ABB 1SDA101521R1 is a SACE Tmax XT7L M 1600 A three-pole fixed moulded case circuit breaker with front connections and an Ekip Touch Measuring LSIG electronic trip unit providing advanced LSIG protection and integrated electrical measurement.
£7,896.28
The ABB XT7L M 1600 Ekip Touch Measuring LSIG, order code 1SDA101521R1, is a high-performance three-pole moulded case circuit breaker (MCCB) designed for demanding low-voltage power distribution applications. Part of the ABB SACE Tmax XT family, this configuration combines a 1600 A rated current with the advanced Ekip Touch Measuring LSIG solid-state electronic protection release.
The Ekip Touch Measuring LSIG trip unit provides long-time, short-time, instantaneous and earth-fault protection together with integrated electrical measurement functionality. This combination supports precise circuit protection, monitoring and protection coordination in sophisticated industrial, commercial and infrastructure power distribution systems.
The XT7L M configuration combines a three-pole design with fixed construction and front terminal connections. Its L performance level provides 120 kA short-circuit breaking performance, making this 1600 A breaker particularly suitable for switchboards and distribution systems with very high prospective fault currents.
The ABB XT7L M provides comprehensive protection for high-current electrical distribution circuits where precise fault protection and electrical measurement are required. Its Ekip Touch Measuring LSIG release combines long-time, short-time, instantaneous and earth-fault protection with integrated measurement functionality, supporting effective protection coordination and improved visibility of electrical system conditions.
Combining a 1600 A current rating with 120 kA L-level short-circuit performance, fixed construction and front terminal connections makes this XT7L configuration particularly suitable for demanding industrial and infrastructure switchboards where very high prospective fault currents require exceptional interruption capability.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA101521R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | XT7 |
| Performance level | L |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 3 |
| Trip unit | Ekip Touch Measuring LSIG |
| Release type | Solid-state electronic release |
| Protection functions | Long-time, short-time, instantaneous and earth fault (LSIG) |
| Measurement functionality | Integrated electrical measurement |
| Overload protection adjustment range | 640–1600 A |
| Short-time short-circuit adjustment range | 960–16000 A |
| Instantaneous short-circuit adjustment range | 2400–24000 A |
| Rated voltage | 690 V AC |
| Short-circuit breaking performance | 120 kA |
| Mounting / version | Fixed |
| Terminal position | Front |
| Degree of protection | IP20 |
| Power dissipation | 94 W |
| Optional motor operator | Yes |
| Standard | EN/IEC 60947-2 |
The ABB 1SDA101521R1 is a SACE Tmax XT7L M three-pole fixed moulded case circuit breaker rated at 1600 A and equipped with an Ekip Touch Measuring LSIG solid-state electronic protection release.
The Ekip Touch Measuring LSIG release provides long-time, short-time, instantaneous and earth-fault protection together with integrated electrical measurement functionality.
The circuit breaker has a rated current and rated uninterrupted current of 1600 A, making it suitable for demanding high-current low-voltage distribution applications.
The XT7L M is an L performance-level breaker with 120 kA short-circuit breaking performance, making it suitable for electrical installations with very high prospective fault currents.
The electronic release provides an overload adjustment range of 640–1600 A, a short-time short-circuit adjustment range of 960–16000 A and an instantaneous short-circuit adjustment range of 2400–24000 A.
The ABB 1SDA101521R1 is a three-pole circuit breaker intended for three-phase low-voltage electrical distribution systems.
This model is a fixed circuit breaker with its main circuit connections positioned at the front.
ABB SACE Tmax XT moulded case circuit breakers are used across industrial, commercial and infrastructure power systems where advanced electronic protection, integrated electrical measurement, exceptional short-circuit performance and dependable switching are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.