1SDA132708R1 ABB XT1H 125 TMF 60-600 3-Pole Fixed Circuit Breaker

1SDA132708R1 ABB XT1H 125 TMF 60-600 3-Pole Fixed Circuit Breaker

ABB 1SDA132708R1 is an XT1H 125 three-pole fixed moulded-case circuit breaker with a 60 A TMF thermal-magnetic trip unit, 600 A instantaneous magnetic protection and UL/CSA configuration.

SKU: 1SDA132708R1MPN: 1SDA132708R1
Price
List Price £6,579.37 ex VAT
Your Price (ex VAT) Save 25%
£4,934.53 25% OFF
You save £1,644.84 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,934.53
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,934.53

Why Choose the ABB 1SDA132708R1 XT1H 125 Circuit Breaker?

The ABB 1SDA132708R1 is a SACE Tmax XT1H 125 moulded-case circuit breaker with a 60 A TMF thermal-magnetic trip unit, three-pole configuration and fixed installation. Designed for UL/CSA applications, it provides dependable overload and short-circuit protection for commercial and industrial low-voltage distribution systems.

The breaker uses ABB's TMF fixed thermal-magnetic trip unit, combining a 60 A rated current with a 600 A instantaneous magnetic trip setting. This fixed protection arrangement provides straightforward circuit protection without requiring electronic trip-unit configuration or an auxiliary power supply.

As an XT1H breaker, the 1SDA132708R1 provides the H short-circuit performance level in the compact XT1 frame. It is configured as a three-pole fixed breaker with front terminals and is suitable for UL/CSA low-voltage distribution applications requiring substantial interrupting capability.

Key Advantages

  • Genuine ABB SACE Tmax XT moulded-case circuit breaker.
  • 60 A rated current with fixed thermal-magnetic protection.
  • 600 A instantaneous magnetic trip setting.
  • XT1H high short-circuit performance for demanding distribution applications.
  • Three-pole fixed configuration with front terminals.
  • Designed for UL/CSA applications.

Key Features

  • SACE Tmax XT1H 125 frame.
  • TMF thermal-magnetic trip unit.
  • 60 A nominal current.
  • 600 A instantaneous magnetic protection.
  • 3-pole configuration.
  • Fixed (F) breaker execution.
  • Front (F) terminal connection.
  • UL/CSA configuration for North American applications.

Compact Thermal-Magnetic Protection with High Breaking Capacity

The ABB SACE Tmax XT1 combines compact construction with robust protection for low-voltage power distribution. Its TMF trip unit uses thermal protection for overload conditions and magnetic protection for high-current short circuits, providing a simple and dependable protection system without electronic adjustment.

The ABB 1SDA132708R1 combines a 60 A TMF release with the XT1H performance level, including an interrupting rating of 65 kA at 480 V AC under UL 489. This makes it suitable for three-phase circuits where compact fixed installation and high fault-current interruption capability are required.

Typical Applications

  • Industrial low-voltage distribution panels.
  • Commercial electrical distribution systems.
  • Three-phase feeder circuit protection.
  • Machinery and equipment power distribution.
  • Industrial switchboards and control panels.
  • UL/CSA low-voltage electrical installations.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA132708R1
Product type Moulded-case circuit breaker
Frame XT1
Short-circuit performance level H
Frame rated uninterrupted current 125 A
Trip unit TMF
Release type Thermal-magnetic
Rated current 60 A
Instantaneous magnetic trip setting 600 A
Number of poles 3
Mounting execution Fixed
Terminal connection Front
Terminal type Bolt
Rated voltage 600Y/347 V
Rated operational voltage 600Y/347 V AC / 500 V DC
UL 489 interrupting rating at 240 V AC 100 kA
UL 489 interrupting rating at 480 V AC 65 kA
UL 489 interrupting rating at 600Y/347 V AC 25 kA
Standard UL 489

Frequently Asked Questions

What is the ABB 1SDA132708R1?

The ABB 1SDA132708R1 is an XT1H 125 three-pole fixed moulded-case circuit breaker with a 60 A TMF thermal-magnetic trip unit for UL/CSA applications.

What is the rated current of the ABB 1SDA132708R1?

The breaker has a rated current of 60 A.

What does TMF 60-600 mean?

TMF identifies the fixed thermal-magnetic release; this configuration has a 60 A rated current and 600 A instantaneous magnetic trip setting.

What is the interrupting rating of the XT1H 1SDA132708R1?

The XT1H performance level provides a UL 489 interrupting rating of 100 kA at 240 V AC, 65 kA at 480 V AC and 25 kA at 600Y/347 V AC.

What does F F mean in the XT1H configuration?

The F F designation identifies a fixed breaker execution with front terminal connections, providing a conventional installation arrangement for compatible switchboards and distribution panels.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded-case circuit breakers combine compact construction, dependable thermal-magnetic protection and high short-circuit performance for commercial and industrial low-voltage power distribution.