1SDA102913R1 ABB XT7S 1200 Ekip Touch LSIG 1200 3p F F UL

1SDA102913R1 ABB XT7S 1200 Ekip Touch LSIG 1200 3p F F UL

ABB 1SDA102913R1 is a SACE Tmax XT7S 1200 three-pole fixed moulded case circuit breaker with front terminals, a 1200 A Ekip Touch LSIG electronic trip unit and UL configuration.

SKU: 1SDA102913R1MPN: 1SDA102913R1
Price
List Price £7,374.35 ex VAT
Your Price (ex VAT) Save 25%
£5,530.76 25% OFF
You save £1,843.59 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,530.76
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,530.76

Why Choose the ABB XT7S 1200 Ekip Touch LSIG 1200 3p F F UL?

The ABB XT7S 1200 Ekip Touch LSIG 1200 3p F F UL, order code 1SDA102913R1, is a high-current SACE Tmax XT moulded case circuit breaker designed for demanding low-voltage power-distribution systems. It combines the XT7S 1200 breaker frame with an advanced Ekip Touch LSIG solid-state electronic trip unit rated at 1200 A.

The Ekip Touch LSIG trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. This comprehensive electronic protection package provides adjustable protection for feeders and distribution circuits while supporting selective coordination and integrated ground-fault protection.

This configuration is a three-pole, fixed circuit breaker with front terminals and a lever operating mechanism. Designed for AC systems and certified for UL applications, the XT7S performance level provides an interrupting rating of 50 kA at 480 V AC, making it suitable for substantial industrial and commercial distribution installations.

Key Advantages

  • 1200 A rated current for high-current distribution applications.
  • Ekip Touch LSIG advanced electronic protection.
  • Long-time protection against sustained overload conditions.
  • Short-time protection supports selective short-circuit coordination.
  • Instantaneous protection provides rapid response to severe short-circuit faults.
  • Integrated ground-fault protection for enhanced system protection.
  • 50 kA interrupting rating at 480 V AC.
  • Three-pole, fixed construction with front terminals.
  • Designed and certified for UL applications.

Key Features

  • ABB SACE Tmax XT7S 1200 moulded case circuit breaker.
  • 1200 A rated current and rated uninterrupted current.
  • Ekip Touch LSIG solid-state electronic trip unit.
  • LSIG protection: long-time, short-time, instantaneous and ground-fault.
  • S short-circuit performance level.
  • 65 kA at 240 V AC UL 489 interrupting rating.
  • 50 kA at 480 V AC UL 489 interrupting rating.
  • 25 kA at 600 V AC UL 489 interrupting rating.
  • 3-pole construction.
  • Fixed installation with front terminals.
  • Lever operating mechanism.
  • Designed for 50/60 Hz AC distribution systems.
  • UL certified configuration.
  • ABB order code 1SDA102913R1.

Advanced Ekip Touch LSIG Protection

The Ekip Touch LSIG trip unit combines four essential protection functions within an advanced electronic platform. Long-time protection responds to sustained overloads, short-time protection assists selective coordination, instantaneous protection provides rapid interruption of severe short-circuit currents, and ground-fault protection detects potentially damaging current paths to earth.

Combined with the XT7S 1200 platform and full 1200 A current rating, the ABB 1SDA102913R1 provides comprehensive protection for high-current distribution systems. Its 50 kA at 480 V AC interrupting rating, fixed construction and front-terminal arrangement make it particularly suitable for demanding switchboard, feeder and main-distribution applications.

Typical Applications

  • Industrial low-voltage power-distribution systems.
  • High-current commercial electrical switchboards.
  • 1200 A three-phase feeder protection.
  • Main and sub-main distribution circuits.
  • Power-distribution panels and switchgear assemblies.
  • Circuits requiring advanced electronic LSIG protection.
  • Applications requiring integrated ground-fault protection.
  • Systems requiring 50 kA interrupting capability at 480 V AC.
  • UL low-voltage electrical installations.

Technical Specifications

Series SACE Tmax XT
Frame XT7S 1200
ABB order code 1SDA102913R1
Alternate catalogue number XT7SU312EQFF000XXX
Product type Moulded case circuit breaker (MCCB)
Rated current (In) 1200 A
Rated uninterrupted current (Iu) 1200 A
Trip unit Ekip Touch LSIG
Trip-unit technology Solid-state electronic
Protection functions L / S / I / G
Long-time protection Overload
Short-time protection Short-circuit
Instantaneous protection Short-circuit
Ground-fault protection Integrated
Short-circuit performance level S
UL 489 interrupting rating at 240 V AC 65 kA
UL 489 interrupting rating at 480 V AC 50 kA
UL 489 interrupting rating at 600 V AC 25 kA
Rated operational voltage 600 V AC
Rated frequency 50 / 60 Hz
Number of poles 3
Mounting Fixed
Terminal arrangement Front terminals
Operating mechanism Lever
Current type AC
Standard UL
EAN 8015644034245

Frequently Asked Questions

What is the rated current of ABB 1SDA102913R1?

The ABB 1SDA102913R1 has a rated current and rated uninterrupted current of 1200 A.

What protection does the Ekip Touch LSIG trip unit provide?

The Ekip Touch LSIG trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and integrated ground-fault protection.

What is the interrupting rating of ABB 1SDA102913R1?

Under UL 489, the XT7S configuration provides interrupting ratings of 65 kA at 240 V AC, 50 kA at 480 V AC and 25 kA at 600 V AC.

How is the ABB XT7S 1SDA102913R1 configured?

It is a three-pole, fixed-mounted moulded case circuit breaker with front terminals, a lever operating mechanism and an Ekip Touch LSIG electronic trip unit.

Is ABB 1SDA102913R1 suitable for ground-fault protection?

Yes. The G function in the LSIG protection package provides integrated ground-fault protection alongside long-time, short-time and instantaneous protection.

Trusted ABB Circuit Protection

ABB SACE Tmax XT moulded case circuit breakers combine high-current capability, substantial short-circuit performance and advanced Ekip electronic protection to provide dependable circuit protection for demanding industrial and commercial low-voltage distribution systems.