ABB EPX-A1B-016L2 (1SDA123195R1) 16 A single-pole Formula A1C125 thermal-magnetic outgoing MCCB with LSC L2 connection arrangement for compatible ABB Protecta Power distribution panelboards.
£194.77
The ABB EPX-A1B-016L2 is a 16 A single-pole moulded case circuit breaker (MCCB) supplied with an LSC L2 connection arrangement for compatible ABB Protecta Power electrical distribution panelboards. Identified by ABB order code 1SDA123195R1, this device forms part of the Protecta Power Devices product group and provides a dedicated outgoing circuit protection solution for suitable low-voltage distribution assemblies.
Based on the ABB Formula A1C125 circuit breaker platform, the EPX-A1B-016L2 uses thermal-magnetic protection to respond to overload and short-circuit conditions. Its 16 A current rating and single-pole (1P) configuration make it suitable for appropriately designed outgoing circuits where a compact MCCB-based protection arrangement is required.
The L2 designation identifies the specified connection variant within ABB's Protecta Power single-pole outgoing device range. ABB also lists corresponding L1 and L3 variants, allowing the correct version to be selected for the intended panelboard connection position. The EPX-A1B-016L2 combines the specified circuit breaker with its associated LSC arrangement, supporting coordinated integration into compatible Protecta Power distribution equipment.
Outgoing circuit breakers are essential components of a low-voltage distribution panelboard. Each outgoing protective device must be selected to suit the connected circuit, conductor characteristics and available fault level. The ABB EPX-A1B-016L2 provides a 16 A single-pole MCCB solution for compatible Protecta Power assemblies, allowing the specified outgoing circuit to be protected using ABB's Formula A1 device platform.
The product's thermal-magnetic protection arrangement provides two complementary functions. The thermal element responds to sustained overcurrent conditions that may otherwise cause excessive conductor heating, while the magnetic element responds to sufficiently high short-circuit currents. These functions help protect the outgoing circuit when the breaker is correctly selected and installed in accordance with the manufacturer's instructions.
The A1C125 designation identifies the Formula circuit breaker family, while the 16 A rating identifies the current rating of this particular device. The 125 A frame designation must not be confused with the 16 A circuit breaker rating. The device should be selected according to its actual protective characteristics and the requirements of the outgoing circuit.
ABB's Protecta Power selection literature identifies the 16 A single-pole A1 outgoing MCCB as an 18 kA device. The applicable short-circuit breaking capacity must nevertheless be checked at the installation's operating voltage and against the exact device documentation. A circuit breaker must have adequate breaking capacity for the prospective fault current at its installed position, unless an approved coordinated protection arrangement permits otherwise.
The LSC L2 designation is important when specifying the correct outgoing device variant. ABB lists the corresponding EPX-A1B-016L1, EPX-A1B-016L2 and EPX-A1B-016L3 references within its Protecta Power single-pole outgoing range. These variants should not be treated as interchangeable without checking the required connection arrangement and panelboard configuration.
For the Protecta Power outgoing MCCB system, ABB specifies that an MCCB base plate and cover are required with each outgoing device. The EPX-A1B-016L2 should therefore be considered part of a complete outgoing circuit assembly rather than a fully installed, standalone distribution solution. The correct mounting accessories, covers and any additional connection components must be confirmed against the selected panelboard.
ABB's published Protecta Power selection information identifies a maximum cable capacity of 50 mm² for A1 single-pole devices. This is a product-range connection limit rather than a recommended conductor size for a 16 A circuit. The actual cable cross-section must be determined from the load, installation method, protective device characteristics, terminal compatibility and applicable wiring regulations.
The EPX-A1B-016L2 is particularly relevant where a project requires a 16 A outgoing MCCB with the L2 connection variant. Correct selection supports consistent panelboard construction and helps avoid ordering an otherwise similar device with the wrong connection designation. Installation and commissioning should be carried out by competent electrical personnel using the current ABB technical documentation.
| Product group | Protecta Power Devices |
|---|---|
| Compatible distribution range | ABB Protecta Power |
| ABB order code | 1SDA123195R1 |
| Manufacturer product description | A1C125 16A 1p + LSC L2 TMA |
| Product type | Moulded case circuit breaker (MCCB) with LSC arrangement |
| Device application | Outgoing circuit protection |
| Rated current | 16 A |
| Number of poles | 1P (single-pole) |
| Device family | ABB Formula A1C125 |
| Frame size | 125 A family |
| Protection technology | Thermal-magnetic |
| Trip designation | TMA, as specified in the product description |
| Overload protection | Thermal protection function |
| Short-circuit protection | Magnetic protection function |
| Published outgoing device breaking-capacity classification | 18 kA; confirm applicable rated operational voltage and detailed breaking-capacity data |
| Connection arrangement | LSC L2 |
| Connection variant | L2 |
| Alternative position variants | EPX-A1B-016L1 and EPX-A1B-016L3 |
| Maximum published A1 single-pole cable capacity | 50 mm², subject to terminal and installation requirements |
| Mounting accessories | Appropriate MCCB base plate and cover required for the outgoing assembly |
| Operating functionality | Manual switching and automatic overcurrent tripping |
| System type | Low-voltage electrical distribution |
| Application | Compatible Protecta Power outgoing circuits |
The ABB EPX-A1B-016L2 is a 16 A single-pole thermal-magnetic MCCB with an LSC L2 connection arrangement. It is designed for compatible ABB Protecta Power outgoing distribution circuits and provides overload and short-circuit protection.
L2 identifies the specified connection variant within ABB's Protecta Power single-pole outgoing device range. ABB also lists EPX-A1B-016L1 and EPX-A1B-016L3 variants. The correct version should be selected according to the approved panelboard connection arrangement.
The EPX-A1B-016L2 has a 16 A current rating and a single-pole (1P) configuration. It belongs to the ABB Formula A1C125 circuit breaker family. The 125 A frame designation does not change the device's specified 16 A rating.
The EPX-A1B-016L2 uses thermal-magnetic protection. The thermal function responds to sustained overload conditions, while the magnetic function responds to short-circuit conditions. ABB's Protecta Power literature identifies the corresponding 16 A single-pole A1 outgoing device with an 18 kA breaking-capacity classification; the applicable voltage and detailed ratings must be verified before installation.
Yes. ABB's Protecta Power selection literature specifies that an MCCB base plate and cover are required with each outgoing device. The correct accessories must be selected for the panelboard and circuit breaker arrangement. The EPX-A1B-016L2 should not be treated as a complete enclosed outgoing distribution assembly on its own.
ABB Protecta Power provides coordinated low-voltage distribution components for commercial and industrial electrical installations. The EPX-A1B-016L2 combines a 16 A single-pole Formula A1C125 circuit breaker with thermal-magnetic protection and an LSC L2 connection arrangement, giving electrical contractors and panel builders a clearly identified outgoing protection option for compatible Protecta Power assemblies.
We use cookies