ABB 1SDA125124R1 Emax 3 E2.3B air circuit breaker with 2000 A rated current, four-pole fixed construction and Ekip Aware LI electronic release for low-voltage power distribution protection.
£7,146.84
The ABB 1SDA125124R1 is an Emax 3 E2.3B 2000 air circuit breaker designed for reliable low-voltage power distribution protection in demanding industrial and commercial installations. This four-pole fixed circuit breaker combines a 2000 A rated current with an Ekip Aware LI electronic release for dependable long-time overload and instantaneous short-circuit protection.
With its E2.3B breaking-capacity class, rear-mounted horizontal terminals and fixed construction, the 1SDA125124R1 provides a robust solution for switchboards, distribution systems and other high-current electrical installations where controlled interruption and reliable circuit protection are essential.
As part of the ABB SACE Emax 3 platform, this circuit breaker combines high-current switching capability with electronic protection and intelligent functionality for modern low-voltage power distribution systems.
The ABB Emax 3 E2.3B 2000 is designed to provide dependable protection and switching for high-current low-voltage electrical distribution systems. Its Ekip Aware LI release provides long-time overload and instantaneous short-circuit protection to help safeguard conductors, switchgear and connected equipment against damaging overcurrents.
The four-pole fixed construction and rear horizontal terminals make the 1SDA125124R1 suitable for integration into suitably designed distribution boards and switchboards. Its 2000 A rating provides substantial current-handling capability for high-demand distribution applications.
Tick the specs you need, then view products that match.
| Trip Unit | LI | |
|---|---|---|
| Device Type | ACB | |
| Current | 2000 A | |
| Poles | 4-pole | |
| Phase | Three Phase | |
| Breaking Capacity | 42 kA | |
| Application | Power distribution | |
| Mounting Type | Fixed | |
| Brand | ABB | |
| Product family | SACE Emax 3 | |
| Breaker type | E2.3B | |
| Rated current | 2000 A | |
| Number of poles | 4 | |
| Installation | Fixed | |
| Trip unit | Ekip Aware LI | |
| Long-time current setting | 800–2000 A | |
| Instantaneous current setting | 3000–30000 A | |
| Rated ultimate short-circuit breaking capacity, Icu at 440 V AC | 42 kA | |
| Short-time withstand current, Icw for 1 s | 42 kA | |
| Terminal arrangement | Rear-mounted, horizontal | |
| Auxiliary contacts | 4 | |
| Contact position indication | Open/closed | |
| HS Code | 85362090 |
ABB 1SDA125124R1 is an Emax 3 E2.3B 2000 Ekip Aware LI four-pole fixed air circuit breaker for low-voltage power distribution protection.
The ABB 1SDA125124R1 has a rated current of 2000 A.
The 1SDA125124R1 uses an Ekip Aware LI electronic release providing long-time overload and instantaneous short-circuit protection.
The ABB 1SDA125124R1 is a fixed four-pole circuit breaker with rear-mounted horizontal terminals.
The ABB 1SDA125124R1 has a rated ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a short-time withstand current of 42 kA for 1 s.
ABB Emax 3 circuit breakers provide advanced circuit protection and switching for modern low-voltage power distribution systems, helping machine builders, panel builders and industrial operators develop reliable electrical infrastructure.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.