Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA101820R1 XT7L M 1250 is a 1250 A four-pole fixed moulded case circuit breaker with Ekip Dip LIG solid-state protection, front terminals and 120 kA L-class interruption performance for demanding low-voltage AC power systems.
£6,671.72
The ABB 1SDA101820R1, designated XT7L M 1250 Ekip Dip LIG In=1250A 4p F F, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage AC power systems. Part of the ABB SACE Tmax XT7 range, it combines a 1250 A rated uninterrupted current with an Ekip Dip LIG solid-state trip unit and the high short-circuit interruption capability of the XT7L platform.
The ABB Ekip Dip LIG electronic trip unit provides long-time overload (L), instantaneous short-circuit (I) and ground-fault (G) protection. This protection combination is particularly useful where overload and rapid short-circuit protection are required alongside ground-fault protection, without the short-time protection function found on LSI and LSIG releases.
With a rated operational voltage of 690 V AC, four-pole construction, fixed installation and front terminals, the 1SDA101820R1 is engineered for integration into high-capacity switchboards and power distribution assemblies. The XT7L platform provides 120 kA interruption performance, supporting dependable fault clearing in installations with very high prospective short-circuit currents.
Moulded case circuit breakers such as the ABB Tmax XT7 protect low-voltage electrical systems against damaging overcurrents while providing dependable switching and isolation. The XT7L platform is designed for demanding installations, with its 120 kA interruption performance helping safeguard cables, switchgear and connected equipment where prospective short-circuit currents are particularly high.
The Ekip Dip LIG release combines adjustable long-time overload protection with instantaneous short-circuit and ground-fault protection. Together with the 1250 A rating, four-pole construction and 690 V AC operational voltage, the 1SDA101820R1 provides a robust solution for industrial, generator, transformer and plant protection applications requiring high interruption performance and ground-fault detection.
| Series | SACE Tmax XT |
|---|---|
| Frame | XT7M |
| ABB order code | 1SDA101820R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated uninterrupted current (Iu) | 1250 A |
| Trip unit rated current (In) | 1250 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | Ekip Dip LIG |
| Release type | Electronic / solid-state |
| Protection functions | L, I and G |
| Overload release adjustment | 500–1250 A |
| Instantaneous short-circuit release adjustment | 1250–12,500 A |
| Interruption rating | L |
| Short-circuit interruption performance | 120 kA |
| Installation version | Fixed |
| Main circuit connection | Bolted connection |
| Terminal configuration | Front terminals |
| Manual operating element | Toggle |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Degree of protection | IP20 |
| Power loss | 57 W |
| DIN rail mounting | No |
| Standard | IEC |
| EAN / UPC | 8056221018647 |
The ABB 1SDA101820R1 is a 1250 A four-pole moulded case circuit breaker designed for protection and switching in demanding low-voltage systems, including industrial distribution, transformer, generator and plant applications.
The circuit breaker is fitted with an Ekip Dip LIG solid-state trip unit, providing long-time overload, instantaneous short-circuit and ground-fault protection.
LIG denotes long-time overload (L), instantaneous short-circuit (I) and ground-fault (G) protection. Unlike LSI or LSIG releases, this configuration does not include a short-time (S) protection function.
The XT7L M 1250 is an L-class circuit breaker with 120 kA short-circuit interruption performance, making it suitable for low-voltage systems with very high prospective fault currents.
The 1SDA101820R1 is a four-pole fixed circuit breaker with bolted front terminals. It uses manual toggle operation and can be equipped with an optional motor drive for powered operation.
ABB SACE Tmax XT moulded case circuit breakers are widely specified by panel builders, electrical engineers and industrial operators for dependable electronic protection, ground-fault protection, high short-circuit interruption capability and reliable high-capacity low-voltage power distribution.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.