Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA125311R1 is an E1.3N 630 Ekip Aware LI three-pole air circuit-breaker designed for low-voltage power distribution and circuit protection.
£3,830.89
The ABB 1SDA125311R1 is an E1.3N 630 Ekip Aware LI three-pole air circuit-breaker from the ABB SACE Emax 3 range, designed for dependable low-voltage power distribution and circuit protection. It combines a 630 A rated current with an electronic Ekip Aware release and LI protection functions for demanding industrial and commercial electrical systems.
The E1.3N 630 configuration provides a high short-circuit breaking capacity suitable for power distribution applications, while the Ekip Aware electronic release provides adjustable overload and short-circuit protection. The withdrawable moving-part configuration supports installation within compatible Emax 3 switchgear assemblies and facilitates servicing and equipment replacement.
With a 630 A rated permanent current, 690 V rated voltage and three-pole construction, the ABB 1SDA125311R1 is suited to transformer, generator, feeder and general installation protection where reliable switching and controlled interruption are required.
Air circuit-breakers such as the ABB Emax 3 E1.3N provide controlled switching and protection for low-voltage electrical distribution systems. The electronic Ekip Aware release monitors electrical conditions and provides configurable protection against overload and short-circuit events.
The ABB 1SDA125311R1 combines a 630 A current rating with three-pole construction and Ekip Aware LI protection. Its E1.3N class provides a 66 kA short-circuit breaking capacity at 400 V AC, making the breaker suitable for demanding distribution installations where high fault-current interruption capability is required.
Tick the specs you need, then view products that match.
| Trip Unit | LI | |
|---|---|---|
| Device Type | ACB | |
| Current | 630 A | |
| Poles | 3-pole | |
| Phase | Three Phase | |
| Breaking Capacity | 66 kA | |
| Application | Power distribution | |
| Mounting Type | Withdrawable | |
| Manufacturer | ABB | |
| Series | SACE Emax 3 | |
| Model | E1.3N 630 Ekip Aware LI 3p WMP | |
| Order code | 1SDA125311R1 | |
| Product type | Air circuit-breaker | |
| Rated permanent current (Iu) | 630 A | |
| Rated voltage | 690 V AC | |
| Number of poles | 3 | |
| Trip unit | Ekip Aware | |
| Protection functions | LI | |
| Overload release setting | 252–630 A | |
| Instantaneous short-circuit release setting | 945–9450 A | |
| Rated short-circuit breaking capacity (Icu) at 400 V AC | 66 kA | |
| Power loss | 62 W | |
| Degree of protection | IP30 | |
| Configuration | Withdrawable / moving part | |
| EAN | 8056221258630 | |
| HS Code | 85362090 |
The ABB 1SDA125311R1 is an E1.3N 630 Ekip Aware LI three-pole air circuit-breaker from the ABB SACE Emax 3 range.
The circuit-breaker has a 630 A rated permanent current.
The circuit-breaker uses an Ekip Aware electronic release with LI protection functions, providing adjustable overload and instantaneous short-circuit protection.
The ABB 1SDA125311R1 has a rated short-circuit breaking capacity of 66 kA at 400 V AC.
The circuit-breaker is designed for low-voltage power distribution, transformer, generator, feeder and installation protection within compatible ABB SACE Emax 3 switchgear systems.
ABB SACE Emax 3 air circuit-breakers provide engineered switching and protection solutions for demanding low-voltage electrical distribution systems, combining electronic trip technology with configurations suited to professional switchgear applications.