Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB EPX-XT4N-TM0803 is an 80 A three-pole SACE Tmax XT4N160 moulded case circuit breaker with 36 kA breaking capacity at 415 V AC and adjustable TMA thermal-magnetic protection for commercial and industrial low-voltage electrical distribution systems.
£586.50
The ABB EPX-XT4N-TM0803 is a high-quality 80 A three-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in commercial and industrial low-voltage electrical distribution systems. Part of the ABB Protecta Power Devices range, this circuit breaker incorporates the proven ABB SACE Tmax XT4N platform with a TMA thermal-magnetic trip unit, delivering reliable circuit protection for compatible electrical distribution assemblies.
Featuring a 36 kA rated ultimate short-circuit breaking capacity at 415 V AC, the EPX-XT4N-TM0803 is designed to interrupt electrical faults while protecting cables, switchgear and connected equipment. Its thermal-magnetic protection system combines adjustable thermal overload protection with magnetic short-circuit protection, supporting effective protection of three-phase electrical circuits.
With an 80 A rated current, three-pole configuration and ABB Tmax XT4N160 frame, this MCCB is suitable for outgoing feeders, commercial distribution boards and industrial switchboards. Its robust construction and compatibility with appropriately configured ABB Protecta Power distribution systems make it a practical choice for electrical contractors, panel builders and maintenance engineers.
The ABB EPX-XT4N-TM0803 incorporates a TMA thermal-magnetic trip unit designed to protect electrical installations against sustained overloads and short-circuit faults. The thermal protection element responds to excessive current over time, helping prevent overheating of conductors and connected equipment. The magnetic protection element provides rapid disconnection when high fault currents occur.
The adjustable magnetic trip setting range of 400–800 A provides flexibility when coordinating the circuit breaker with the electrical installation. Combined with adjustable thermal protection, the TMA trip arrangement allows engineers to select suitable protective characteristics according to conductor capacity, circuit loading and fault conditions.
The ABB SACE Tmax XT4N160 platform offers a robust moulded case design for industrial and commercial power distribution. Its three-pole construction enables simultaneous switching of three phase conductors, while the manual operating mechanism supports straightforward circuit operation and resetting.
For installation within ABB Protecta Power distribution boards, the EPX-XT4N-TM0803 should be used with appropriate mounting components, terminal connections and protective covers. Electrical designers should verify prospective fault current, cable sizing, protective device coordination and applicable installation standards before commissioning.
| Product range | Protecta Power Devices |
|---|---|
| Circuit breaker series | SACE Tmax XT |
| Circuit breaker frame | XT4 |
| Performance level | XT4N |
| Frame configuration | XT4N160 |
| ABB order code | 1SDX253482R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 80 A |
| Maximum frame rating | 160 A |
| Number of poles | 3P (three pole) |
| Rated ultimate short-circuit breaking capacity (Icu) | 36 kA at 415 V AC |
| Trip unit designation | TMA |
| Trip technology | Thermal-magnetic |
| Overload protection | Adjustable thermal |
| Short-circuit protection | Adjustable magnetic |
| Magnetic trip setting range | 400–800 A |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Applicable standard | IEC 60947-2 |
| Installation type | Electrical distribution board / switchboard mounting |
| Compatible system | ABB Protecta Power |
| Product category | Protecta Power Devices |
The ABB EPX-XT4N-TM0803 is an 80 A three-pole moulded case circuit breaker designed to protect commercial and industrial low-voltage electrical distribution circuits against overloads and short circuits.
The EPX-XT4N-TM0803 has an 80 A rated current and uses the ABB SACE Tmax XT4N160 platform, which has a maximum frame rating of 160 A.
The EPX-XT4N-TM0803 has a 36 kA rated ultimate short-circuit breaking capacity at 415 V AC. The applicable breaking capacity must be checked against the operating voltage and prospective fault current of the electrical installation.
TMA identifies a thermal-magnetic trip unit providing adjustable thermal overload protection and adjustable magnetic short-circuit protection. These functions help protect electrical conductors and connected equipment against excessive current and fault conditions.
Yes. The ABB XT4N160 TMA 80 A circuit breaker has an adjustable magnetic trip setting range of 400–800 A, allowing the short-circuit protection threshold to be selected according to the requirements of the installation.
Both products use the ABB SACE Tmax XT4N160 three-pole platform and provide 36 kA breaking capacity. The EPX-XT4N-TM0633 has a rated current of 63 A, while the EPX-XT4N-TM0803 has a rated current of 80 A.
Yes. Its three-pole configuration enables simultaneous switching and protection of three phase conductors, making it suitable for compatible three-phase low-voltage distribution circuits requiring an 80 A protective device.
Yes. The EPX-XT4N-TM0803 belongs to the ABB Protecta Power Devices range and is intended for compatible distribution assemblies. Appropriate XT4 mounting components, terminal connections, covers and installation accessories must be selected according to the switchboard configuration.
ABB SACE Tmax XT moulded case circuit breakers provide dependable overload and short-circuit protection for commercial and industrial electrical installations. The EPX-XT4N-TM0803 combines an 80 A three-pole XT4N160 circuit breaker with 36 kA breaking capacity and adjustable TMA thermal-magnetic protection, delivering a reliable solution for compatible ABB Protecta Power distribution assemblies.