Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA107706R1 is a fixed three-pole SACE Tmax XT4V 160 moulded-case circuit breaker with a 52 A MA magnetic trip unit, front terminals, adjustable 260–520 A instantaneous protection and 150 kA ultimate short-circuit breaking capacity at 415 V AC.
£1,074.15
The ABB 1SDA107706R1, designated XT4V 160 MA 52 Im=260...520 3p F F, is a three-pole ABB SACE Tmax XT4 moulded-case circuit breaker designed particularly for motor protection applications. It combines the compact XT4 frame with a 52 A MA magnetic-only trip unit, providing adjustable instantaneous short-circuit protection without a thermal overload protection function.
The MA release provides an adjustable magnetic trip threshold from 260–520 A, equivalent to approximately 5–10 × In. This makes the breaker particularly suitable for motor circuits where overload protection is provided separately and the MCCB is required to provide high-performance short-circuit protection while accommodating normal motor starting currents.
The 1SDA107706R1 uses ABB's XT4V high-breaking-capacity configuration, providing an ultimate short-circuit breaking capacity of 150 kA at 415 V AC. It is supplied as a complete three-pole breaker for fixed installation with front terminals, providing a compact solution for demanding industrial motor and distribution applications.
The MA magnetic release is designed for applications where instantaneous short-circuit protection is required without integral thermal overload protection. On the 1SDA107706R1, the magnetic threshold is adjustable from 260–520 A, allowing the trip level to be coordinated with motor starting characteristics while maintaining rapid protection against high fault currents.
The XT4V configuration provides particularly high short-circuit performance for a compact XT4 breaker, reaching 150 kA at 415 V AC and 50 kA at 690 V AC. In motor applications, the MA breaker is typically coordinated with separate overload protection and switching equipment to provide a complete motor control and protection solution.
| Series | SACE Tmax XT / Tmax XT 250 Range |
|---|---|
| Order code | 1SDA107706R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Application | Motor protection |
| Frame | XT4V 160 |
| Trip unit | MA |
| Protection technology | Magnetic |
| Rated current | 52 A |
| Instantaneous magnetic protection setting | 260–520 A |
| Magnetic adjustment | 5–10 × In |
| Number of poles | 3 |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Rated voltage | 690 V |
| Ultimate short-circuit breaking capacity at 415 V AC | 150 kA |
| Ultimate short-circuit breaking capacity at 690 V AC | 50 kA |
| Power loss | 4.7 W |
| Operating mechanism | Toggle |
| Front degree of protection | IP20 |
| Integrated earth-fault protection | No |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Complete device with protection unit | Yes |
| EAN / GTIN | 8015644103736 |
| Customs tariff number | 85362090 |
The 1SDA107706R1 is an ABB SACE Tmax XT4V 160 three-pole moulded-case circuit breaker with a 52 A MA magnetic trip unit, adjustable 260–520 A instantaneous protection, fixed mounting and front terminals.
The breaker has a rated current of 52 A. Its instantaneous magnetic protection can be adjusted from 260–520 A.
The MA trip unit provides magnetic short-circuit protection and is particularly suited to motor applications. It does not provide conventional thermal overload protection, so appropriate separate overload protection should be used where required by the application.
The XT4V configuration provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC and 50 kA at 690 V AC.
XT4V 160 identifies the XT4 high-breaking-capacity frame, MA 52 identifies the 52 A magnetic protection unit, Im=260...520 specifies the adjustable instantaneous magnetic trip range, 3p denotes three poles, and F F identifies fixed mounting with front terminals.
ABB SACE Tmax XT moulded-case circuit breakers provide compact and configurable protection for industrial power systems, with the 1SDA107706R1 combining a 52 A MA magnetic release, adjustable 260–520 A instantaneous protection and 150 kA breaking capacity at 415 V AC for demanding three-phase motor applications.