a 36 kA short-circuit breaking capacity at 415 V AC and a three-pole (3P) configuration, the EPX-XT4N-TM2503 is well suited to demanding outgoing feeder and sub-distribution applications. Its adjustable thermal protection and established ABB XT4N platform make it a practical choice for electrical contractors, switchboard manufacturers, panel builders and facilities engineers.
Moulded case circuit breakers such as the ABB EPX-XT4N-TM2503 protect electrical distribution systems by automatically interrupting current when overload or short-circuit conditions occur. The thermal protection element responds to sustained excessive current, while the magnetic protection element operates rapidly during short-circuit faults. This combined protection helps reduce the risk of cable damage, electrical equipment failure and disruption to essential power distribution infrastructure.
The ABB SACE Tmax XT4N250 platform provides dependable high-current circuit protection for three-phase electrical networks. Its three-pole construction enables coordinated switching and protection of all three phase conductors, making the EPX-XT4N-TM2503 suitable for outgoing feeders, distribution board circuits and industrial electrical supplies. The TMA trip technology allows the thermal overload setting to be coordinated with the current-carrying capacity of the protected circuit.
The corresponding ABB XT4N250 TMA release provides an adjustable thermal setting from 175 A to 250 A and a nominal magnetic trip setting of 2500 A. These characteristics support dependable protection of higher-current distribution feeders. The exact release fitted to the Protecta Power assembly should be checked against the manufacturer's documentation before applying protection settings.
With a 250 A rated current and 36 kA breaking capacity at 415 V AC, the EPX-XT4N-TM2503 is suited to appropriately designed commercial and industrial installations. Final circuit breaker selection should consider the prospective short-circuit current, operating voltage, conductor sizing, protective device coordination and compatible ABB Protecta Power mounting arrangements.
| Product group | Protecta Power Devices |
|---|---|
| Series | SACE Tmax XT |
| Circuit breaker platform | XT4N250 |
| ABB order code | 1SDX253487R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 250 A |
| Frame rating | 250 A |
| Short-circuit breaking capacity | 36 kA at 415 V AC |
| Number of poles | 3 |
| Pole configuration | Three-pole (3P) |
| Trip unit | Thermal-magnetic adjustable (TMA) |
| Trip technology | Thermal-magnetic |
| Thermal protection | Adjustable overload protection |
| Thermal setting range | 175–250 A on the corresponding ABB XT4N250 TMA release |
| Magnetic protection | Short-circuit protection |
| Nominal magnetic trip setting | 2500 A on the corresponding ABB XT4N250 TMA release |
| Protection functions | Overload and short-circuit protection |
| Rated operational voltage of XT4N platform | Up to 690 V AC |
| Rated insulation voltage of XT4N platform | 1000 V |
| Rated impulse withstand voltage of XT4N platform | 8 kV |
| Applicable circuit breaker standard | IEC 60947-2 |
| Mounting type | Compatible ABB Protecta Power distribution assembly |
| Installation | Fixed distribution board installation using compatible mounting and connection accessories |
| Application | Three-phase low-voltage electrical power distribution |
The ABB EPX-XT4N-TM2503 is a 250 A three-pole moulded case circuit breaker designed to protect high-current three-phase electrical distribution circuits against overloads and short circuits in compatible ABB Protecta Power distribution systems.
The EPX-XT4N-TM2503 has a 250 A rated current and a 36 kA short-circuit breaking capacity at 415 V AC. It is based on the ABB XT4N250 platform, which has a 250 A frame rating. The installation operating voltage and prospective fault current must be considered when selecting the breaker.
TMA stands for Thermal-Magnetic Adjustable. This trip technology combines adjustable thermal overload protection with magnetic short-circuit protection. The corresponding ABB XT4N250 TMA release provides a thermal adjustment range of 175–250 A and a nominal magnetic trip setting of 2500 A. The fitted release characteristics should be confirmed against the manufacturer's documentation.
The three-pole (3P) configuration enables coordinated switching and protection of three phase conductors. This makes the EPX-XT4N-TM2503 suitable for three-phase electrical distribution circuits and appropriately designed industrial equipment supplies. Unlike a four-pole circuit breaker, it does not provide a dedicated switched neutral pole.
The breaker is intended for installation within compatible ABB Protecta Power distribution boards, where it provides high-current outgoing feeder protection. Its ABB XT4N250 platform is suitable for commercial and industrial distribution applications. Compatible mounting, connection and cable management accessories should be selected for the specific distribution assembly.
ABB SACE Tmax XT circuit breakers are widely specified by electrical engineers, contractors and panel builders for dependable low-voltage power distribution. The EPX-XT4N-TM2503 combines 250 A current capacity, three-pole switching, 36 kA short-circuit breaking performance and thermal-magnetic adjustable protection to support reliable electrical installations in commercial and industrial ABB Protecta Power distribution systems.