ABB 1SDA125708R1 Emax 3 E2.3H 1600 A four-pole withdrawable air circuit breaker moving part with Ekip Aware LI electronic protection for low-voltage power distribution.
£7,597.95
The ABB 1SDA125708R1 is a high-performance four-pole withdrawable air circuit breaker (ACB) moving part for the ABB SACE Emax 3 E2.3H platform. It is configured with an Ekip Aware LI electronic trip unit and a 1600 A frame rating, providing dependable protection and monitoring for low-voltage electrical distribution systems.
Designed for demanding power distribution applications, the Emax 3 E2.3H platform combines advanced electronic protection with a robust withdrawable construction. The moving part allows the circuit breaker to be withdrawn from its fixed installation position for inspection, maintenance and servicing while supporting efficient switchboard operation.
The ABB 1SDA125708R1 is a 1600 A, four-pole E2.3H circuit breaker moving part with Ekip Aware LI protection. Its Ekip Aware LI configuration provides long-time and instantaneous overcurrent protection, with adjustable long-time current settings and instantaneous protection suitable for high-capacity low-voltage distribution applications.
The ABB SACE Emax 3 E2.3H platform is designed for high-capacity low-voltage electrical distribution where dependable circuit protection, switching capability and serviceability are essential. The electronic Ekip Aware LI trip unit provides adjustable protection parameters to help coordinate the breaker with the wider distribution system.
The withdrawable construction allows the breaker assembly to be moved between operating and withdrawn positions within a compatible switchboard. This configuration can simplify inspection and maintenance activities while helping electrical engineers manage high-current distribution equipment efficiently.
Tick the specs you need, then view products that match.
| Trip Unit | LI | |
|---|---|---|
| Device Type | ACB | |
| Current | 1600 A | |
| Poles | 4-pole | |
| Phase | Three Phase | |
| Breaking Capacity | 100 kA | |
| Application | Power distribution | |
| Mounting Type | Withdrawable | |
| Manufacturer | ABB | |
| Series | SACE Emax 3 | |
| Breaker family | E2.3H | |
| Model / ordering code | 1SDA125708R1 | |
| Product type | Withdrawable air circuit breaker moving part | |
| Rated current | 1600 A | |
| Number of poles | 4-pole | |
| Trip unit | Ekip Aware LI | |
| Long-time current setting I1 | 640–1600 A | |
| Instantaneous current setting I3 | 2400–24000 A | |
| Rated short-circuit breaking capacity Icu at 440 V | 100 kA | |
| Rated short-time withstand current Icw for 1 s | 85 kA | |
| Installation type | Withdrawable / draw-out | |
| Electrical system | Low-voltage power distribution | |
| HS Code | 85362090 |
The ABB 1SDA125708R1 is a four-pole withdrawable moving part for an Emax 3 E2.3H air circuit breaker used for high-capacity low-voltage power distribution and circuit protection.
The E2.3H configuration associated with the 1SDA125708R1 has a rated current of 1600 A.
The 1SDA125708R1 is configured with an Ekip Aware LI electronic trip unit providing long-time and instantaneous overcurrent protection.
The long-time current setting I1 is adjustable from 640–1600 A, while the instantaneous setting I3 is adjustable from 2400–24000 A.
Yes. The 1SDA125708R1 is a four-pole withdrawable moving part designed for use with the ABB SACE Emax 3 E2.3H air circuit breaker system.