1SDA101808R1 ABB XT7L M 1250 Ekip G Touch LSIG 1250A 4P Circuit Breaker

1SDA101808R1 ABB XT7L M 1250 Ekip G Touch LSIG 1250A 4P Circuit Breaker

ABB 1SDA101808R1 is a 1250 A four-pole XT7L M fixed moulded case circuit breaker with front terminals, stored-energy operation and an Ekip G Touch LSIG electronic trip unit for advanced generator, overload, short-circuit and earth-fault protection.

SKU: 1SDA101808R1MPN: 1SDA101808R1
Price
List Price £14,212.62 ex VAT
Your Price (ex VAT) Save 25%
£10,659.47 25% OFF
You save £3,553.16 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,659.47
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,659.47

Why Choose the ABB XT7L M 1250 Ekip G Touch LSIG Circuit Breaker?

The ABB XT7L M 1250 Ekip G Touch LSIG, order code 1SDA101808R1, is a high-performance four-pole moulded case circuit breaker from the ABB SACE Tmax XT7 range, engineered for generator and demanding low-voltage power-distribution applications. This configuration combines a 1250 A rated current with the advanced Ekip G Touch LSIG electronic trip unit.

The Ekip G Touch LSIG trip unit provides long-time, short-time, instantaneous and earth-fault protection, delivering comprehensive electronic protection for generator-connected and general distribution systems. Its touch interface supports convenient configuration and coordination of protection parameters, helping engineers achieve selective and dependable fault protection throughout complex electrical networks.

This XT7L M configuration is supplied as a fixed four-pole circuit breaker with front terminals, together with stored-energy and lever operating mechanisms. With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, it provides robust protection for high-current systems with substantial prospective fault levels.

Key Advantages

  • High-capacity 1250 A moulded case circuit breaker for generator and power-distribution applications.
  • Advanced Ekip G Touch LSIG electronic trip unit for generator-oriented protection.
  • Long-time, short-time, instantaneous and earth-fault protection in one electronic release.
  • Touch interface supports convenient protection configuration and system coordination.
  • 120 kA ultimate breaking capacity at 415 V AC for installations with high prospective fault currents.
  • Four-pole fixed configuration with front terminals.
  • Stored-energy and lever operating mechanisms for dependable switching operation.

Key Features

  • ABB SACE Tmax XT7 series.
  • 1250 A rated current.
  • 690 V AC rated operational voltage.
  • Ekip G Touch LSIG solid-state electronic trip unit.
  • LSIG protection functions: long-time, short-time, instantaneous and earth-fault.
  • 1000 V rated insulation voltage.
  • 8 kV rated impulse withstand voltage.
  • Four-pole fixed construction with front terminals.
  • 120 kA Icu and Ics at 415 V AC.
  • IP20 degree of protection.

Advanced Generator Protection for High-Current Distribution Systems

Generator-connected and high-current industrial networks require circuit breakers capable of safely interrupting severe fault currents while providing precise electronic protection. The ABB XT7L M combines a 1250 A current rating with 120 kA breaking capacity at 415 V AC, providing robust protection for demanding generator, transformer and main distribution applications.

The Ekip G Touch LSIG electronic trip unit combines long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection within an advanced touch-based platform. This combination supports effective protection coordination and helps safeguard generators, conductors, switchgear and connected equipment while limiting the impact of faults on unaffected sections of the electrical network.

Typical Applications

  • Generator protection and generator switchboards.
  • Standby and emergency power systems.
  • Main low-voltage distribution boards.
  • Industrial switchboards and high-current power-distribution systems.
  • Transformer secondary and feeder protection.
  • Systems requiring integrated overload, short-circuit and earth-fault protection.

Technical Specifications

Series SACE Tmax XT7
ABB order code 1SDA101808R1
GTIN/EAN 8056221018524
Product type Moulded case circuit breaker
Frame XT7 M
Performance class XT7L
Rated current 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 8 kV
Trip unit Ekip G Touch LSIG
Protection functions Long-time, short-time, instantaneous and earth-fault
Poles 4
Mounting type Fixed
Terminal arrangement Front terminals
Operating mechanism Stored energy and lever operation
Ultimate breaking capacity at 415 V AC 120 kA
Service breaking capacity at 415 V AC 120 kA
Ultimate breaking capacity at 690 V AC 50 kA
Rated short-time withstand current 20 kA
Power loss per pole 57 W
Mechanical durability 20,000 cycles
Degree of protection IP20
Motor drive Optional
Standard IEC 60947-2
ABB product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA101808R1?

The ABB 1SDA101808R1 is an XT7L M fixed four-pole moulded case circuit breaker rated at 1250 A and equipped with an Ekip G Touch LSIG electronic trip unit.

What protection functions does the Ekip G Touch LSIG provide?

The Ekip G Touch LSIG provides long-time, short-time, instantaneous and earth-fault protection, represented by the L, S, I and G protection functions.

Is the ABB XT7L M 1250 Ekip G Touch LSIG suitable for generator protection?

Yes. The Ekip G Touch LSIG is designed for generator and installation protection, making this breaker suitable for generator switchboards and other demanding low-voltage distribution systems.

What is the breaking capacity of the ABB 1SDA101808R1?

The breaker provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC and 50 kA at 690 V AC.

Where is the ABB XT7L M 1250 Ekip G Touch LSIG typically used?

It is typically used in generator switchboards, standby power systems, industrial main distribution boards, transformer systems and high-current feeders requiring advanced LSIG electronic protection.

Trusted ABB Protection for Generator and Industrial Power Systems

ABB SACE Tmax XT circuit breakers combine high short-circuit interruption performance with advanced electronic protection technology, providing dependable protection for generators and demanding industrial low-voltage power-distribution systems.