ABB EPX-XT2N-TM0503 is a 50 A three-pole Tmax XT2N160 moulded case circuit breaker with a 36 kA breaking capacity at 415 V AC and adjustable TMA thermal-magnetic overload and short-circuit protection for compatible ABB Protecta Power distribution assemblies.
£444.10
The ABB EPX-XT2N-TM0503 is a 50 A, three-pole moulded case circuit breaker (MCCB) designed for reliable overload and short-circuit protection in compatible ABB Protecta Power low-voltage distribution assemblies. Based on the ABB SACE Tmax XT2N160 circuit breaker platform, this device combines a 36 kA breaking capacity at 415 V AC with an adjustable TMA thermal-magnetic trip unit.
Designed for commercial and industrial electrical distribution, the EPX-XT2N-TM0503 provides coordinated protection for three-phase outgoing circuits. Its 50 A rated current, compact XT2 frame and three-pole construction make it suitable for electrical panelboards, sub-distribution systems and appropriately rated equipment feeders.
The TMA thermal-magnetic release incorporates adjustable thermal overload protection and magnetic short-circuit protection. For the corresponding ABB XT2N 160 TMA 50-500 circuit breaker, the thermal setting range is 35–50 A, while the magnetic protection setting range is 250–500 A. These settings enable electrical engineers to coordinate the circuit breaker's response with the installation's conductor ratings and protection requirements.
The XT2N circuit breaker family is engineered for professional low-voltage power distribution and offers a combination of compact construction, mechanical switching capability and dependable fault interruption. The corresponding ABB XT2N 160 TMA configuration uses a fixed mounting arrangement with front terminals, supporting integration into appropriately designed electrical distribution equipment.
Identified by ABB order code 1SDX253468R1, the EPX-XT2N-TM0503 belongs to the ABB Protecta Power Devices range. It provides a manufacturer-specified 50 A outgoing MCCB option for compatible Protecta Power panelboards requiring three-pole thermal-magnetic protection and a 36 kA short-circuit breaking-capacity classification.
The ABB EPX-XT2N-TM0503 provides a practical solution for protecting appropriately rated electrical distribution circuits against overload and short-circuit conditions. By combining the compact ABB Tmax XT2N platform with adjustable thermal-magnetic protection, it supports reliable operation in professional low-voltage distribution systems.
The thermal overload protection function responds to sustained overcurrent conditions that could otherwise cause excessive heating of electrical cables and connected equipment. On the corresponding ABB XT2N 160 TMA 50-500 breaker, the thermal setting can be adjusted from 35–50 A, allowing the protection threshold to be selected according to the conductor rating and expected circuit loading.
The magnetic short-circuit protection function responds to high fault currents. Its adjustable instantaneous threshold, ranging from 250–500 A on the corresponding XT2N TMA device, allows the protective response to be configured according to the installation's fault conditions and coordination requirements.
Unlike electronic trip units, the TMA release uses thermal and magnetic operating elements. This provides a conventional, adjustable protection solution without requiring electronic trip-unit configuration or additional electronic monitoring functions.
The three-pole configuration enables coordinated switching and protection of the three phase conductors in a suitable three-phase electrical system. It is appropriate for installations where a neutral switching pole is not required by the circuit design.
The 36 kA breaking capacity at 415 V AC is an important consideration when selecting protection for installations with significant prospective fault currents. ABB specifies both ultimate and service short-circuit breaking capacities of 36 kA at this voltage for the corresponding XT2N 160 TMA breaker.
Breaking capacity varies with operating voltage. For example, the corresponding ABB XT2N device has an ultimate breaking capacity of 30 kA at 500 V AC and 10 kA at 690 V AC. Electrical designers must therefore use the rating applicable to the actual system voltage rather than assuming the 36 kA classification applies universally.
The ABB XT2N160 frame provides a compact mechanical platform for the 50 A protective device. Its corresponding fixed breaker construction and front terminal arrangement support integration into properly designed electrical distribution equipment.
When installing the EPX-XT2N-TM0503 within an ABB Protecta Power panelboard, the correct mounting arrangement, outgoing connections and protective covers must be selected. Compatibility should be verified using the appropriate ABB Protecta Power installation and selection documentation.
