ABB EPX-XT2N-TM0403 is a 40 A three-pole moulded case circuit breaker with 36 kA short-circuit breaking capacity and TMA thermal-magnetic protection, designed for reliable overload and short-circuit protection in commercial and industrial low-voltage electrical distribution systems.
£444.10
The ABB EPX-XT2N-TM0403 is a compact and reliable 40 A three-pole moulded case circuit breaker (MCCB) designed to provide dependable overload and short-circuit protection in low-voltage electrical distribution systems. Featuring a 36 kA short-circuit breaking capacity and a TMA thermal-magnetic trip unit, this circuit breaker belongs to the ABB Protecta Power Devices range and uses ABB's established Tmax XT2N circuit breaker technology.
Designed for commercial and industrial electrical installations, the EPX-XT2N-TM0403 combines effective circuit protection with a compact construction suitable for modern power distribution equipment. Its thermal-magnetic protection system provides overload protection and magnetic short-circuit tripping, helping safeguard electrical cables, connected equipment and distribution infrastructure against excessive current and electrical faults.
With a 40 A rated current, three-pole configuration and 36 kA breaking capacity, the ABB EPX-XT2N-TM0403 is particularly suitable for three-phase outgoing circuits in commercial distribution boards, industrial electrical panels and compatible ABB Protecta Power assemblies. Supplied under ABB order code 1SDX253467R1, this MCCB offers a dependable solution for protecting low-voltage electrical distribution circuits.
Moulded case circuit breakers such as the ABB EPX-XT2N-TM0403 protect electrical installations by automatically interrupting current when overload or short-circuit conditions occur. By combining circuit switching with protective tripping mechanisms, MCCBs help reduce the risk of damage to electrical cables, distribution equipment and connected installations.
The TMA thermal-magnetic trip unit uses two complementary protection principles. Its thermal element responds to sustained overload currents, while the magnetic element provides rapid tripping during high-current short circuits. The adjustable thermal protection allows the breaker to be configured for suitable circuit protection requirements, subject to the installation design and manufacturer's settings.
The ABB Tmax XT2N platform provides a compact and robust circuit breaker design for modern low-voltage switchgear. The EPX-XT2N-TM0403 uses a 40 A protective rating within the XT2N frame family, offering three-pole protection for appropriately rated outgoing distribution circuits.
As part of the ABB Protecta Power Devices range, this MCCB is intended for use with compatible electrical distribution equipment. Its 36 kA breaking capacity makes it suitable for installations where the prospective short-circuit current does not exceed the breaker's verified interruption capability at the relevant operating voltage.
| Product group | Protecta Power Devices |
|---|---|
| Series | Tmax XT2 / Protecta Power |
| ABB order code | 1SDX253467R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current | 40 A |
| Number of poles | 3 |
| Pole configuration | 3P |
| Short-circuit breaking capacity | 36 kA |
| Breaking capacity classification | N (normal breaking capacity) |
| Trip unit type | TMA thermal-magnetic |
| Thermal trip setting range | 28–40 A |
| Overload protection | Adjustable thermal trip |
| Short-circuit protection | Magnetic trip |
| Frame family | XT2N |
| Frame rating | 160 A |
| Rated operational voltage (frame family) | Up to 690 V AC |
| Rated insulation voltage (frame family) | 1,000 V |
| Rated impulse withstand voltage (frame family) | 8 kV |
| Applicable standard | IEC/EN 60947-2 |
| Application | Low-voltage electrical distribution |
| Installation type | Compatible electrical distribution board / switchgear assembly |
| Operating mechanism | Manual toggle-operated circuit breaker |
| Typical electrical system | Three-phase AC distribution |
The ABB EPX-XT2N-TM0403 is a three-pole moulded case circuit breaker designed to protect low-voltage electrical distribution circuits against overloads and short circuits. It is suitable for compatible commercial and industrial distribution assemblies, including ABB Protecta Power systems.
The EPX-XT2N-TM0403 has a 40 A rated current. Its thermal-magnetic protection system is designed to provide overcurrent protection for appropriately rated electrical distribution circuits.
The ABB EPX-XT2N-TM0403 has a specified 36 kA short-circuit breaking capacity. This represents its fault-interruption capability under the applicable rated conditions. The installation voltage and prospective fault current must be checked to confirm suitability.
TMA thermal-magnetic protection combines a thermal overload protection element with a magnetic short-circuit protection element. The thermal mechanism responds to sustained excessive current, while the magnetic mechanism trips rapidly when a sufficiently high short-circuit current occurs.
Yes. The corresponding ABB XT2N 40 A TMA trip unit provides an adjustable thermal protection setting, typically within a 28–40 A range. The appropriate setting must be selected according to the protected circuit and the manufacturer's installation requirements.
Yes. The three-pole (3P) configuration allows the circuit breaker to switch and protect three phase conductors together, making it suitable for appropriately designed three-phase low-voltage distribution circuits.
The ABB manufacturer order code is 1SDX253467R1. The corresponding product reference is EPX-XT2N-TM0403, identifying the 40 A, three-pole, 36 kA thermal-magnetic MCCB within the ABB Protecta Power Devices range.
This MCCB is typically installed within compatible electrical distribution boards, switchgear assemblies and commercial or industrial distribution panels. It is particularly suitable for ABB Protecta Power installations requiring 40 A three-pole outgoing circuit protection.
ABB Protecta Power circuit protection devices combine established Tmax XT circuit breaker technology with practical integration into modern electrical distribution systems. The EPX-XT2N-TM0403 provides dependable 40 A three-pole thermal-magnetic protection and a 36 kA breaking capacity for appropriately specified commercial and industrial installations.