Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA125714R1 Emax 3 E2.3B 2000 Ekip Aware LSI four-pole withdrawable air circuit breaker moving part for high-current low-voltage power distribution.
£8,063.10
The ABB 1SDA125714R1 is an Emax 3 E2.3B 2000 air circuit breaker moving part equipped with an Ekip Aware LSI electronic trip unit and configured as a four-pole withdrawable moving part (WMP).
Designed for low-voltage power distribution systems, this 2000 A SACE Emax 3 circuit breaker provides adjustable long-time, short-time and instantaneous overcurrent protection for demanding industrial and commercial installations.
The E2.3B platform combines high-current switching capability with electronic protection, making the ABB 1SDA125714R1 suitable for main incomers, feeders and distribution applications where dependable circuit protection and maintainability are required.
The ABB 1SDA125714R1 provides a high-current Emax 3 solution for electrical distribution systems requiring dependable circuit protection and controlled switching. Its Ekip Aware LSI release provides adjustable long-time, short-time and instantaneous protection functions to suit the characteristics of the connected installation.
As a four-pole withdrawable moving part, the unit is designed for switchgear assemblies where maintainability and practical access to the circuit breaker are important. The E2.3B 2000 platform provides a 42 kA Icu rating at 440 V AC for demanding low-voltage distribution applications.
Tick the specs you need, then view products that match.
| Device Type | ACB | |
|---|---|---|
| Current | 2000 A | |
| Poles | 4-pole | |
| Phase | Three Phase | |
| Breaking Capacity | 42 kA | |
| Trip Unit | LSI | |
| Application | Power distribution | |
| Mounting Type | Withdrawable | |
| Manufacturer | ABB | |
| Series | SACE Emax 3 | |
| Model | E2.3B 2000 | |
| Part Number | 1SDA125714R1 | |
| Product Type | Air circuit breaker moving part | |
| Rated Current | 2000 A | |
| Protection Functions | Long-time, short-time and instantaneous | |
| Long-Time Setting I1 | 800–2000 A | |
| Instantaneous Setting I3 | 3000–30000 A | |
| Number of Poles | 4 | |
| Configuration | Withdrawable moving part (WMP) | |
| Auxiliary Contacts | 4 | |
| Rated Voltage | Up to 690 V AC | |
| Rated Short-Circuit Breaking Capacity Icu | 42 kA at 440 V AC | |
| Short-Time Withstand Current Icw | 42 kA for 1 s | |
| Ingress Protection | IP30 | |
| Power Dissipation | 450 W | |
| HS Code | 85362090 |
ABB 1SDA125714R1 is an Emax 3 E2.3B 2000 four-pole withdrawable moving part with an Ekip Aware LSI electronic trip unit and a 2000 A rated current.
The Ekip Aware LSI release provides long-time, short-time and instantaneous overcurrent protection functions with adjustable settings.
The ABB 1SDA125714R1 has a rated current of 2000 A.
The ABB 1SDA125714R1 is configured as a four-pole withdrawable moving part.
The unit is suitable for high-current low-voltage distribution applications including industrial switchboards, main distribution boards, feeder protection and infrastructure power systems.
ABB SACE Emax 3 circuit breakers combine high-current switching capability with configurable electronic protection for demanding low-voltage power distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.