Before commissioning, electrical contractors should confirm conductor current-carrying capacity, termination suitability, protective settings, prospective short-circuit current and coordination with upstream protective devices. The selected thermal and magnetic settings must be appropriate for the circuit and connected equipment.
Combining a 50 A rated current, three-pole construction, 36 kA fault-interruption capability and adjustable TMA protection, the EPX-XT2N-TM0503 provides a dependable outgoing MCCB solution for commercial and industrial electrical distribution applications.
| Product group | Protecta Power Devices |
|---|---|
| Product model | EPX-XT2N-TM0503 |
| ABB order code | 1SDX253468R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Circuit breaker range | ABB SACE Tmax XT |
| Circuit breaker family | XT2N |
| Frame designation | XT2N160 |
| Frame-current designation | 160 A |
| Rated current (In) | 50 A |
| Number of poles | 3 |
| Pole configuration | Three-pole (3P) |
| Breaking-capacity classification | 36 kA |
| Trip unit | TMA |
| Protection technology | Adjustable thermal-magnetic |
| Overload protection | Thermal |
| Short-circuit protection | Magnetic |
| Thermal adjustment range | 35–50 A |
| Instantaneous magnetic adjustment range | 250–500 A |
| Rated operational voltage (Ue) of corresponding XT2N breaker | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 36 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 36 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 30 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 10 kA |
| Operating mechanism | Manual |
| Corresponding breaker installation configuration | Fixed |
| Corresponding breaker terminal arrangement | Front terminals |
| Applicable circuit breaker standard | IEC 60947-2 |
| Corresponding ABB XT2N breaker reference | 1SDA067015R1 |
| Compatible distribution system | ABB Protecta Power |
| Related 40 A three-pole model | EPX-XT2N-TM0403 |
| Related 63 A three-pole model | EPX-XT2N-TM0633 |
| Related 80 A three-pole model | EPX-XT2N-TM0803 |
| Related 50 A XT1N model | EPX-XT1N-TM0503 |
| Primary application | Three-phase outgoing circuit protection in compatible low-voltage distribution assemblies |
The ABB EPX-XT2N-TM0503 is a 50 A three-pole thermal-magnetic MCCB designed for outgoing circuit protection in compatible ABB Protecta Power low-voltage distribution assemblies.
The EPX-XT2N-TM0503 has a rated current of 50 A and belongs to the ABB Tmax XT2N160 circuit breaker family, which uses a 160 A frame designation.
The EPX-XT2N-TM0503 has a 36 kA breaking-capacity classification. The corresponding ABB XT2N 160 TMA breaker has an ultimate short-circuit breaking capacity of 36 kA at 415 V AC.
Yes. The EPX-XT2N-TM0503 is a three-pole (3P) MCCB designed to protect and switch three phase conductors in suitable low-voltage electrical distribution systems.
TMA identifies an adjustable thermal-magnetic trip unit. It provides adjustable thermal overload protection and adjustable instantaneous magnetic short-circuit protection.
The corresponding ABB XT2N 160 TMA 50-500 breaker provides a thermal adjustment range of 35–50 A. The selected setting must be coordinated with the conductor current-carrying capacity and installation requirements.
The corresponding ABB XT2N 160 TMA 50-500 breaker provides an instantaneous magnetic adjustment range of 250–500 A. The setting should be selected according to the circuit's fault conditions and protection coordination requirements.
The EPX-XT2N-TM0503 has a rated current of 50 A, while the EPX-XT2N-TM0633 has a rated current of 63 A. Both are three-pole ABB Tmax XT2N thermal-magnetic MCCB configurations with a 36 kA breaking-capacity classification.
Yes. The EPX-XT2N-TM0503 belongs to the ABB Protecta Power Devices range and is intended for compatible low-voltage distribution assemblies. The correct mounting components, connections and protective covers must be confirmed before installation.
ABB Protecta Power moulded case circuit breakers provide a coordinated approach to low-voltage electrical distribution. The EPX-XT2N-TM0503 combines a 50 A rating, three-pole Tmax XT2N construction, 36 kA breaking capacity and adjustable TMA protection, supporting electrical contractors and panel builders in creating dependable, professionally assembled distribution systems.