1SDA107596R1 ABB XT6H 800 Ekip Dip LS/I In=630 4P F F

1SDA107596R1 ABB XT6H 800 Ekip Dip LS/I In=630 4P F F

ABB 1SDA107596R1 is a fixed four-pole SACE Tmax XT6H 800 moulded-case circuit breaker with a 630 A Ekip Dip LS/I electronic trip unit, front terminals and 70 kA ultimate short-circuit breaking capacity at 415 V AC.

SKU: 1SDA107596R1MPN: 1SDA107596R1
Price
List Price £3,020.48 ex VAT
Your Price (ex VAT) Save 25%
£2,265.36 25% OFF
You save £755.12 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,265.36
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,265.36

Why Choose the ABB 1SDA107596R1 XT6H 800 Ekip Dip LS/I 630A Circuit Breaker?

The ABB 1SDA107596R1, designated XT6H 800 Ekip Dip LS/I In=630 4p F F, is a four-pole ABB SACE Tmax XT6 moulded-case circuit breaker designed for high-performance protection of low-voltage power distribution systems. It combines an XT6H 800 frame with a 630 A Ekip Dip LS/I solid-state trip unit, providing electronic overload and short-circuit protection.

The XT6H offers ABB's H short-circuit performance level, with an ultimate short-circuit breaking capacity of 70 kA at 415 V AC. Its Ekip Dip LS/I release provides long-time overload protection together with selectable short-time or instantaneous short-circuit protection, supporting effective coordination in industrial and commercial distribution networks.

The 1SDA107596R1 is supplied as a four-pole fixed circuit breaker with front terminals. It has a rated operational voltage of 690 V AC, a rated insulation voltage of 1000 V and an impulse withstand voltage of 8 kV, making it a robust solution for demanding IEC low-voltage installations.

Key Advantages

  • Genuine ABB SACE Tmax XT6 moulded-case circuit breaker.
  • 630 A Ekip Dip LS/I electronic trip unit for configurable circuit protection.
  • Provides long-time overload and short-time or instantaneous short-circuit protection.
  • Four-pole construction for three-phase distribution systems with neutral.
  • High 70 kA ultimate breaking capacity at 415 V AC.
  • Fixed mounting with front terminals for straightforward switchboard integration.
  • Electronic protection provides greater adjustment flexibility than conventional thermomagnetic releases.

Key Features

  • ABB SACE Tmax XT6H 800 frame.
  • Ekip Dip LS/I solid-state release.
  • Rated current: 630 A.
  • Overload setting range: 252–630 A.
  • Short-circuit setting range: 630–6300 A.
  • Number of poles: 4.
  • Current type: AC.
  • Mounting: Fixed.
  • Main terminals: Front terminals.
  • Short-circuit performance level: H.
  • Front degree of protection: IP20.

High-Performance Electronic LS/I Protection

The Ekip Dip LS/I release combines electronic long-time overload protection with configurable short-circuit protection. Its overload setting can be adjusted across 252–630 A, while the short-circuit setting extends from 630–6300 A. This flexibility allows the protection characteristics to be coordinated with conductors, downstream equipment and other protective devices within the distribution system.

Combined with the XT6H high-breaking-capacity frame, the 1SDA107596R1 is particularly well suited to installations with significant prospective fault currents. The breaker provides both Icu and Ics performance of 70 kA at 415 V AC, while its fixed construction and front terminals provide a practical configuration for integration into low-voltage switchboards and distribution assemblies.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-distribution switchboards.
  • Commercial and infrastructure electrical distribution.
  • Four-wire three-phase AC distribution systems.
  • Feeder and distribution circuit protection.
  • Installations requiring high short-circuit breaking capacity.
  • Systems requiring adjustable electronic overload and short-circuit protection.
  • Fixed MCCB installations requiring a 630 A electronic trip unit.

Technical Specifications

Series SACE Tmax XT / Tmax XT 250 Range
Order code 1SDA107596R1
Product type Moulded-case circuit breaker (MCCB)
Product main type SACE Tmax XT
Frame size XT6
Frame designation XT6H 800
Trip unit Ekip Dip LS/I
Trip unit technology Solid-state / electronic
Rated current 630 A
Rated uninterrupted current 800 A
Overload release setting 252–630 A
Short-circuit release setting 630–6300 A
Number of poles 4
Current type AC
Mounting Fixed
Terminal arrangement Front terminals
Operating mechanism Toggle
Short-circuit performance level H
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 8 kV
Rated frequency 50/60 Hz
Ultimate breaking capacity at 415 V AC 70 kA
Service breaking capacity at 415 V AC 70 kA
Ultimate breaking capacity at 440 V AC 50 kA
Ultimate breaking capacity at 500 V AC 50 kA
Ultimate breaking capacity at 690 V AC 25 kA
Rated short-time withstand current 10 kA
Front degree of protection IP20
Power loss 33.2 W
Product width 268 mm
Product height 280 mm
Product depth 103.5 mm
Product net weight 12 kg
Standard IEC 60947-2
GTIN 8056221028301
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA107596R1?

The 1SDA107596R1 is an ABB SACE Tmax XT6H 800 four-pole moulded-case circuit breaker with a 630 A Ekip Dip LS/I solid-state trip unit, fixed mounting and front terminals.

What is the rated current of the ABB 1SDA107596R1?

The breaker uses an Ekip Dip LS/I release rated at 630 A. It is installed in an XT6H frame with a rated uninterrupted current of 800 A.

What protection does the Ekip Dip LS/I trip unit provide?

The Ekip Dip LS/I trip unit provides electronic long-time overload protection together with short-time or instantaneous short-circuit protection. The overload setting is adjustable from 252–630 A and the short-circuit setting from 630–6300 A.

What is the breaking capacity of the ABB XT6H 1SDA107596R1?

The XT6H configuration has an ultimate short-circuit breaking capacity of 70 kA at 415 V AC. Its rated service short-circuit breaking capacity at 415 V AC is also 70 kA.

What does XT6H 800 Ekip Dip LS/I In=630 4p F F mean?

XT6H 800 identifies the XT6 frame with H short-circuit performance level, Ekip Dip LS/I identifies the electronic trip unit, In=630 specifies its 630 A rated current, 4p denotes four poles, and F F identifies fixed construction with front terminals.

Trusted ABB High-Performance Circuit Protection

ABB SACE Tmax XT moulded-case circuit breakers combine robust construction with configurable electronic protection, with the 1SDA107596R1 delivering 630 A four-pole Ekip Dip LS/I protection and 70 kA breaking performance at 415 V AC for demanding low-voltage distribution applications.