ABB 1SDA101804R1 XT7L M 1250 is a 1250 A four-pole fixed moulded case circuit breaker with an Ekip G Dip LS/I solid-state electronic trip unit, front terminals and stored-energy operating mechanism for demanding generator and low-voltage power-distribution protection.
£6,313.57
The ABB 1SDA101804R1 is a high-performance SACE Tmax XT7L M moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power systems. This fixed four-pole circuit breaker combines a 1250 A rated current with ABB’s Ekip G Dip LS/I solid-state electronic trip unit, providing overload and short-circuit protection for generator and power-distribution applications.
As part of the ABB SACE Tmax XT range, the XT7L M 1250 is engineered for installations requiring high interruption performance and dependable electronic protection. The Ekip G Dip LS/I release provides long-time, short-time and instantaneous protection functions, while its generator-oriented Ekip G configuration makes it suitable for power-generation and associated distribution circuits.
The 1SDA101804R1 features a four-pole fixed configuration with front terminals, an XT7M frame and a stored-energy operating mechanism. Its XT7L performance level belongs to ABB’s 120 kA interruption class, providing robust protection for high-current installations where substantial prospective short-circuit currents may occur.
The ABB Tmax XT7L M platform is engineered for high-current electrical systems where dependable fault interruption is essential. With its 1250 A rated current and XT7L 120 kA interruption class, the 1SDA101804R1 provides a robust protective solution for generator circuits, incoming supplies and major distribution feeders exposed to significant prospective short-circuit currents.
The Ekip G Dip LS/I solid-state trip unit provides long-time, short-time and instantaneous protection functions. This combination protects against sustained overloads and different levels of short-circuit current while supporting coordinated protection strategies in generator and industrial power-distribution systems.
| Series | SACE Tmax XT |
|---|---|
| Order code | 1SDA101804R1 |
| GTIN / EAN | 8056221018487 |
| Product type | Moulded case circuit breaker |
| Frame size | XT7M |
| Performance level | XT7L |
| Rated current | 1250 A |
| Number of poles | 4 |
| Trip unit | Ekip G Dip LS/I |
| Release type | Solid-state electronic |
| Protection functions | Long-time, short-time and instantaneous |
| Interruption rating | L |
| Interruption class | 120 kA |
| Mounting type | Fixed |
| Terminal connection | Front terminals |
| Operating mechanism | Stored energy |
| Standard | IEC |
| Product weight | 15.5 kg |
| Country of origin | Italy |
| Application | Generator and low-voltage power-distribution protection |
The ABB 1SDA101804R1 is a 1250 A four-pole moulded case circuit breaker designed for protection and switching in demanding generator and low-voltage power-distribution applications.
The breaker is fitted with an Ekip G Dip LS/I solid-state electronic trip unit, providing long-time, short-time and instantaneous protection functions.
LS/I identifies the principal protection functions provided by the trip unit: long-time (L), short-time (S) and instantaneous (I) protection. This configuration protects against overload and short-circuit conditions without an LSIG ground-fault protection function.
The 1SDA101804R1 uses ABB’s XT7L performance level, identified by an L interruption rating and belonging to the 120 kA interruption class for demanding low-voltage power systems.
The 1SDA101804R1 is a fixed four-pole circuit breaker with front terminals and a stored-energy operating mechanism, designed for integration into low-voltage switchboards and power-distribution assemblies.
ABB SACE Tmax XT circuit breakers combine high short-circuit interruption performance with Ekip electronic protection technology, providing dependable protection for generators, industrial switchboards, major feeders and critical low-voltage power-distribution systems.