1SDA107569R1 ABB XT6N 800 TMA 630-6300 4P F F InN=100%In

1SDA107569R1 ABB XT6N 800 TMA 630-6300 4P F F InN=100%In

ABB 1SDA107569R1 is a fixed four-pole SACE Tmax XT6N 800 moulded-case circuit breaker with a 630 A TMA thermomagnetic release, front terminals, adjustable 3150–6300 A instantaneous protection and a fully rated neutral at 100% of the phase current.

SKU: 1SDA107569R1MPN: 1SDA107569R1
Price
List Price £2,360.34 ex VAT
Your Price (ex VAT) Save 25%
£1,770.26 25% OFF
You save £590.09 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,770.26
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,770.26

Why Choose the ABB 1SDA107569R1 XT6N 800 TMA 630-6300 4P Circuit Breaker?

The ABB 1SDA107569R1, designated XT6N 800 TMA 630-6300 4p F F InN=100%In, is a four-pole ABB SACE Tmax XT6 moulded-case circuit breaker designed for dependable protection of low-voltage AC and DC distribution systems. It combines a 630 A TMA thermomagnetic trip unit with adjustable instantaneous protection in a fixed-mounted XT6N 800 frame.

The TMA release provides thermal overload protection together with adjustable magnetic short-circuit protection. On this configuration, the instantaneous protection setting I3 is adjustable from 3150–6300 A, allowing the breaker to be coordinated with the requirements of the protected distribution circuit.

The 1SDA107569R1 is supplied as a four-pole fixed circuit breaker with front terminals and a fully rated neutral. The InN=100%In configuration means the neutral pole is rated for the full phase current, making this version particularly suitable for four-wire distribution systems where full neutral capacity is required.

Key Advantages

  • Genuine ABB SACE Tmax XT6 moulded-case circuit breaker.
  • 630 A TMA thermomagnetic release for overload and short-circuit protection.
  • Adjustable instantaneous magnetic protection from 3150–6300 A.
  • Four-pole construction for three-phase and neutral distribution systems.
  • 100% fully rated neutral for applications requiring full neutral current capacity.
  • Fixed mounting with front terminals for conventional switchboard installation.
  • Suitable for both AC and DC circuit protection applications within the breaker's specified ratings.

Key Features

  • ABB SACE Tmax XT6N 800 frame.
  • TMA thermomagnetic trip unit.
  • Rated current: 630 A.
  • Instantaneous protection I3: 3150–6300 A.
  • Number of poles: 4.
  • Neutral rating: 100% of phase rated current.
  • Mounting: Fixed.
  • Connection: Front terminals.
  • Interruption rating class: N.
  • Designed and certified for IEC applications.

Thermomagnetic Protection with a Fully Rated Neutral

The ABB TMA trip unit combines thermal overload protection with instantaneous magnetic short-circuit protection. For the 1SDA107569R1, the magnetic protection setting I3 can be adjusted from 3150–6300 A, providing flexibility when coordinating the breaker with downstream equipment, conductors and the expected characteristics of the electrical distribution system.

Unlike XT6 four-pole configurations with reduced neutral protection, the 1SDA107569R1 incorporates a fully rated neutral at 100% of the phase current. This makes it particularly appropriate for four-wire systems where the neutral conductor must carry the same rated current as the phase conductors, while the fixed construction and front terminals provide a practical arrangement for switchboard integration.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-distribution switchboards.
  • Commercial building electrical distribution.
  • Four-wire systems requiring a fully rated neutral.
  • Feeder and distribution circuit protection.
  • AC and DC distribution applications within the circuit breaker's specified ratings.
  • Fixed-mounted MCCB installations requiring adjustable thermomagnetic protection.

Technical Specifications

Series SACE Tmax XT / Tmax XT 250 Range
Order code 1SDA107569R1
Alternate catalogue number XT6NE4630BFF000XXX
Product type Moulded-case circuit breaker (MCCB)
Frame size XT6
Frame designation XT6N 800
Trip unit TMA thermomagnetic
Rated current 630 A
Instantaneous protection setting I3 3150–6300 A
Number of poles 4
Neutral rating 100% of phase rated current
Neutral configuration Fully rated neutral
Mounting Fixed
Terminal arrangement Front terminals
Interruption rating N
Application AC/DC circuit protection
Standard IEC
Certification IEC
Product net width 280 mm
Product net height 268 mm
Product net depth 103.5 mm
Product net weight 12 kg
Minimum order quantity 1 piece
EAN / UPC 8015644102227
Customs tariff number 85362090
RoHS Compliant with EU Directive 2011/65/EU and amendment 2015/863

Frequently Asked Questions

What is the ABB 1SDA107569R1?

The 1SDA107569R1 is an ABB SACE Tmax XT6N 800 four-pole moulded-case circuit breaker with a 630 A TMA thermomagnetic release, fixed mounting, front terminals and a fully rated neutral.

What is the rated current of the ABB 1SDA107569R1?

The circuit breaker has a rated current of 630 A and uses an ABB TMA thermomagnetic trip unit.

What is the instantaneous short-circuit protection range?

The TMA release provides adjustable instantaneous magnetic protection with an I3 setting range of 3150–6300 A.

What does InN=100%In mean on the ABB 1SDA107569R1?

InN=100%In means the neutral is fully rated at 100% of the phase rated current. This differs from reduced-neutral configurations where the neutral protection is set below the phase rating.

What does XT6N 800 4p F F mean?

XT6N 800 identifies the Tmax XT6 frame and N interruption-rating class, 4p identifies the four-pole configuration, and F F identifies the fixed circuit breaker construction with front terminals.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded-case circuit breakers combine robust construction, coordinated protection and flexible installation options, with the 1SDA107569R1 providing 630 A four-pole thermomagnetic protection, adjustable 3150–6300 A instantaneous protection and a fully rated neutral for demanding low-voltage distribution applications.