1SDA101952R1 ABB XT2V 160 Ekip Dip LIG 10A 3P Fixed Circuit Breaker

1SDA101952R1 ABB XT2V 160 Ekip Dip LIG 10A 3P Fixed Circuit Breaker

ABB 1SDA101952R1 is an XT2V 160 three-pole fixed moulded case circuit breaker with front terminals, a 10 A Ekip Dip LIG electronic trip unit and 150 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA101952R1MPN: 1SDA101952R1
Price
List Price £1,819.79 ex VAT
Your Price (ex VAT) Save 25%
£1,364.84 25% OFF
You save £454.95 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,364.84
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,364.84

Why Choose the ABB XT2V 160 Ekip Dip LIG In=10A 3p F F Circuit Breaker?

The ABB 1SDA101952R1, product type XT2V 160 Ekip Dip LIG In=10A 3p F F, is a high-performance three-pole moulded case circuit breaker (MCCB) designed for protection of low-voltage power distribution systems. As part of the ABB SACE Tmax XT range, it combines the compact XT2 frame with an Ekip Dip LIG electronic trip unit to provide dependable overload, instantaneous short-circuit and earth-fault protection.

This circuit breaker features a fixed three-pole configuration with front terminals for straightforward integration into switchboards, distribution panels and industrial electrical assemblies. The Ekip Dip LIG electronic release provides adjustable protection settings, while the XT2V short-circuit performance level delivers exceptionally high breaking capacity for demanding installations.

With a 10 A rated Ekip Dip LIG trip unit and an XT2 frame rated for an uninterrupted current of 160 A, the 1SDA101952R1 provides precise protection within a compact platform. The XT2V version offers an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for electrical systems where very high prospective fault currents may occur.

Key Advantages

  • High-performance three-pole moulded case circuit breaker for low-voltage power distribution.
  • 10 A Ekip Dip LIG electronic trip unit for precise circuit protection.
  • Exceptional 150 kA ultimate breaking capacity at 380–415 V AC.
  • Provides overload, instantaneous short-circuit and earth-fault protection.
  • Fixed construction with front terminals for convenient switchboard installation.
  • Compact ABB Tmax XT2 design combines high breaking performance with efficient use of panel space.

Key Features

  • ABB SACE Tmax XT2V 160 moulded case circuit breaker.
  • Three-pole configuration for three-phase electrical systems.
  • 10 A rated Ekip Dip LIG electronic release.
  • 160 A rated uninterrupted current (Iu) for the XT2 frame.
  • 150 kA ultimate breaking capacity at 380–415 V AC.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage and 8 kV impulse withstand voltage.
  • Fixed construction with front terminal connections.

Reliable Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB Tmax XT2 protect low-voltage electrical installations against damaging overcurrents and fault conditions. The Ekip Dip LIG electronic release provides long-time overload, instantaneous short-circuit and ground-fault protection, allowing the circuit breaker to isolate faults and help protect cables, equipment and distribution infrastructure.

The XT2V performance level is engineered for installations requiring particularly high short-circuit interruption capability. Combined with the compact XT2 platform, fixed mounting and front terminals, the 1SDA101952R1 provides a practical protection solution for industrial switchboards, commercial power distribution and OEM electrical assemblies.

Typical Applications

  • Low-voltage power distribution switchboards.
  • Industrial electrical distribution panels.
  • Commercial and infrastructure electrical systems.
  • OEM machinery and control-panel assemblies.
  • Protection of feeders, cables and distribution circuits.
  • Installations with high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA101952R1
Product type Moulded case circuit breaker (MCCB)
Application Power distribution protection
Frame XT2
Short-circuit performance level V
Trip unit Ekip Dip LIG
Release type Electronic
Trip unit rated current (In) 10 A
Rated uninterrupted current (Iu) 160 A
Number of poles 3
Rated operational voltage 690 V AC / 500 V DC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate breaking capacity (Icu) 200 kA at 220–240 V AC
Service breaking capacity (Ics) 150 kA at 380–440 V AC
Installation Fixed
Terminal connection Front terminals
Current type AC
Mechanical durability 25,000 cycles
Electrical durability 8,000 cycles
Power loss 0.1 W per pole at rated operating conditions
Standard IEC 60947
Weight approx. 1.3 kg
EAN 8056221019965

Frequently Asked Questions

What is the ABB 1SDA101952R1 used for?

The ABB 1SDA101952R1 is a three-pole Tmax XT2V moulded case circuit breaker designed to protect low-voltage power distribution circuits against overloads, short circuits and earth faults.

What is the rated current of the Ekip Dip LIG trip unit?

The installed Ekip Dip LIG electronic trip unit is rated at 10 A, while the XT2 circuit-breaker frame has a rated uninterrupted current of 160 A.

What breaking capacity does the XT2V 160 provide?

The XT2V version provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for demanding installations with high prospective fault currents.

What protection functions are included with the Ekip Dip LIG release?

The Ekip Dip LIG electronic release provides long-time overload, instantaneous short-circuit and ground-fault protection for low-voltage distribution circuits.

How is the ABB 1SDA101952R1 installed?

The circuit breaker is a fixed three-pole unit with front terminals, designed for installation within low-voltage switchboards, distribution panels and similar electrical assemblies.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where compact construction, dependable electrical protection and high short-circuit performance are required.