ABB 1SDA101541R1 XT7L M 1600 is a 1600 A three-pole fixed moulded case circuit breaker with front bolt connections, 120 kA ultimate breaking capacity at 400 V AC and an Ekip G Dip LS/I electronic trip unit for generator and low-voltage distribution protection.
£5,907.85
The ABB XT7L M 1600 Ekip G Dip LS/I, order code 1SDA101541R1, is a high-performance three-pole moulded case circuit breaker (MCCB) designed for generator protection and demanding low-voltage power distribution applications. Part of the ABB SACE Tmax XT7 family, it combines a 1600 A rated uninterrupted current with the generator-oriented Ekip G Dip LS/I electronic trip unit.
The Ekip G Dip LS/I trip unit provides long-time, short-time and instantaneous protection functions for safeguarding generators, feeders and distribution circuits against overload and short-circuit conditions. Its adjustable electronic protection allows the breaker response to be coordinated with the requirements of the protected electrical system.
With a 1600 A rated uninterrupted current, 690 V rated voltage, three-pole configuration, fixed construction and front bolt connections, the 1SDA101541R1 is engineered for high-current switchboard applications. The XT7L version provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, making it suitable for installations with substantial prospective fault currents.
Generator-fed electrical systems can have different operating and fault-current characteristics from utility-fed networks, making appropriately coordinated protection essential. The ABB Ekip G Dip LS/I electronic trip unit provides adjustable long-time, short-time and instantaneous protection, enabling the XT7L M 1600 to protect generator circuits and associated distribution equipment against overload and short-circuit conditions.
The combination of a 1600 A rated uninterrupted current, 690 V rated voltage and 120 kA ultimate breaking capacity at 400 V AC makes the 1SDA101541R1 suitable for demanding generator switchboards and high-current distribution systems. Its fixed front-connected construction and optional motor operator capability also support integration into modern low-voltage switchboards requiring dependable protection and flexible switching arrangements.
| Series | SACE Tmax XT |
|---|---|
| Order code | 1SDA101541R1 |
| EAN / GTIN | 8056221015851 |
| Product type | Moulded case circuit breaker |
| Frame | XT7 M |
| Performance level | L |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated voltage | 690 V |
| Number of poles | 3 |
| Trip unit | Ekip G Dip LS/I |
| Trip-unit technology | Electronic |
| Protection functions | Long-time, short-time and instantaneous |
| Overload release adjustment range | 640–1600 A |
| Short-time delayed short-circuit release range | 960–16000 A |
| Instantaneous short-circuit release range | 1600–16000 A |
| Ultimate breaking capacity (Icu) at 400 V AC, 50 Hz | 120 kA |
| Integrated ground-fault protection | No |
| Installation | Fixed |
| Main circuit connection | Bolt connection |
| Connection position | Front |
| Operating element | Toggle |
| Optional motor operator | Yes |
| Integrated motor operator | No |
| DIN rail mounting | No |
| Degree of protection | IP20 |
| Power loss | 94 W |
The ABB 1SDA101541R1 is a 1600 A three-pole moulded case circuit breaker designed for generator protection and demanding high-current low-voltage power distribution applications.
The breaker is fitted with an Ekip G Dip LS/I electronic trip unit providing long-time, short-time and instantaneous protection functions for generator and distribution circuits.
The overload release is adjustable from 640–1600 A, the short-time delayed short-circuit release from 960–16000 A, and the instantaneous short-circuit release from 1600–16000 A.
The ABB XT7L M 1600 has an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, 50 Hz, providing high fault-interruption capability for demanding electrical installations.
The 1SDA101541R1 is a fixed three-pole circuit breaker with front bolt connections. An optional motor operator can be fitted where electrically operated switching is required.
ABB SACE Tmax XT circuit breakers combine advanced electronic protection, high fault-breaking performance and flexible system integration for demanding generator, industrial and commercial low-voltage power distribution applications.