ABB 1SDA101749R1 is an XT7H M 1600 four-pole fixed moulded case circuit breaker rated at 1600 A with front terminals and an Ekip G Dip LS/I electronic trip unit for generator protection.
£6,771.62
The ABB XT7H M 1600 Ekip G Dip LS/I, order code 1SDA101749R1, is a high-performance SACE Tmax XT moulded case circuit breaker designed specifically for generator protection in demanding low-voltage electrical systems. This XT7H M configuration combines a rated uninterrupted current of 1600 A with ABB's Ekip G Dip LS/I electronic protection technology.
The Ekip G Dip LS/I trip unit is engineered for generator applications, providing adjustable overload and short-circuit protection with time-delay functionality. This allows the breaker to protect generating equipment and associated distribution circuits while accommodating the distinctive operating and fault-current characteristics of generator-fed systems.
The 1SDA101749R1 is supplied as a four-pole, fixed circuit breaker with front terminals. Its XT7H 70 kA performance class, 1600 A current rating and generator-specific electronic protection make it a robust choice for generator switchboards, standby power systems and other high-current generation applications.
Generator-fed electrical systems require protection characteristics that account for the operating behaviour and fault-current capabilities of generating equipment. ABB's Ekip G technology is developed for generator applications, enabling appropriate overload and short-circuit protection while supporting coordinated operation between the generator, circuit breaker and downstream distribution system.
The Ekip G Dip LS/I release provides adjustable overload and short-circuit protection with time-delay functionality. Combined with the 1600 A rating, four-pole construction, front terminals and XT7H high-performance breaker platform, the 1SDA101749R1 provides a robust solution for generator switchboards, standby generation and distributed power installations.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA101749R1 |
| EAN | 8056221017930 |
| Product type | Moulded case circuit breaker for generator protection |
| Frame / configuration | XT7H M |
| Performance level | XT7H |
| Rated uninterrupted current (Iu) | 1600 A |
| Trip unit rated current (In) | 1600 A |
| Number of poles | 4 |
| Trip unit | Ekip G Dip LS/I |
| Protection application | Generator protection |
| Release type | Electronic |
| Overload adjustment range | 640–1600 A |
| Delayed short-circuit adjustment range | 960–16000 A |
| Instantaneous short-circuit adjustment range | 1600–16000 A |
| Rated voltage | 690 V |
| Performance class | 70 kA |
| Mounting configuration | Fixed |
| Terminal arrangement | Front terminals |
The ABB 1SDA101749R1 is an XT7H M 1600 SACE Tmax XT moulded case circuit breaker designed for generator protection, rated at 1600 A and supplied with four poles, fixed mounting, front terminals and an Ekip G Dip LS/I electronic trip unit.
The Ekip G Dip LS/I electronic trip unit is designed for generator protection and provides adjustable overload and short-circuit protection with time-delay functionality.
The breaker has a rated uninterrupted current and trip-unit rated current of 1600 A.
The Ekip G Dip LS/I trip unit provides an overload adjustment range of 640–1600 A.
The 1SDA101749R1 belongs to ABB's XT7H 70 kA performance class, providing high short-circuit performance for demanding generator protection applications.
The ABB 1SDA101749R1 is a four-pole circuit breaker, making it suitable for generator systems requiring four-pole switching and protection.
This model is supplied in a fixed configuration with front terminals for installation in compatible low-voltage generator and distribution switchboards.
ABB SACE Tmax XT circuit breakers are widely specified in industrial, commercial, infrastructure and power-generation applications where dependable high-current protection, advanced electronic releases and robust short-circuit performance are required.