Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA101531R1 XT7L M 1000 is a fixed three-pole SACE Tmax XT motor-protection moulded-case circuit breaker with a 1000 A Ekip M Dip I electronic trip unit, front terminals and 120 kA ultimate and service breaking capacity at 415 V AC.
£4,702.59
The ABB XT7L M 1000 Ekip M Dip I, order code 1SDA101531R1, is a high-performance SACE Tmax XT moulded-case circuit breaker for motor protection. This fixed three-pole breaker combines the XT7L M platform with an Ekip M Dip I electronic trip unit and a rated current of 1000 A, providing dedicated short-circuit protection for demanding high-power motor circuits.
The Ekip M Dip I electronic release is intended for motor-protection applications and provides adjustable short-circuit protection. Its adjustable characteristics allow protection to be coordinated with the starting behaviour and separate overload protection of large motors, helping distinguish normal motor starting currents from genuine high-current fault conditions.
The XT7L M 1000 is supplied in a fixed three-pole configuration with front terminals and incorporates stored-energy and lever operating mechanisms. ABB specifies the XT7L M Ekip M Dip I family in the 120 kA class, with this 1000 A version providing both ultimate and service short-circuit breaking capacities of 120 kA at 415 V AC.
Large industrial motors can draw substantial current during starting, so motor-circuit protection must accommodate normal starting conditions while responding effectively to genuine short-circuit faults. Adjustable electronic short-circuit protection supports coordination with contactors, starters and separate overload protection while providing rapid interruption when dangerous fault currents occur.
The Ekip M Dip I release combines dedicated motor short-circuit protection with the high-breaking-performance XT7L platform. Together with its 1000 A rating, 120 kA ultimate and service breaking capacity at 415 V AC and fixed front-terminal configuration, the 1SDA101531R1 provides a robust solution for high-power motor feeders in demanding industrial installations.
| Series | SACE Tmax XT |
|---|---|
| Order code | 1SDA101531R1 |
| EAN | 8056221015752 |
| Product type | Moulded-case circuit breaker for motor protection |
| Frame | XT7 |
| Breaking-performance version | XT7L |
| Rated current | 1000 A |
| Rated uninterrupted current | 1000 A |
| Number of poles | 3 |
| Trip unit | Ekip M Dip I |
| Release type | Solid-state electronic release |
| Short-time short-circuit adjustment range | 600–10000 A |
| Instantaneous short-circuit adjustment range | 1000–10000 A |
| Integrated earth-fault protection | No |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 8 kV |
| Ultimate breaking capacity at 415 V AC | 120 kA |
| Service breaking capacity at 415 V AC | 120 kA |
| Ultimate breaking capacity at 690 V AC | 50 kA |
| Service breaking capacity at 690 V AC | 50 kA |
| Rated short-time withstand current | 20 kA |
| Power loss per pole at rated operating conditions | 37 W |
| Installation | Fixed |
| Terminal arrangement | Front terminals |
| Main-circuit connection | Bolted connection |
| Motor drive | Optional |
| Degree of protection | IP20 |
The ABB 1SDA101531R1 is an XT7L M 1000 fixed three-pole SACE Tmax XT moulded-case circuit breaker for motor protection, equipped with a 1000 A Ekip M Dip I electronic trip unit and front terminals.
The circuit breaker has a rated current and rated uninterrupted current of 1000 A, making it suitable for high-current three-phase motor-protection applications.
The Ekip M Dip I is a solid-state electronic motor-protection release providing adjustable short-circuit protection, intended for motor circuits where overload protection is coordinated separately.
The XT7L M 1000 provides rated ultimate and service short-circuit breaking capacities of 120 kA at 415 V AC and 50 kA at 690 V AC.
The breaker is supplied as a fixed three-pole unit with front terminals and bolted main-circuit connections. An optional motor drive can be used where automated operation is required.
ABB SACE Tmax XT motor-protection circuit breakers combine high short-circuit breaking performance with dedicated electronic protection to help safeguard critical motor feeders in demanding industrial electrical systems.
We use cookies