ABB EPX-XT5S-TM6303 is a 630 A three-pole Tmax XT5S moulded case circuit breaker with a 50 kA breaking-capacity classification and adjustable TMA thermal-magnetic overload and short-circuit protection for compatible Protecta Power low-voltage distribution assemblies.
£2,085.44
The ABB EPX-XT5S-TM6303 is a high-performance 630 A, three-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT5S range, designed for compatible ABB Protecta Power low-voltage electrical distribution assemblies. Featuring a 50 kA breaking-capacity classification and an adjustable TMA thermal-magnetic trip unit, this circuit breaker provides dependable overload and short-circuit protection for demanding commercial and industrial installations.
Built around the ABB Tmax XT5S 630 circuit breaker platform, the EPX-XT5S-TM6303 combines a 630 A rated current with three-pole switching and adjustable protection characteristics. Its thermal-magnetic release responds to sustained overload conditions and high short-circuit currents, helping protect electrical conductors, distribution equipment and connected installations.
The TMA trip unit provides adjustable thermal overload protection and magnetic short-circuit protection. For the corresponding ABB XT5S 630 TMA configuration, the thermal setting range is 252–630 A, while the instantaneous magnetic setting range is 3150–6300 A. These adjustments allow electrical engineers to configure the protective response according to the installation's operating conditions and coordination requirements.
Identified by ABB order code 1SDX248631R1, the EPX-XT5S-TM6303 forms part of the ABB Protecta Power Devices range. It provides a manufacturer-specified 630 A outgoing MCCB option for compatible distribution panelboards requiring substantial current capacity, adjustable thermal-magnetic protection and a 50 kA fault-interruption classification.
High-current electrical distribution systems require protective devices capable of responding effectively to overloads and short-circuit faults. The ABB EPX-XT5S-TM6303 combines the ABB Tmax XT5S circuit breaker platform with an adjustable thermal-magnetic trip unit, supporting reliable protection of appropriately designed commercial and industrial distribution circuits.
The thermal protection function responds to sustained overload currents that could otherwise produce excessive heating in electrical conductors and connected equipment. On the corresponding ABB XT5S 630 TMA breaker, the thermal setting can be adjusted within a range of 252–630 A. This allows the protection setting to be coordinated with the cable current-carrying capacity and the intended operating load.
The magnetic protection function responds to high short-circuit currents. Its adjustable instantaneous operating threshold, specified as 3150–6300 A on the corresponding XT5S 630 TMA configuration, allows the short-circuit response to be selected according to the requirements of the installation.
Unlike electronic trip units, the TMA thermal-magnetic release provides protection through thermal and magnetic operating elements. This makes it a practical choice for installations where adjustable overload and instantaneous short-circuit protection are required without additional electronic monitoring functions.
The three-pole configuration provides coordinated switching and protection of the three phase conductors. It is suitable for appropriately designed three-phase electrical distribution circuits, with any neutral conductor arrangement addressed separately according to the electrical system design.
The 50 kA breaking-capacity classification is an important consideration when specifying protection for distribution systems with substantial prospective fault currents. The actual interrupting capability must be confirmed at the installation's rated operating voltage, and the device must be selected to satisfy the applicable short-circuit protection requirements.
For installation within the ABB Protecta Power system, the EPX-XT5S-TM6303 must be matched with the appropriate panelboard mounting and connection arrangements. ABB advises that a side cableway extension box may be considered for XT5 outgoing devices where larger cables require additional installation space.
Electrical designers should also verify conductor sizes, terminal compatibility, protective coordination, ambient temperature and the thermal performance of the completed assembly. The corresponding ABB XT5S 630 TMA breaker uses a fixed configuration with front terminals, but the supplied Protecta Power arrangement should be checked before installation.
With its substantial current rating, adjustable thermal-magnetic protection and ABB Tmax XT5S construction, the EPX-XT5S-TM6303 provides a practical solution for high-capacity outgoing circuit protection in professionally assembled low-voltage distribution systems.
| Product group | Protecta Power Devices |
|---|---|
| Product model | EPX-XT5S-TM6303 |
| ABB order code | 1SDX248631R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Circuit breaker range | ABB SACE Tmax XT |
| Circuit breaker family | XT5S |
| Frame configuration | XT5S 630 |
| Rated current | 630 A |
| Number of poles | 3 |
| Pole configuration | Three-pole (3P) |
| Breaking-capacity classification | 50 kA, subject to the applicable operating voltage and ABB technical data |
| Trip unit | TMA |
| Trip technology | Adjustable thermal-magnetic |
| Overload protection | Thermal |
| Short-circuit protection | Magnetic |
| Thermal adjustment range | 252–630 A for the corresponding XT5S 630 TMA breaker |
| Instantaneous magnetic adjustment range | 3150–6300 A for the corresponding XT5S 630 TMA breaker |
| Operating mechanism | Manual toggle operation |
| Installation configuration | Fixed in the corresponding XT5S 630 TMA breaker |
| Terminal arrangement | Front terminals in the corresponding XT5S 630 TMA breaker |
| Applicable circuit breaker standard | IEC 60947-2 |
| Compatible distribution system | ABB Protecta Power |
| Related 400 A three-pole model | EPX-XT5S-TM4003 |
| Related 630 A four-pole model | EPX-XT5S-TM6304 |
| Related 630 A electronic LS/I model | EPX-XT5S-E1-6303 |
| Related 630 A electronic LSI model | EPX-XT5S-E2-6303 |
| Application | High-capacity outgoing circuit protection in compatible low-voltage distribution assemblies |
The ABB EPX-XT5S-TM6303 is a 630 A three-pole thermal-magnetic MCCB designed for high-capacity outgoing circuit protection in compatible ABB Protecta Power low-voltage distribution assemblies.
The EPX-XT5S-TM6303 has a rated current of 630 A and uses the ABB Tmax XT5S 630 circuit breaker platform.
The EPX-XT5S-TM6303 is specified with a 50 kA breaking-capacity classification in the ABB Protecta Power range. The applicable breaking capacity must be verified at the installation's operating voltage.
Yes. The EPX-XT5S-TM6303 is a three-pole (3P) MCCB designed to protect and switch three phase conductors in suitable low-voltage electrical distribution systems.
TMA identifies an adjustable thermal-magnetic trip unit. It provides thermal overload protection and magnetic short-circuit protection, with adjustable settings on the corresponding ABB XT5S 630 TMA breaker.
The corresponding ABB XT5S 630 TMA breaker provides a thermal adjustment range of 252–630 A. The selected setting must be coordinated with the connected conductors and installation requirements.
The corresponding ABB XT5S 630 TMA breaker has an instantaneous magnetic adjustment range of 3150–6300 A. The setting must be selected according to the installation's fault conditions and protection coordination requirements.
The EPX-XT5S-TM6303 uses adjustable TMA thermal-magnetic protection, while the EPX-XT5S-E1-6303 is the corresponding 630 A three-pole XT5S model with electronic LS/I protection.
Yes. The EPX-XT5S-TM6303 belongs to the ABB Protecta Power Devices range and is intended for compatible low-voltage distribution assemblies. The appropriate panelboard mounting, connection and cable accommodation arrangements must be confirmed before installation.
ABB Protecta Power moulded case circuit breakers provide a coordinated solution for demanding electrical distribution applications. The EPX-XT5S-TM6303 combines a 630 A rating, three-pole Tmax XT5S construction, 50 kA breaking-capacity classification and adjustable TMA protection, supporting professional electrical contractors and panel builders in delivering dependable low-voltage distribution assemblies.
We use cookies