ABB 1SDA101544R1 XT7L M 1250 is a fixed three-pole SACE Tmax XT moulded-case circuit breaker with a 1250 A Ekip G Touch LSIG electronic trip unit, front terminals and 120 kA ultimate and service breaking capacity at 415 V AC.
£8,459.86
The ABB XT7L M 1250 Ekip G Touch LSIG, order code 1SDA101544R1, is a high-performance SACE Tmax XT moulded-case circuit breaker designed for advanced generator, transformer and installation protection. This fixed three-pole breaker combines the XT7L M platform with an Ekip G Touch LSIG electronic trip unit and a rated uninterrupted current of 1250 A.
The Ekip G Touch LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions through ABB's advanced electronic protection platform. Its generator-oriented functionality makes the breaker particularly suitable for power-generation and critical distribution applications where precise protection, system coordination and dependable fault interruption are required.
The XT7L M 1250 is supplied in a fixed three-pole configuration with front terminals and incorporates stored-energy and lever operating mechanisms. It provides both ultimate and service short-circuit breaking capacities of 120 kA at 415 V AC, together with a rated operational voltage of 690 V AC, making it suitable for demanding high-current installations with substantial prospective fault levels.
Generator, transformer and high-capacity distribution circuits require carefully coordinated protection against overload, short-circuit and earth-fault conditions. Electronic trip technology enables protection characteristics to be matched to the requirements of the electrical system, helping limit damaging fault energy while maintaining effective coordination with other protective devices.
The Ekip G Touch LSIG release combines generator-oriented electronic protection with the robust XT7L platform. Together with the 1250 A rating, 120 kA ultimate and service breaking capacity at 415 V AC and fixed front-terminal configuration, the 1SDA101544R1 provides a comprehensive solution for critical high-current power systems.
| Series | SACE Tmax XT |
|---|---|
| Order code | 1SDA101544R1 |
| EAN | 8056221015882 |
| Product type | Moulded-case circuit breaker |
| Application | Transformer, generator and installation protection |
| Frame | XT7 |
| Sub-type | XT7M |
| Breaking-performance version | XT7L |
| Rated current | 1250 A |
| Rated uninterrupted current | 1250 A |
| Number of poles | 3 |
| Trip unit | Ekip G Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and ground fault |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 8 kV |
| Ultimate breaking capacity at 415 V AC | 120 kA |
| Service breaking capacity at 415 V AC | 120 kA |
| Ultimate breaking capacity at 690 V AC | 50 kA |
| Service breaking capacity at 690 V AC | 50 kA |
| Rated short-time withstand current | 20 kA |
| Short-circuit performance level | L |
| Installation | Fixed |
| Terminal arrangement | Front terminals |
| Operating mechanism | Stored-energy and lever operating mechanisms |
| Power loss per pole at rated operating conditions | 57 W |
| Standard | IEC 60947-2 |
The ABB 1SDA101544R1 is an XT7L M 1250 fixed three-pole SACE Tmax XT moulded-case circuit breaker equipped with a 1250 A Ekip G Touch LSIG electronic trip unit and front terminals.
The breaker has a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC, making it suitable for demanding high-current low-voltage systems.
The Ekip G Touch LSIG electronic release provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection for generator and electrical distribution applications.
The XT7L M 1250 provides both ultimate and service short-circuit breaking capacities of 120 kA at 415 V AC and 50 kA at 690 V AC.
The breaker is supplied as a fixed three-pole unit with front terminals and incorporates stored-energy and lever operating mechanisms for integration into high-current switchboard assemblies.
ABB SACE Tmax XT circuit breakers combine high short-circuit breaking performance with advanced electronic protection for demanding generator, transformer, industrial and commercial electrical distribution systems.